Abstract
When lightning surges with wide frequency spectrum and power converting devices are considered, it is desirable to evaluate grounding system performance by grounding impedances. This paper presents the measured results for frequency-dependent grounding impedance for the vertical grounding electrode and counterpoise on a scale of full size. Grounding impedances of vertical grounding electrodes and counterpoises give capacitive or inductive behaviors according to the length of grounding electrodes and soil resistivity. It is inefficient to extend the length of the grounding electrode in order to decrease the ground resistance, and when designing the grounding system, the consideration of the grounding impedance should be desirable. In order to reduce the grounding impedance of counterpoise, the grounding conductors are jointed at the center of counterpoises. It is effective to reduce the grounding impedance by connecting ground rods to counterpoises in parallel.
넓은 범위의 주파수 스펙트럼을 포함하고 있는 낙뢰나 전력변환 기기들을 고려할 때 접지시스템의 성능은 접지임피던스에 의해 평가되어야 한다. 본 논문은 실규모의 수직 접지전극과 매설지선에 대한 접지임피던스의 주파수 의존성에 대한 측정결과를 나타낸다. 수직 접지전극과 매설지선의 접지임피던스는 접지전극의 길이와 토양의 대지저항률에 따라 용량성 또는 유도성 특성을 나타내었으며, 단순히 접지저항을 낮추기 위해 접지전극의 길이를 증가시키는 것은 비효율적이며 접지임피던스를 고려한 접지설계가 요구된다. 또한 매설지선의 접지임피던스를 저감시키기 위해 접지도선은 매설지선의 중앙에 접속되어야 하며, 봉상 접지전극을 매설지선과 병렬로 설치하는 것이 접지임피던스의 저감에 효과적인 것으로 나타났다.