• Title/Summary/Keyword: 열원 시스템

Search Result 343, Processing Time 0.023 seconds

과열방지장치가 설치된 복합열원 난방시스템에 관한 연구 (A Study on Hybrid Heating System with Anti-Superheating Devices)

  • 박윤철;고광수;한유리
    • 한국태양에너지학회 논문집
    • /
    • 제27권2호
    • /
    • pp.19-27
    • /
    • 2007
  • The previous study was conducted to develop an air source multi heat pump system that could be operated with the solar collector and air source heat exchangers as heat source of the system. There is a winter-sowing problems in air source multi heat pump system when the outdoor temperature goes down under freezing point. The winter-sowing problem was solved by adapting R-22 refrigerant as working fluid in the previous study. However, when the system operated at high temperature, another problems are come out such as overheating of the solar collector outlet which lead to the superheat of the compressor inlet of the heat pump system. The condition could deteriorates a compressor in some case. In this study, we installed the anti-superheating devices on the previously developed system. As results of system performance test, COP of the system with anti-superheating technique is 2.4. It is a little improved COP compare to previous study's 2.23. In the results of multi heat source heating system, during operating solar collector, COP is relatively high between $200\;W/m^2$ and $400\;W/m^2$ solar intensity. It is recommended to extend the study on performance optimization with balancing the solar collect and capacity of compressor at higher solar irradiation conditions.

소규모 SCW 지중열 시스템의 난방시 지하수 온도 변화 특성에 관한 연구 (A Study on Specific of Ground Water Temperature Changes of the Small Scaled SCW GWHP System in Case of Heating)

  • 양승진;이원호;김주영;홍원화;안창환
    • 대한설비공학회:학술대회논문집
    • /
    • 대한설비공학회 2008년도 하계학술발표대회 논문집
    • /
    • pp.1347-1352
    • /
    • 2008
  • The SCW ground heat pump system releases ground energy from the ground water of ground heat exchanger. In other word, ground water is used to heating through releases ground energy which oneself has. But the thermal efficiency of system is going to down because repetitive process of ground water will lost ground energy in standing column well system and if heating load is continually increase, energy of ground water may be frozen or there are no benefits to use ground energy as it owes just little energy. To solve these problems, there are need to exchange water to the ground heat exchanger then the way will be used to maintain Efficiency continually as the way of to be supplied with fresh ground water into ground heat exchanger. However, this type causes waste of ground water. Therefore it is essential to discharge water to outside timely on a heat exchanger. Therefor through a study, find out the best time to discharge water to outside and exchange water to ground heat exchanger, and propose to the DB of design of the ground heat exchanger.

  • PDF

냉매를 작동유체로 사용하는 태양열 난방시스템에 관한 연구 (A study on the solar assisted heating system with refrigerant as working fluid)

  • 김지영;고광수;박윤철
    • 한국태양에너지학회 논문집
    • /
    • 제25권4호
    • /
    • pp.37-44
    • /
    • 2005
  • An experimental study was conducted to analyze performance of a heating system with variation of control logic of the system. The system uses a solar as heat source and composed with heat pump that uses R-22 as working fluid. The difference between the developed system and the commercially available heating system is working fluid. The solar assisted heating system which was widely distributed in the market uses water as a working fluid. It could be freezing in case of the temperature drops down under freezing point. The anti-freezing fluids such as methyl-alcohol or ethylene-glycol are mixed with the water to protect the freezing phenomena. However, the system developed in this study uses a refrigerant as a working fluid. It makes the system to run under zero degree temperature conditions. Another difference of the developed system compare with commercial available one is auxiliary heating method. The developed system has removed an auxiliary electric heater that has been used in conventional solar assisted heating system. Instead of the auxiliary electric heater, an air source heat exchanger which generally used as an evaporator of a heat pump was adapted as a backup heating device of the developed system. As results, an efficiency of the developed system is higher than a solar assisted heat pump with auxiliary electric heater. The merit of the developed system is on the performance increment when the system operates at a lower solar energy climate conditions. In case of the developed system operates at a normal condition, COP of the solar collector driven heat pump is higher than the air source heat exchanger driven heat pump's.

