• Title/Summary/Keyword: 접지임피던스의 주파수의존성

Search Result 17, Processing Time 0.036 seconds

Frequency-Dependent Grounding Impedances of Counterpoises Associated with Soil Resistivity (대지저항률에 따른 매설지선의 접지임피던스의 주파수의존성)

  • Kim, Tae-Ki;Choi, Young-Chul;Choi, Jong-Hyuk;Lee, Bok-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.24 no.5
    • /
    • pp.114-121
    • /
    • 2010
  • This paper deals with the frequency-dependent grounding impedances of counterpoises relevant to the soil resistivity, the length of counterpoises and the feeding point of test current. The grounding impedances of counterpoises buried in one-layered and two-layered soils were measured and analyzed in the frequency range from 1[kHz] to 10[MHz]. As a result, the frequency-dependent grounding impedances strongly depend on the soil resistivity, and the grounding impedances within the frequency of several tens [kHz] are capacitive behavior in high soil resistivity. When injecting the ground current to the end of counterpoise buried in soil with high resistivity, the grounding impedances in high frequency are increased.

Frequency Dependence of Impedance of the Grounding Grid (접지그리드의 접지임피던스의 주파수 의존성)

  • 이복희;이동문;엄주홍;김교운
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.17 no.5
    • /
    • pp.22-28
    • /
    • 2003
  • This paper describes the frequency dependence of the grounding impedance. In order to propose the evaluation method of the transient response of powered grounding systems, the grounding impedances were measured with varying the frequency of incoming currents by way of the variable frequency inverter and band pass filter. The magnitude and phase of the grounding impedance were analyzed in the frequency range of 20 [Hz]∼2.1[kHz]. The grounding impedance were increased with increasing the frequency of the test current. The grounding impedance at the frequency of 2[kHz] in the actual 22.9[kV] substation grounding system was approximately 3 times as large as the 60[Hz] grounding impedance. It was found that the frequency dependence of the grounding impedance is mainly subject to the inductive reactance of the grounding conductors. As a result, it is critical to determine the shape and size of grounding grid reducing the resultant inductance in grounding systems for lightning surge protection.

Frequency-Dependant Grounding Impedances According to the Length of Grounding Electrode and the Joint Position of Ground Conductors (접지전극의 길이 및 접지도선의 접속위치에 따른 접지임피던스의 주파수의존성)

  • Choi, Jong-Hyuk;Choi, Young-Chul;Cho, Sung-Chul;Lee, Bok-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.24 no.5
    • /
    • pp.37-43
    • /
    • 2010
  • When lightning surges with wide frequency spectrum and power converting devices are considered, it is desirable to evaluate grounding system performance by grounding impedances. This paper presents the measured results for frequency-dependent grounding impedance for the vertical grounding electrode and counterpoise on a scale of full size. Grounding impedances of vertical grounding electrodes and counterpoises give capacitive or inductive behaviors according to the length of grounding electrodes and soil resistivity. It is inefficient to extend the length of the grounding electrode in order to decrease the ground resistance, and when designing the grounding system, the consideration of the grounding impedance should be desirable. In order to reduce the grounding impedance of counterpoise, the grounding conductors are jointed at the center of counterpoises. It is effective to reduce the grounding impedance by connecting ground rods to counterpoises in parallel.

A Novel Method for Measuring the Ground Impedance using Variable Frequency Inverter (가변주파수 인버터를 이용한 접지임피던스의 새로운 측정기법)

  • 이복희;엄주홍
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.53 no.5
    • /
    • pp.253-257
    • /
    • 2004
  • In order to analyze the frequency dependance of ground impedance in grounding grids for lightning and surge protection, a novel method for measuring the ground impedance as a function of frequency were experimentally investigated. The experiments were carried out in rectangular grounding grids with $6{\times}8$ conductors of 22 $mm^2$ buried at a depth of 0.5 m. The test current was injected by the variable frequency inverter whose frequency is linearly controlled for the established period in the range of 5∼500 KHz. The amplitude and phase of ground impedance were calculated from the waveforms of the test current and ground potential rise measured by the band-pass filter tuned in a specific frequency. The frequency dependence of ground impedance was mainly caused by the inductive current flowing through grounding conductors over the frequency of 100 KHz. The proposed measurement method of ground impedance would be applicable to evaluate the transient response characteristics in lightning protection grounding systems.

