Abstract
The porcelain insulators are important devices, that are used to isolate electrically and hold mechanically in the high-voltage power transmission systems. The faults of the insulators induce very serious problems to the power transmission line. In this paper, we introduce techniques for fault detections of insulators by acoustic radiation noises from them. We measured radiation noises from normal state insulators and fault state insulators. The used insulators were two different type porcelain insulators, a cut out switch, two different type line posters, and a lightning arrester. Each results was compared each other in time domain, frequency domain and filter banks' outputs. We found the possibility of detection of insulators' faults and also suggested techniques for fault detections.
애자는 송전선 시스템에서 전기적으로나 기계적으로 매우 중요한 소자이다. 송전선 시스템에 설치된 이후 애자의 열화 등에 의해 고장이 난 애자를 찾아내기 위해 애자로 부터의 방사 소음을 측정하여 분석하였다. 대상으로 한 제품은 2종류의 현수 애자, COS, 2종류의 Line Poster, 피뢰기이며, 이들 제품의 정상 상태와 고장 상태의 방사 소음을 각각 측정하여 시간 파형, 주파수 스펙트럼, 피크 검출의 결과를 서로 비교하여 그 차이점을 제시하였다. 또한, 이를 바탕으로 방사 소음으로부터 고장 상태의 애자의 검출의 가능성 및 그 방법을 제시하였다.