An Experimental Study on the Propagation Characteristics and Reduction of Impulse Noises from a High Voltage COS Fuse

고전압 COS 퓨즈로부터 방사된 충격성 소음의 전파특성과 저감에 관한 실험적 연구

  • 송화영 (서울산업대학교 에너지환경대학원) ;
  • 주경민 (서울산업대학교 에너지환경대학원) ;
  • 이동훈 (서울산업대학교 소음진동연구센터) ;
  • 강내국 (서울산업대학교 에너지환경대학원 에너지시스템공학과) ;
  • 정낙헌 (한국전력공사)
  • Published : 2005.11.01

Abstract

This experimental study describes the propagation characteristics and reduction of impulse noises emitted from a high voltage COS(Cut Out Switch) fuse of a transformer. When a high voltage COS fuse becomes a short circuit by the over current. The peak sound Pressure above 150dB(A) is generated. In this study, an impulse noise generator is designed for generating the impulse noises similar to the noise level of COS fuse, which is utilized to test the noise reduction of a reactive silencer. The reactive silencers have been tested for 10 different types with each different porosity, hole diameter and length. From the experimental results, it is found that the reactive silencer has an excellent performance to greatly suppress the impulse noise and that its performance is closely connected with the porosity and hole diameter.

Keywords