Frequency-Dependent Resistivity and Relative Dielectric Constant of Soil on Water Content (수분함유량에 따른 토양의 저항률 및 비유전율의 주파수의존성)

  • Choi, Jong-Hyuk;Cha, Eung-Suk;Lee, Bok-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.24 no.1
    • /
    • pp.98-104
    • /
    • 2010
  • In order to evaluate the performance of a grounding system against lightning or fault currents including high frequency components, the grounding impedance should be considered rather than the steady state ground resistance. To evaluate the ground impedance, the frequency dependence of resistivity and relative dielectric constant of the soil have to be analyzed. This paper deals with the frequency dependence of the resistivity and relative dielectric constant of three types of soil on water content. As a result, the resistivity of soil is getting lower with increasing of water content. It is nearly independent of the frequency in the range less than 1[MHz], and is decreased over the frequency range above 1[MHz]. On the other hand, the relative dielectric constant is rapidly decreased with the frequency in the range less than 1[MHz], but it is nearly independent on the frequency over the range of 1[MHz]. It was found from the experiments that the frequency-dependant resistivity and relative dielectric constant of soil should be considered when designing the grounding systems for protection from lightning or switching surges.

Calculation Method of Transient Potential Rises of Horizontal Ground Electrodes Depending on Injection Point of the Ground Current (접지전류의 입사점에 따른 정보통신설비용 수평접지전극의 과도전위상승 계산 방법)

  • Ahn, Chang-Hwan
    • Journal of the Institute of Electronics and Information Engineers
    • /
    • v.51 no.12
    • /
    • pp.197-203
    • /
    • 2014
  • When the lightning current is injected to the ground system of information and communication facilities, analysis of the transient potential rise in the ground system is one of main factors to effectively design the ground system. The performance of grounding systems is normally estimated with the grounding impedance and the transient potential rise which represents the electrical characteristics of the grounding system. The method for calculating the grounding impedance depending on the injection point of the lightning current was proposed. The delta-gap source model was proposed to calculate the grounding impedance in the case that the lightning current is injected to the center of the horizontal ground electrode. A new program which is possible to apply the frequency-dependent soil parameters using the Debye model was developed, because a commercial program for analyzing the performance of the grounding system can not apply to the frequency-dependent soil parameters. The experiment was carried out to confirm the availability of the simulation results with the same condition. Finally, the transient potential rises of a horizontal ground electrode depending on the lightning current waveforms were analyzed by using the results of the grounding impedance which is associated with the frequency-dependent soil parameters.

Analysis of Transient Potential Rises of Horizontal Ground Electrodes Considering the Frequency-Dependent of Soil (토양의 주파수의존성을 고려한 정보통신설비용 수평접지전극의 과도전위상승 분석)

  • Ahn, Chang Hwan
    • Journal of the Institute of Electronics and Information Engineers
    • /
    • v.53 no.2
    • /
    • pp.147-153
    • /
    • 2016
  • The lightning protection of information and communication facilities is very important factor to improve a reliability of the action of these equipment. Especially the transient potential rise of ground electrode being injected with the lightning current is to be a basic data of the dielectric strength for both power and communication facilities so that more accurate analysis should be required. The transient potential rise can be calculated from the ground impedance and the ground impedance is strongly dependent upon the shape of the ground electrode and the frequency-dependence of soil. The Debye's equation which is able to calculate the characteristics of dielectrics is used to analyze the frequency-dependent of soil. Also, the method to calculate the transient potential rise from the ground impedance is specified in this paper. In order to analyze the transient potential rise resulting from calculations with Debye's equation, TLM(transmission line method) and case of ${\rho}$(resistivity)-constant are simulated, respectively. The length of a horizontal ground electrode is 30 m and simulations were performed at 10, 100, $1000{\Omega}{\cdot}m$ with the standard lightning current waveform. In result, the transient potential rise of horizontal ground electrode calculating with Debye's equation is lower than it of other models.

