A Study on Correction of the Protective Relay Equipped in the Dedicated Line Used for Connecting Distributed Generators to Power Network

분산전원 계통 연계 전용선로에 설치된 보호 계전기의 정정에 관한 연구

  • Jeong, Jong-Chan (Department of Electrical and Computer Engineering, Kangwon National University) ;
  • Jang, Sung-Il (Department of Electrical and Computer Engineering, Kangwon National University) ;
  • Choi, Don-Man (Department of Electrical and Computer Engineering, Kangwon National University) ;
  • Kim, Kwang-Ho (Department of Electrical and Computer Engineering, Kangwon National University)
  • 정종찬 (강원대학교 전기전자정보통신공학부) ;
  • 장성일 (강원대학교 전기전자정보통신공학부) ;
  • 최돈만 (강원대학교 전기전자정보통신공학부) ;
  • 김광호 (강원대학교 전기전자정보통신공학부)
  • Published : 2002.11.15

Abstract

This paper describes the correction of the protective relay equipped in the dedicated line used for connecting distributed generators (DG) to power grid. The fault current measured in a relaying point might be changed according to the fault conditions. Generally, the fault current of the line to line fault or the line to ground fault at the dedicated line is much higher than the protective set value due to the large fault level. However. when the high impedance fault is occurred in the dedicated line, we may not detect it because its fault level can be lower than the generating capacity of DG. And, the protective relay with conventional set value may generate a trip signal for insertion of DG due to the large transient characteristics of generators. Through the various simulations such as the fault in the dedicated line and the insertion of DG, we show that it would be necessary to modify the protective relay set value for detecting the high impedance fault occurred in the dedicated line and for preventing the mis-operation of protective relay caused by the insertion of DG.

Keywords