DOI QR코드

DOI QR Code

An Experimental Study on the Noise Reduction and the Feasibility of Short Current of a Silencer for a High Voltage COS Fuse

고전압 COS 퓨즈용 소음기의 소음저감 및 전류차단 성능에 관한 실험적 연구

  • 이동훈 (서울산업대학교 기계공학과) ;
  • 송화영 (서울산업대학교 에너지환경대학원 에너지시스템공학과)
  • Published : 2008.07.20

Abstract

This experimental study describes the noise reduction and the feasibility of short current of a silencer for a high voltage COS(cut out switch) fuse of a transformer. When a high voltage COS fuse becomes a short circuit by the over current, the strong impulse noise over 150 dB(A) is generated. For the purpose of the reduction of impulse noise, in this study, the diffuser type and the reactive type silencers have been designed and tested, respectively. And also the electrical test on the short current is performed. From the experimental results, the well designed reactive type silencer has been shown to have the noise reduction of about 20 dB(A). It has been found that the feasibility of short current for the COS fuse is closely related to the porosity of the silencer.

Keywords

References

  1. Song, H. Y., Ju, K. M., Lee, D. H., Kang, R. G. and Jung, N. H., 2005, 'An Experimental Study on the Propagation Characteristics and Reduction of Impulse Noises from a High Voltage COS Fuse', Proceeding of the KSNVE Annual Autumn Conference, pp. 71-74
  2. Song, H. Y., Kim, D. H., Lee, J. S. and Lee, D. H., 2006, 'Reactive Silencer Design for Suppressing Impulse Noises from a High Voltage Cut Out Switch Fuse', Proceeding of the KSNVE Annual Spring Conference
  3. Song, H. Y., Kim, D. H., Lee, J. S. and Lee, D. H., 2006, 'An Experimental Study on the Control of Duration time of Impulse Noise from a High Voltage COS Fuse', Proceeding of the KSNVE Annual Autumn Conference
  4. Song, H. Y., 2004, 'An Experimental Study on the Propagation Characteristics and Reduction of Impulse Noises', Master's Degree Paper in the Graduate School of Energy and Environment, Seoul National University of Technology
  5. KEPCO, 2001, 'KEPCO Standard Procurement Specifications - Special High Voltage Cut Out Switch', ES 151-961
  6. Institute of Electrical and Electrics Engineers (IEEE), 'IEEE Standard Design for High-voltage Fuses, Distribution Enclosed Single-pole Air Switches, Fuse Disconnecting Switched, and Accessories', IEEE Std C37.41-1994
  7. Jeong, G. C., Hyun, S. I., Lee, J. W. and Kwon, Y. P., 1994, 'Performance of Absorption Diffuser Silencers', Transactions of the Korean Society for Noise and Vibration Engineering, Vol. 4, No. 3, pp. 377-384
  8. Lee, D. H., Lee, D. H. and Kwon, Y. P., 1991, 'A Study on the Performance of a Perforated Tube Muffler with Air Flow', Proceeding of the KSNVE Annual Spring Conference, pp. 11-15