• Title/Summary/Keyword: 22.9kV Cable

Search Result 146, Processing Time 0.031 seconds

Interface Effects and Dielectric Properties of 22.9kV XLPE sheets (22-9kV급 XLPE 시이트의 유전특성과 계면효과)

  • 이관우;이종복;황보승;박대희
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2000.11a
    • /
    • pp.441-444
    • /
    • 2000
  • In this paper, dielectric properties of XLPE sheets of 22kV cable with semiconducting and water were investigated. The breakdown strength of XLPE under rod/needle electrode were measured at without oil. It is found that the dielectric properties such tan$\delta$ of XLPE sheet dependence on semiconducting and water layer and are decreased much lower increase with temperature. The breakdown strength and the electrode effect are obtained as a function of thickness, and a equation for the sheet thickness dependent breakdown strength is also discussion.

  • PDF

Lightning Impulse Characteristics for 22.9kV Power Cable Before and After Cyclic Aging for 14days (14주기 열화에 따른 22.9kV 전력케이블의 Lightning-Impulse 특성분석)

  • Kim, We-Young;Heo, Jong-Cheol;Park, Tae-Gone
    • Proceedings of the KIEE Conference
    • /
    • 2005.07c
    • /
    • pp.2274-2276
    • /
    • 2005
  • Cyclic aging for 14days is performed to remove the large amount of the volatiles found in freshly manufactured cable. In this paper, we examined lightning impulse characteristics of power cable before and after cyclic aging for 14days. As the result, the breakdown voltage after aging was lower than that before aging, but the breakdown voltage after aging was higher than that before aging in TR CNCV-W $60mm^2$ power cable.

  • PDF

A Study on Lightning Surges in Underground Distribution Systems

  • Jung Chae-Kyun;Kim Sang-Kuk;Lee Jong-Beom
    • KIEE International Transactions on Power Engineering
    • /
    • v.5A no.2
    • /
    • pp.171-176
    • /
    • 2005
  • The effects of surge arresters for the protection of transmission systems against direct lightning strokes have already been reviewed by many researchers. However, their studies have not encompassed underground cable systems. Therefore, in this paper we investigate the 22.9kV combined distribution systems that have arresters and ground wires. In addition, we analyze the overvoltages on underground distribution cable sections when direct lightning strokes contact the overhead ground wire using EMTP. Finally, we discuss the effect of lightning strokes according to the change of cable length and installation of arresters. This study provides insulation coordination methods for reasonable system design in 22.9kV underground distribution cable systems.

The Accident Hazard and Material Analysis of Power Cable due to Thermal Stress under PL System (PL법 환경하에서 열 충격에 따른 전력케이블의 재료분석 및 사고위험성)

  • Kim, Young-Seok;Shong, Kil-Mok;Jung, Jin-Su;Jung, Jong-Wook;Kim, Sun-Gu;Kim, Sang-Hyun
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.57 no.1
    • /
    • pp.82-87
    • /
    • 2008
  • It is impossible to database(DB) the patterns of power cable events and cause analysis of faulted cable because the product liability(PL) law have been enforced in Korea, since 2002. In additions, simulation and pattern of power cable events are needed for DB system under accelerated deterioration. In this paper, we tested for resistance to cracking of cable below the 22.9kV class due to thermal stresses. This method of exam is following IEC 60811-3-1(Common test methods for insulating and sheathing materials of electric cables). From the results, The 22.9kV calss A power cable was discolored on the surface and significantly reduced in the longitudinal direction. As the thermal weight properties of A power cable was definitely varied, we are able to guess the problem of manufacture. If the cable was defect by the manufacture, the victims would be able to claim for damage in the PL system.

A Study on the Development of Corrosion Detecting System for 22.9 kV Distribution Power Line Insulation Cable (22.9kV 배전선로 절연전선의 부식 검출 시스템 개발에 대한 연구)

  • Kim, Yong-Jun;Oh, Yong-Cheul;Yi, Keon-Young
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.60 no.7
    • /
    • pp.1410-1416
    • /
    • 2011
  • A corrosion detecting system for 22.9 kV distribution power line insulation cable, which can travel autonomously along the live line, is proposed. Eddy current test method is employed to detect the corrosion, and the system developed here is capable of detecting internal corrosion of a ACSR-OC. Somewhat details of the electrical and mechanical mechanism of the system and traveling algorithm are introduced. Experimental results applied to the sample cables having artificial corrosion and the operating distribution lines are provided. From the result, we confirmed that the system is useful for detecting internal corrosion of a ACSR, and is expected to be a new non-destructive testing equipment in the area of diagnosis for the distribution power line.

