• 제목/요약/키워드: COS(Cut Out Switch)

검색결과 14건 처리시간 0.02초

Embedded 기술을 이용한 COS MEMS 시스템 설계 (COS MEMS System Design with Embedded Technology)

  • Hong, Seon Hack;Lee, Seong June;Park, Hyo Jun
    • KEPCO Journal on Electric Power and Energy
    • /
    • 제6권4호
    • /
    • pp.405-411
    • /
    • 2020
  • In this paper, we designed the COS MEMS system for sensing the falling detection and explosive noise of fuse link in COS (Cut Out Switch) installing on the power distribution. This system analyzed the failure characteristics and an instantaneous breakdown of power distribution. Therefore, our system strengths the industrial competence and guaranties the stable power supply. In this paper, we applied BLE (Bluetooth Low Energy) technology which is suitable protocol for low data rate, low power consumption and low-cost sensor applications. We experimented with LSM6DSOX which is system-in-module featuring 3 axis digital accelerometer and gyroscope boosting in high-performance mode and enabling always-on low-power features for an optimal motion for the COS fuse holder. Also, we used the MP34DT05-A for gathering an ultra-compact, low power, omnidirectional, digital MEMS microphone built with a capacitive sensing element and an IC interface. The proposed COS MEMS system is developed based on nRF52 SoC (System on Chip), and contained a 3-axis digital accelerometer, a digital microphone, and a SD card. In this paper of experiment steps, we analyzed the performance of COS MEMS system with gathering the accelerometer raw data and the PDM (Pulse Data Modulation) data of MEMS microphone for broadcasting the failure of COS status.

과전류 차단과 보호협조 성능이 향상된 한류형 COS 퓨즈링크 개발 (Development of Current Limiting COS Fuse Link with Improved Overcurrent and Protection Coordination performance)

  • 김윤현;김영주
    • 한국산학기술학회논문지
    • /
    • 제21권3호
    • /
    • pp.129-136
    • /
    • 2020
  • 컷아웃스위치(COS: Cut Out Switch 이하 COS)는 전력계통에서 수용가로 전력을 송배전하기 위해 사용되는 변압기의 입력단에 설치되어 사고전류로부터 변압기를 보호하기 위해 설치되는 보호장치이다. COS는 크게 퓨즈링크와 COS몸체 및 접속부로 구성되어 사고전류시 퓨즈링크의 엘리먼트가 용단되어 사고전류를 차단하는 역할을 한다. COS 퓨즈링크가 용단되어 발생하는 강력한 아크가 화염과 소음을 유발시켜 주변지역 거주자에게 불쾌감 및 공포감을 주며, 아크화염으로 인하여 주변기기의 2차 피해를 유발시킬 수 있다. 본 논문에서는 COS 동작 시 발생되는 아크와 소음 및 보호협조의 문제점을 해결하기 위해 폭발형이 아닌 한류형 COS 퓨즈를 개발하였다. 또한 과전류 차단 기능이 없는 한류형 퓨즈의 단점을 개선하기 위해 퓨즈 엘리멘트, 스트라이커와 COS 퓨즈금구 개발을 통하여 과전류 차단성능의 신뢰성을 향상시켰다. COS의 동작 특성 향상은 퓨즈 엘리멘트의 최적 형상 도출, 스트라이커의 원활한 동작을 위한 동작선의 재질과 두께 및 저항 산정, 그리고 스트라이커와 연계된 하부금구류의 구조 개선을 통하여 수행하였다. 본 연구에서 개발한 COS 퓨즈링크는 공인기관의 시험을 통하여 차단성능과 보호협조 성능을 검증하였다. 시험은 본 연구의 한류형 COS와 기존의 폭발형 비한류형 COS의 비교 시험으로 수행하였다.

