• 제목/요약/키워드: AVR step test

검색결과 13건 처리시간 0.023초

AVR 스템시험에 의한 울진 N/P 1호기 PSS 모델링 연구 (A Study of PSs Modeling of Ulchin N/P #1 by AVR Step Test)

  • 김동준;문영환;전동훈;김태균
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제50권8호
    • /
    • pp.351-358
    • /
    • 2001
  • This paper deals with the PSS modeling of Ulchin N/P #1 as well as the generator and excitation system modeling by utilizing the recorded data from AVR step test, which has been performed by entering small voltage signal into the AVR summing point. In addition to it. two recorded results obtained from the AVR step test with PSS sunning and without PSS running have not only been compared each other on the time domain, but also they heve been analyzed with FFT analysis on the frequency domain; thus, the desirable effects of running PSS in Ulchin N/P #1 on power system have been explicitly confirmed. Finally, the derived PSS model parameters lead to good matches between simulation results and recorded data.

  • PDF

MVR모드에서 AVR모드로의 절환에 의한 여자계 모델정수 결정 (Identification of Excitation System Model Parameters from the Test of Switching from MVR Mode to AVR Mode)

  • 김동준;문영환;최경선;류승헌;송석하;이홍택
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1996년도 추계학술대회 논문집 학회본부
    • /
    • pp.91-94
    • /
    • 1996
  • A simulation procedure was developed for identifying Yungnam unit 2 excitation model parameters to improve the accuracy of stability simulation of KEPCO. First, generator model parameters are derived by using modified load rejection technique from measured load rejection test. For identifying excitation model parameters, switch was changed from MVR mode to AVR mode in Yungnam unit 2 excitation system instead of applying to a small step to the voltage reference($V_{ref}$) because of saving time and efforts, assuming the test result would show coincided result with applying to a small step to the $V_{ref}$. However, it was found that the response of switching from MVR to AVR is greatly different from it of applying small signal to the $V_{ref}$. A simulation procedure was needed to take into accounts of real AVR component status before and after switching from MVR to AVR. This paper reports the procedure which duplicated the measured response and addresses the merits of this test on conventional AVR step test.

  • PDF

측정에 의한 울진 원자력 1호기 PSS 모델링 연구 (A Study of PSS Modelling of Ulchin Nuclear Plant Unit #1 by AVR Step Test)

  • 김동준;문영환;전동훈;김태균
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2000년도 추계학술대회 논문집 학회본부 A
    • /
    • pp.152-155
    • /
    • 2000
  • This paper deals with the PSS modelling of Ulchin N/P Unit #1 by utilizing the recorded data from AVR step test. In addition to it, the recorded results obtained from the AVR step test with PSS running and without PSS running are not only compared each other on the time domain but they are also analyzed with FFT on the frequency domain; the desirable effect of running PSS in Ulchin N/P Unit #1 is examined. Finally, the derived PSS model parameters lead to good matches between simulation results and recorded data.

  • PDF

축소형 5KVA 동기발전기 AVR/PSS 강건한 제어정수 설계 및 튜닝 (Design and Tuning of Micro 5KVA Machine's AVR/PSS Robust Control Parameters)

  • 김동준;문영환;김태균;신정훈
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2000년도 하계학술대회 논문집 A
    • /
    • pp.165-168
    • /
    • 2000
  • This paper describes the guideline of design and tuning of practical Micro 5KVA machine's digital AVR/PSS control parameters by using the computer models and testing on-line AVR step test of laboratory simulator under the no-load or load conditions. The suggested procedures can be also applied to the large scaled machine's AVR/PSS control parameter tuning in KEPCO system.

  • PDF

부하차단시험에 의한 서인천복합화력 발전기.제어계의 모델링 및 검증 (Modeling and verification of generator/control system of Seo-Inchon combined-cycle plant by load rejection test)

  • 최경선;문영환;김동준;추진부;류승헌;권태원
    • 대한전기학회논문지
    • /
    • 제45권4호
    • /
    • pp.501-510
    • /
    • 1996
  • The gas-turbine generator of Seo-Incheon combined-cycle plant was tested for derivation of a model for dynamic analysis. Load rejection and AVR step test was performed to get the dynamic response of generator. The parameters of generator/control system model were determined by these measured data. No-load saturation test was performed for the saturation characteristics of the generator under steady state. V-curve test was also performed so as to find exact generator parameters. Q-axis parameters of generator was derived by measuring power angle. AVR and governor constants have been tuned by their oscillatory period and setting time characteristics. The derived parameters of generator control system is verified by one-machine infinite bus system simulation. (author). 7 refs., 20 figs., 5 tabs.