멀티존 온돌난방제어를 위한 필요공급온수온도 산출법에 관한 연구 (A Study on the Required Supply Water Temperature Calculating Method for the Control of Multizone Radiant Floor Heating System)

  • 최정민;이규남;류성룡;김용이;여명석;김광우
    • 설비공학논문집
    • /
    • 제19권1호
    • /
    • pp.77-85
    • /
    • 2007
  • One of the most common approaches to achieve better thermal comfort with the radiant floor heating system is supply water temperature control, which is that supply water temperature is varied with outdoor air temperature. But the application of this control method was not easy, because there has been no way to determine the supply water temperature. So in this study, a comprehensive, yet simple calculation method to find out the required supply water temperature is suggested by combining the building heat loss equation and the heat emission model of hydronic radiant floor heating system for single zone. And then using this calculation method, the multizone control method is suggested and confirmed through the thermal simulation. It is shown that indoor air temperature is stably maintained around the set point.

적외선 램프를 이용한 비접촉식 태양전지셀 솔더링 장치 개발에 관한 연구 (A Study on the Development of Noncontact Soldering Device of PV Cells Using Infrared Lamp)

  • 노태정;김선진;박민용
    • 한국산학기술학회논문지
    • /
    • 제14권1호
    • /
    • pp.45-50
    • /
    • 2013
  • Photopia를 활용하여 적외선 램프 반사부의 각 형상에 대한 조도 분포를 해석하여 최적인 원호 형상으로 설계하였다. 적외선 온도센서를 통해 태양전지셀의 솔더링 온도를 피드백 받아서 설정된 솔더링 온도 프로파일과의 오차를 제어값으로서 IR 램프의 전류를 실시간으로 제어하는 솔더링 온도의 폐루프 제어시스템을 구현하였다. HMI 조작반에 의해 쉽게 운전되고, PLC와 IR 램프 제어기에 의하여 강인하게 제어되는 IR 램프 열원을 사용한 태양전지셀의 비접촉식 솔더링 장치를 개발하였다.

현장타설말뚝형 에너지 파일의 시공형태별 지중 열교환량에 관한 연구 (The Effect of Construction Methods on Geothermal Exchange Rates of Cast-in-place Energy Piles)

  • 박용부;남유진;심영종;손정락
    • 토지주택연구
    • /
    • 제3권2호
    • /
    • pp.169-175
    • /
    • 2012
  • 최근, 지열 냉난방 시스템의 초기 공사비를 절감하기 위해 연구되고 있는 에너지 파일의 열교환량을 산정하기 위해 2종류(부속연결형, 슬링키형)의 현장타설말뚝형(PRD, 시공심도 4.5m, 직경 1,200mm) 에너지 파일을 시험시공하고 수치 시뮬레이션에 의해 효율을 상호 비교하였다. 상호 비교결과에 의하면 지중 교환량은 운전시작과 함께 채열에 의한 지중온도의 저하에 의해 점점 감소하였고 부속연결형의 평균 열원수의 온도차는 난방운전에서 $0.37^{\circ}C$, 냉방운전에서 $0.34^{\circ}C$로 나타났다. 또, 부속연결형의 난방운전시 열교환량 231.4W/m보다 냉방운전의 방열량은 252.2W/m로서 9% 높았고 슬링키형은 난방 기간 평균 열교환량이 168.0W/m로 부속연결형에 비해 약 27% 낮은 열교환량을 얻었다.

고온냉매 우회방법을 적용한 열펌프의 성능 개선 연구 (A Study on Performance Improvement of Heat Pump Adopting the Hot Gas Bypass Method)

  • 강신형;변주석
    • 에너지공학
    • /
    • 제15권4호
    • /
    • pp.235-242
    • /
    • 2006
  • 본 연구는 공기 열원 열펌프의 성능 향상을 위한 연구로써 제상 방법으로 고온냉매 우회방법을 사용하고 내부열교환기를 장착한 열펌프 시스템의 성능을 ISO5151의 표준제상 조건에서 실험하였다. 실험은 고온냉매 우회방법과 가장 일반적인 제상 방법인 시간주기 제상방법을 비교하였으며 착상 발생 후 압축기 출구의 고온냉매를 실외기 입구로 우회시킬 때 실외기 홴 속도를 정상속도에 대하여 0%, 30%, 60%, 90%로 변화 시키면서 열펌프의 성능변화를 관찰하였다. 연구결과 210분의 열펌프 가동시간 동안 고온냉매 우회방법은 시간주기 제상방법 보다 $2.2{\sim}6%$ 높은 평균 성능계수를 나타냈으며 고온냉매 우회방법에서는 실외기의 홴 속도가 60%일 때 가장 좋은 성능계수와 난방용량을 나타냈다.