A Electrical Characteristic Simulation and Test for the Steady and Transient State in the 22.9kV HTS Cable Distribution System. (22-9kV배전계통에 대한 초전도케이블의 정상 및 과도상태에 대한 전기적 특성 시험 및 시뮬레이션 결과 검토)

  • Lee, Geun-Joon;Hwnag, Si-Dol;Yang, Byeong-Mo;Lee, Hyun-Chul
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.58 no.12
    • /
    • pp.2316-2321
    • /
    • 2009
  • With rapid development of world economics, electricity demand in metropolitan area has been increased dramatically. HTS(High Temperature Superconducting) cable is one of most promising technology to solve the bottleneck of electric network. However, HTS cable is not considered as matured technology yet to power system planners because of its different characteristics with conventional metal conductors. This paper suggests the comparison results of HTS cable simulation and experiment on steady state operation, also give the simulation results on transient characteristics of HTS cable components. This results could devote not only to discuss the security of HTS cable operation, but also to design power system oriented HTS cable.

AC loss Measurement of Superconducting Power Cable (초전도 전력케이블의 교류손실 측정)

  • Hwang, Si-Dole;Hyun, Ok-Bae;Sohn, Song-Ho;Choi, Hyung-Sik
    • Proceedings of the KIEE Conference
    • /
    • 2005.07a
    • /
    • pp.524-526
    • /
    • 2005
  • As a research activity of the project of "Verification Test of Superconducting Power Cable", we measured the AC loss of a short length superconducting power cable. The rating and the length of the cable were 22.9kV, 1,250A and 2.2m. The voltage taps for measuring the AC loss were attached to both ends of the conductor of the superconducting cable. Through the voltage taps and a lock-in amplifier we measured the in-phase component of the voltage($V_x$) with the load current(I). The AC loss was measured by multiplying the in-phase component of the voltage($V_x$) by the load current(I). The value of the AC loss of the superconducting power cable was 1.18W/m/phase/kA at 77.3K, 1atm.

  • PDF

Considerations on the Propagation of Partial Discharge Pulse in 3-Phase Power Cable Systems including Cross-Bonding Joints (3상 전력케이블 크로스본딩 접속에서 부분방전 펄스 전파 특성 고찰)

  • Kim, Jeong-Tae;Kim, Dong-Uk;Kim, Ji-Hong
    • Proceedings of the KIEE Conference
    • /
    • 2011.07a
    • /
    • pp.1606-1607
    • /
    • 2011
  • In this study, the propagation characteristics of partial discharge(PD) pulses in the 3-phase cable systems including crossbonding joints were discussed. For the purpose, experiments for 22.9kV CNCV cables were performed using simulated PD pulses, and on-site partial discharge measurements were carried out for the 345kV XLPE cable system.

  • PDF

The Measurement of Electromagnetic Wave in Power Cable Tunnel of Underground Utility Tunnel (전력구 내 전자기파에 대한 작업 환경 측정)

  • Kang, Dae Kon;Park, Jai Hak
    • Journal of the Korean Society of Safety
    • /
    • v.34 no.1
    • /
    • pp.1-7
    • /
    • 2019
  • Electromagnetic measurements of the power cable tunnel were conducted from August 10 to 20, 2018, in the ${\bigcirc}{\bigcirc}$ city underground utility tunnel. During this period, the average temperature was $31.89^{\circ}C$ and the humidity was 67.56% in power cable tunnel. As a result of the electromagnetic measurement, the highest electric field was 25.3 V/m and the magnetic flux density was $42.6{\mu}T$. The average electric field was 18.56 V/m and the magnetic flux density was $29.32{\mu}T$ in the power cable tunnel. As a result of comparison with the electric equipment technical standard, the electric field in the power cable tunnel was 0.5% of the electric equipment standard and 35.2% of the magnetic flux density. It's similar value that electric field is about robotic vacuum(15.53 V/m), and magnetic flux density is similar value about capsule- type coffee machine ($23.07{\mu}T$). The number of cable lines and the size of the electromagnetic waves were not proportional to each other through comparison of cable lines in the power cable tunnel. It was confirmed that 154 kV, rather than 22.9 kV, could have a greater influence on occupational.

Diagnosis of power cable system based on the HFPD detection at on-site (HFPD 검출법을 이용한 지중 케이블 실선로 진단)

  • Lee, J.S.;Kim, C.S.;Lee, D.G.;Kong, C.H.;Seok, K.H.;Lee, K.W.
    • Proceedings of the KIEE Conference
    • /
    • 2004.05b
    • /
    • pp.97-100
    • /
    • 2004
  • HFPD(High Frequency Partial Discharge) measurement has been widely performed to diagnosis of cable system in the world although Korea just begin. The efficiency of measurement has been reported and proved by many researchers who are engaged in the diagnosis of high power apparatus. LG Cable has investigated the technology of diagnosis for cable system by means of PD measurement for 10 years. In this paper, PD measurement with portable device was performed to evaluate the quality of the 154kV transmission line and the 22.9kV XLPE cable line. Test results are shown that the HFPD detection technology is very attractive for the diagnosis of power cable system by high detection sensitivity at on-site.

  • PDF