  • PDF

다중-입력 PSS의 실제적인 튜닝 방법과 대형 전력 시스템에의 적용 (A Practical Tuning Method of Dual-Input PSS and its Application to Large Power System)

  • 김동준;문영환;허진;신정훈;김태균;추진부
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제51권7호
    • /
    • pp.362-370
    • /
    • 2002
  • This paper describes the practical tuning method of dual-input PSS and its application to Muju P/P #2 with Proto PSS, which is based on DSP technology and uses both frequency and power. First, the model parameters of generator system used in this paper have been derived from the generator characteristic testing. Then, in the selection of PSS parameters, the Bode plot is plotted in order to tune the PSS's time constants which are able to compensate the phase lagging due to generator and excitation system. In addition, the eigenvalue analysis is also performed for determining a reliable PSS gain, $K_{s}$. Finally, the transient stability program has been utilized to verify the safe operation of Proto PSS against the predictable disturbances such as the AVR-step test and generator unloading test. In on-site test, the simulated results have been identically duplicated by implementing AVR step test in Muju P/P #2 with Proto PSS, which has the previously designed PSS parameters.s.

A Biologically Inspired Intelligent PID Controller Tuning for AVR Systems

  • Kim Dong-Hwa;Cho Jae-Hoon
    • International Journal of Control, Automation, and Systems
    • /
    • 제4권5호
    • /
    • pp.624-636
    • /
    • 2006
  • This paper proposes a hybrid approach involving Genetic Algorithm (GA) and Bacterial Foraging (BF) for tuning the PID controller of an AVR. Recently the social foraging behavior of E. coli bacteria has been used to solve optimization problems. We first illustrate the proposed method using four test functions and the performance of the algorithm is studied with an emphasis on mutation, crossover, variation of step sizes, chemotactic steps, and the life time of the bacteria. Further, the proposed algorithm is used for tuning the PID controller of an AVR. Simulation results are very encouraging and this approach provides us a novel hybrid model based on foraging behavior with a possible new connection between evolutionary forces in social foraging and distributed non-gradient optimization algorithm design for global optimization over noisy surfaces.

A Practical Power System Stabilizer Tuning Method and its Verification in Field Test

  • Shin, Jeong-Hoon;Nam, Su-Chul;Lee, Jae-Gul;Baek, Seung-Mook;Choy, Young-Do;Kim, Tae-Kyun
    • Journal of Electrical Engineering and Technology
    • /
    • 제5권3호
    • /
    • pp.400-406
    • /
    • 2010
  • This paper deals with parameter tuning of the Power System Stabilizer (PSS) for 612 MVA thermal power plants in the KEPCO system and its validation in a field test. In this paper, the selection of parameters, such as lead-lag time constants for phase compensation and system gain, is optimized using linear and eigenvalue analyses. This is then verified through the time-domain transient stability analysis. In the next step, the performance of PSS is finally verified by the generator's on-line field test. After the field test, measured and simulated data are also compared to prove the effectiveness of the models used in the simulations.

복합화력발전소 가스터빈 발전기계통 모델정수 도출 및 검증을 위한 특성시험 (Characteristic Tests on the Gas Turbine Generator System for Determination and Verification of Model Parameters in a Combined Cycle Power Plant)

  • 김종구;유호선
    • 플랜트 저널
    • /
    • 제17권4호
    • /
    • pp.35-40
    • /
    • 2021
  • 본 연구에서는 서인천복합 6호기 가스터빈 발전기계통에 대하여 기술특성시험을 실시하여 모델정수를 도출하고 검증하였다. 발전기 최대/최소 무효전력 한계시험 결과 최대 무효전력 한계는 80 MVar이고, 최소 무효전력 한계는 -30 MVar이다. 발전기는 GENROU 모델을 사용하였고, 계자시정수(T'do)는 4.077 s, 관성정수(H)는 5.461 P.U로 결정하였다. 여자시스템은 ESST4B 모델을 사용, 무부하 2% AVR 스텝시험을 모의하는 방식으로 모델정수를 도출하고 검증하였으며, PSS 모델링은 PSS2A 모델정수로 도출하였고, PSS Off/On일때 측정된 계측 데이터를 모의, 비교하여 검증하였다. 조속기-터빈는 GGOV1 모델을 사용하여 모델정수를 도출하고 검증하였다. PSS/E 시뮬레이션 프로그램을 통해 10% 조속기 스텝시험을 모의하여 결정된 조속기-터빈 모델정수의 수치 안정성을 확인하였다.

RTDS를 이용한 PSS 현장 설치 모의 시험 (The trial installation test of PSS to Power Plant using Real Time Digital Simulator)

  • 허진;김동준;문영환;신정훈;김태균
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2002년도 하계학술대회 논문집 A
    • /
    • pp.59-62
    • /
    • 2002
  • Before a developed digital Power System Stabilizer(PSS) is installed to real power system, an efficient trial test for installing PSS is needed. In this paper, the performance of developed digital PSS for a single hydro-turbine generator and infinite bus system has been investigated using Real Time Digital Simulator(RTDS) in order to install PSS to real power system practically. The test system was composed of RTDS, three phase voltage/current amplifier and the PSS and the test scheme provided a very efficient way to verify the design and control performance of a PSS to be applied to real power system. The trial installation test through AVR 3% step test and three fault analysis may be guaranteed to install PSS to real power system.

  • PDF