Frequency Dependence of Impedance of the Grounding Grid  

이복희 (인하대학교 전자전기공학부)
이동문 (인하대학교 전자전기공학부)
엄주홍 (인하대학교 전자전기공학부)
김교운 (운봉공업고등학교)
Publication Information
Journal of the Korean Institute of Illuminating and Electrical Installation Engineers / v.17, no.5, 2003 , pp. 22-28 More about this Journal
Abstract
This paper describes the frequency dependence of the grounding impedance. In order to propose the evaluation method of the transient response of powered grounding systems, the grounding impedances were measured with varying the frequency of incoming currents by way of the variable frequency inverter and band pass filter. The magnitude and phase of the grounding impedance were analyzed in the frequency range of 20 [Hz]∼2.1[kHz]. The grounding impedance were increased with increasing the frequency of the test current. The grounding impedance at the frequency of 2[kHz] in the actual 22.9[kV] substation grounding system was approximately 3 times as large as the 60[Hz] grounding impedance. It was found that the frequency dependence of the grounding impedance is mainly subject to the inductive reactance of the grounding conductors. As a result, it is critical to determine the shape and size of grounding grid reducing the resultant inductance in grounding systems for lightning surge protection.
Keywords
Grounding system; Grounding grid; Ground potential rise; Frequency dependence of grounding impedance; Ground Impedance;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 B.H. Lee, S.C. Lee, The Major Fundamental Technics for Grounding System, Uijae publishing company, 1999, p.64-69, 1981.
2 Muhammad. H. Rashid, Power Electronics, Prentice-Hall, 1993, pp.262-301.
3 Mohan, Undeland, Robbins, Power electronics, John Wiley & Sons, 1995, pp.626-638.
4 A. D. Papalexopoulos, A. P. Meliopoulos, "Frequency Dependent Characteristics of Grounding System", IEEE Trans. on PAS, Vol. 100, No. 4, pp.1918-1922, 1981.
5 I. D. Lu, R. M. Shier, "Application of a Digital Signal Analyzer to the Measurement of Power System Ground Impedance", IEEE Trans. on PAS, Vol. 100, No. 4, pp.1918-1922, 1981.
6 B.H. Lee, J.H. Eom, S.C. Lee, "A New Measurement Method of the Grounding Resistance Using a Low-pass Filter in Energized Substation", Trans. KIEE., Vol. 50C, No. 8, pp.387-393, 2001.
7 B.H. Lee, J.H. Eom, S.W. Kim, "Measurements of the Ground Resistance Using the Test Current Method in Powered Grounding System", Trans. KIEE., Vol. 51C, No. 8, pp.347-353, 2002.   과학기술학회마을