Make-up of Equivalent Circuit of Grounding System using Water Resistivity in Hemispherical Electrode System (반구형 전극계에서 물의 저항률을 이용한 접지시스템의 등가회로 구성)

  • Lee, Bok-Hee;Choi, Jong-Hyuk;Bae, Sung-Bae
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.22 no.8
    • /
    • pp.109-115
    • /
    • 2008
  • A design criterion of grounding systems is commonly based on the ground resistance measured with low frequency in Korea. When lightning surges which have high frequency components are injected into the grounding system, the grounding impedance is great]y different from the static grounding resistance. In order to investigate the effect of water resistivity on the high frequency performance of grounding systems, this paper presents the frequency-dependent admittance using water tank simulating the grounding system in different water resistivities. As a result, because of capacitive effect admittances and conductance are increased with increasing frequency in higher water resistivity of greater than 500[${\Omega}{\cdot}m$]. On the other hand, admittances and conductances are decreased with increasing frequency due to inductive effect in lower water resistivity of less than 500[${\Omega}{\cdot}m$]. The phase difference between the current and voltage increases in the range of 200[kHz] to 5[MHz]. Consequently, frequency-dependent performance of grounding systems is closely related to the soil resistivity, it is necessary to consider the effect of grounding system performance on the frequency and soil resistivity.

An Analysis of Potential Interference Effects in the Vicinity of a Vertical Ground Rod (수직 접지전극 주변에서 전위간섭 영향분석)

  • Cho, Yong-Seung;Yang, Soon-Man;Yoo, Yang-Woo;Lee, Bok-Hee
    • Proceedings of the KIEE Conference
    • /
    • 2011.07a
    • /
    • pp.1570-1571
    • /
    • 2011
  • 인접한 독립 접지전극에 접지전류가 인가된 경우 접지전극 상호간 전위간섭을 일으키게 된다. 상용주파수 접지전류에 대한 전위간섭은 많은 분석이 이루어 졌으나, 뇌서지와 같은 고주파수를 포함하는 접지전류에 대한 전위간섭의 분석은 충분히 수행되지 못하였다. 본 논문에서는 상호간 영향을 줄 수 있는 길이 4 m인 수직 접지전극을 대상으로 주파수에 따른 전위간섭의 영향을 분석하였으며, 수직 접지전극의 주변에 나타나는 대지표면전위와 함께 상호 비교 분석하였다. 그 결과, 전위간섭은 접지임피던스의 변화에 의존하는 경향성을 나타내었으며, 수직 접지전극 길이의 1.5배에 해당하는 이격거리에서 접지전극의 전위와 대지표면전위가 거의 일치하는 것으로 나타났다.

  • PDF

Frequency Dependence of Grounding Impedances of the Deeply-driven Ground Rods (심매설 접지전극의 접지임피던스의 주파수의존성)

  • Kim, Tae-Ki;Kang, Sung-Man;Lee, Bok-Hee
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2008.05a
    • /
    • pp.70-73
    • /
    • 2008
  • Grounding impedance depends on the frequency of current flowing into a grounding system. Especially, the lightning gives a broad frequency spectrum from low frequency up to 1 MHz. So the grounding impedance related to high frequency current like lightning should be measured with high frequency source. In this paper, we described the grounding impedances of deeply-driven ground rods of 10 ${\sim}$ 48 m long with respect to the frequency of injected currents and the feed point. For the experiments, we used the wideband power amplifier which can produce sinusoidal voltages with the frequency ranges of DC ${\sim}$ 250 MHz. As a result, the longer the ground rod is, the lower the ground resistance is. However the grounding impedance of deeply-driven ground rod in the range of higher frequency is significantly increased. As a consequence, it is important to evaluate the high frequency performance of grounding systems for lightning protection.

  • PDF