고전압 COS 퓨즈용 소음기의 소음저감 및 전류차단 성능에 관한 실험적 연구 (An Experimental Study on the Noise Reduction and the Feasibility of Short Current of a Silencer for a High Voltage COS Fuse)

  • 이동훈;송화영
    • 한국소음진동공학회논문집
    • /
    • 제18권7호
    • /
    • pp.783-789
    • /
    • 2008
  • This experimental study describes the noise reduction and the feasibility of short current of a silencer for a high voltage COS(cut out switch) fuse of a transformer. When a high voltage COS fuse becomes a short circuit by the over current, the strong impulse noise over 150 dB(A) is generated. For the purpose of the reduction of impulse noise, in this study, the diffuser type and the reactive type silencers have been designed and tested, respectively. And also the electrical test on the short current is performed. From the experimental results, the well designed reactive type silencer has been shown to have the noise reduction of about 20 dB(A). It has been found that the feasibility of short current for the COS fuse is closely related to the porosity of the silencer.

COS LoRa 기반의 임베디드 시스템 설계 (Embedded System Design with COS LoRa technology)

  • 홍선학;조경순;윤진섭
    • 디지털산업정보학회논문지
    • /
    • 제14권3호
    • /
    • pp.29-38
    • /
    • 2018
  • It is the approach of embedded system design that analyzes COS(Cut Out Switch) failure in the power distribution and an instantaneous breakdown of power distribution supply could cause the weakness of industrial competence and therefore we need to feed the stable power distribution with developing the technology of open-source embedded system. In this paper, we apply the LoRa technology which is the Internet of Things(IoT) protocol for low data rate, low power, low cost and long range sensor applications. We designed the hardware and software architecture setup and experimented the embedded system with network architecture and COS monitoring system including accelerometer for detecting the failure of distribution line and sensing the failure of its fuse holder by recognizing the variation and collision and afterwards sending the information to a gateway. With experimenting we designed the embedded platform for sensing the variation and collision according to the COS failure, monitoring its fuse holder status and transferring the information of states with LoRa technology.

염진해 특성이 향상된 COS의 개발에 관한 연구 (Research and development of advanced COS for anti-contamination)

  • 김인성;한동희;안명상;조한구;강동필;황동석
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1994년도 하계학술대회 논문집 C
    • /
    • pp.1599-1602
    • /
    • 1994
  • Recently, failure of COS(cut out switch) due to contamination has been increased. This paper is on the development of the contamination COS. 1 We designed a porcelain insulator of alternate shed for anti-contamination COS. 2 The COS was coated with HVIC(silicone) to improve resistivity to contamination. 3 The FOV characteristics of COS were examined to obtain dry FOV, wet FOV and contamination FOV.

  • PDF

고전압 COS 퓨즈로부터 방사된 충격성 소음의 전파특성과 저감에 관한 실험적 연구 (An Experimental Study on the Propagation Characteristics and Reduction of Impulse Noises from a High Voltage COS Fuse)

  • 송화영;주경민;이동훈;강내국;정낙헌
    • 한국소음진동공학회:학술대회논문집
    • /
    • 한국소음진동공학회 2005년도 추계학술대회논문집
    • /
    • pp.71-74
    • /
    • 2005
  • This experimental study describes the propagation characteristics and reduction of impulse noises emitted from a high voltage COS(Cut Out Switch) fuse of a transformer. When a high voltage COS fuse becomes a short circuit by the over current. The peak sound Pressure above 150dB(A) is generated. In this study, an impulse noise generator is designed for generating the impulse noises similar to the noise level of COS fuse, which is utilized to test the noise reduction of a reactive silencer. The reactive silencers have been tested for 10 different types with each different porosity, hole diameter and length. From the experimental results, it is found that the reactive silencer has an excellent performance to greatly suppress the impulse noise and that its performance is closely connected with the porosity and hole diameter.

