In this study, a technical characteristic test was conducted on the gas turbine generator system of Seoincheon Combined cycle no.6 to derive and verify the model constants. As a result of the generator maximum/minimum reactive power limit test, the maximum reactive power limit is 80 MVar and the minimum is -30 MVar. The generator uses the GENROU model, the field time constant (T'do) is 4.077 s, and the inertial constant (H) is 5.461 P.U. Excitation system used ESST4B model to derive and verify model constants by simulating no-load 2% AVR step test, PSS modeling derived from PSS2A model constants, and simulated and compared measurement data measured when PSS off/on Did. The GGOV1 model was used for the governor-turbine, and the numerical stability of the determined governor-turbine model constant was verified by simulating a 10% governor step test through the PSS/E simulation program
Keywords
Characteristic test; Generator; Excitation system; Power System Stabilizer; Governor-turbine;
Citations & Related Records
연도 인용수 순위
  • Reference
1 김용학, 곽노홍, 손현일, 신정훈, 심응보, 오세일, 차승태, 최준호, 2007, 전력계통 안정성 향상을 위한 발전기 제어계 특성 시험 및 모델링, 대한전기학회, pp. 473
2 이용희, 2018, 발전기 모델정수 도출을 위한 부하각 보정 알고리즘에 관한 연구, 전남대학교, pp. 1
3 김동준, 2006, 발전기 안정도 해석 파라메타 도출 및 검증 기법 표준화 연구, 한국전력거래소, pp. 31
4 임승현, 2017, 발전기 기술특성시험을 이용한 발전기 모델정수 도출 및 검증, 충남대학교, pp. 2
5 산업통상자원부, 2019, 전력계통 신뢰도 및 전기품질 유지기준(고시 제2019-176호)
6 김상돈, 2014, 산업플랜트 동기발전기 운전특성 및 특성데이터 취득 시험 연구, 고려대학교, pp. 74
7 CWG & MVWG, 1997, Test Guidelines for Synchronous Unit Dynamic Testing and Model Validation, WECC. www.wecc.biz