  • PDF

다공판이 내장된 반사형 소음기의 소음저감 성능 (Noise Reduction Performance of a Reactive type Silencer with Perforated Panels)

  • 이선기;이영철;송화영;이동훈
    • 한국소음진동공학회:학술대회논문집
    • /
    • 한국소음진동공학회 2007년도 추계학술대회논문집
    • /
    • pp.1415-1418
    • /
    • 2007
  • When a high voltage COS fuse becomes a short circuit by the over current, the impulse noise over 150 dB(A) with the strong pulse jet is radiated from the COS fuse of an electric transformer. For the purpose of the impulse noise reduction, in this study, a reactive type silencer with perforated panels are considered. The transmission loss of the silencer are calculated by transfer matrix method. The effect of the porosity, the distance between panels, and the number of perforated panel on the sound transmission loss is investigated and discussed.

  • PDF

고전압 COS 퓨즈로부터 방사된 충격성 소음 저감용 반사형 소음기의 설계 (Reactive Silencer Design for Suppressing Impulse Noise from a High Voltage Cut Out Switch Fuse)

  • 송화영;김덕한;이종석;이동훈
    • 한국소음진동공학회:학술대회논문집
    • /
    • 한국소음진동공학회 2006년도 춘계학술대회논문집
    • /
    • pp.951-954
    • /
    • 2006
  • This Study introduces the design of a reactive type silencer for reducing impulse noises emitted from a high voltage COS fuse of a transformer. When a high voltage COS fuse becomes a short circuit by the over current, the peak sound pressure level above 150dB(A) is generated at the distance of 2m from a COS Fuse. For the purpose of the reduction of impulse noise, in this study. the reactive type silencers have been utilized. The performance of noise reduction for them can be expressed by insertion loss. The reactive silencers have been tested for 23 different types with each different porosity, hole diameter and depth. From the experimental results, it is found that the reactive silencer has an excellent performance to greatly suppress the impulse noise. The one-stage, two-stage and three-stage reactive type silencers have been shown to have the insertion losses of about from 35dB (A) to 25dB(A).

  • PDF

애자의 소음 분석을 통한 애자 고장 탐지 가능성 연구 (A Study on Possibility of Detection of Insulators' Faults by Analyses of Radiation Noises from Insulators)

  • 박규칠;윤종락;이재훈
    • 한국음향학회지
    • /
    • 제28권8호
    • /
    • pp.822-831
    • /
    • 2009
  • 애자는 송전선 시스템에서 전기적으로나 기계적으로 매우 중요한 소자이다. 송전선 시스템에 설치된 이후 애자의 열화 등에 의해 고장이 난 애자를 찾아내기 위해 애자로 부터의 방사 소음을 측정하여 분석하였다. 대상으로 한 제품은 2종류의 현수 애자, COS, 2종류의 Line Poster, 피뢰기이며, 이들 제품의 정상 상태와 고장 상태의 방사 소음을 각각 측정하여 시간 파형, 주파수 스펙트럼, 피크 검출의 결과를 서로 비교하여 그 차이점을 제시하였다. 또한, 이를 바탕으로 방사 소음으로부터 고장 상태의 애자의 검출의 가능성 및 그 방법을 제시하였다.

흡음장치를 내장한 고전압 퓨즈홀더의 최적설계에 관한 연구 (Optimum Design of High Voltage Fuse Holder with a Built-in Acoustic Absorber System)

  • 진영준;이해원;황유섭
    • 한국안전학회지
    • /
    • 제26권1호
    • /
    • pp.8-14
    • /
    • 2011
  • Noise and vibration are likely to disturb the sensory system of human body leading to psychological stress and thereby property damage. In this research, a cut out switch(COS) with a built-in acoustic absorber along with a COS fuse broken was developed to reduce percussion noise. This new system is based on a design approach that combines existing absorber systems: expansion type, resonator type, and acoustic absorber type silencer The noise performance of the new system was simulated using the $SYSNOISE^{TM}$ software under optimized parameters: the diameter of perforated plate 2 mm, the plate thickness 3 mm, the width of expansion room 25 mm, the impinging vortex room 14 mm, and the noise absorbtion room 10 mm. The results showed that it reduced noise by approximately 41.1 dB compared to the current systems available in the market. Furthermore, it showed reduced noise by approximately 12 dB more than a product with an acoustic absorber of the Fault Tamer(USA).