지역난방 급탕공급 부하균등화를 위한 잠열축열조의 현장 적용 (Field Application of a Latent Heat Storage Tank for Load Shaving of Domestic Hot Water Supply in District Heating)

  • 박성용;유호선
    • 플랜트 저널
    • /
    • 제17권2호
    • /
    • pp.42-47
    • /
    • 2021
  • 지역난방의 운영적 측면에서 특정시간의 피크부하 완화를 통한 효율적인 열생산과 공급 및 지역난방 공급 중단 시 급탕 공급은 난방 대비 대체가 어려워 사용자 측면의 불편함과 공급자 측면의 애로사항을 해결할 수 있는 적용 기술이 요구되고 있다. 본 연구에서는 이러한 문제점을 해결할 수 있는 기술 중 열저장 능력과 급탕공급에 적합한 78℃급 수화물계 잠열축열조를 제작하여 지역난방 사용자 아파트 급탕공급설비에 현장 적용하였다. 본 시스템의 적용 결과 기존 공급방식 대비 급탕온도의 변화가 거의 없이 일정하게 사용자에게 공급됨을 확인하였으며, 피크 열부하는 평균 35% 감소와 비상열원으로서의 활용 가능성을 확인하였다. 또한 부하균등화에 따른 피크부하 감소로 기존 열 공급시설에서 10%의 열공급 여유와 신규 열공급시설 건설비용 및 열사용자의 공사비부담금이 각 5%와 10%가 감소됨을 확인하였다.

에너지플러스 시뮬레이션을 통한 하천수 열원 히트펌프 시스템의 적용 가능성 분석 (An Applicability Analysis of River Water Source Heat Pump System using EnergyPlus Simulation)

  • 손병후
    • 한국지열·수열에너지학회논문집
    • /
    • 제18권2호
    • /
    • pp.10-21
    • /
    • 2022
  • A water source heat pump (WSHP) system is regarded as an energy-efficiency heating and cooling supply system for buildings due to its high energy efficiency and low greenhouse gas emissions. Recently, water sources such as river water, lake water, and raw water are attracting attention as heat sources for a heat pump system in Korea. This paper analyzed the applicability of a river water source heat pump system (RSHP). The river water temperature level was compared with the outdoor air and ground temperature levels to present applicability. In addition, the cooling and heating performance were compared through a simulation approach for the RSHP and a ground source heat pump (GSHP) applied to a large-scale office building. To compare the temperature level, the actual data were applied to the river water and the outdoor air, while the simulation results were applied to the ground circulation water. The results showed that the change in river water temperature throughout the year was similar to the change in outdoor air temperature. However, unlike the outdoor air temperature, the difference between the hourly and daily average river water temperatures was not large. The temperature level of river water was lower during the heating season and somewhat higher during the cooling season than that of the ground circulation water. Finally, the performance of the RSHP system was 13.4% lower than that of the GSHP system on an annual-based.

단일심정 지열히트펌프의 수치적 모델링 Part I: 수치해석 모델 검증 (Numerical Simulation of Standing Column Well Ground Heat Pump System Part 1: Validation of the Numerical Model)

  • 박두희;김광균;곽동엽;장재훈;박시삼
    • 한국지반공학회논문집
    • /
    • 제26권2호
    • /
    • pp.33-43
    • /
    • 2010
  • 지열은 고효율 신재생에너지로 각광을 받고 있으며 건축물의 냉난방 설비 시스템으로 활용이 점차 확산되고 있다. 지열 히트펌프 중에서 지하수를 열원으로 사용하는 단일심정(Standing column well)은 특히 효율이 높고 초기설치비용이 저렴하며 국내 지반 수리조건에 적합하다. 반면, 국내에는 아직 SCW의 성능을 평가할 수 있는 수치해석 모델이 없으며 국내 자료를 적용한 수치해석이 수행된 바 없다. 본 연구에서는 SCW 수치해석 모델을 유한체적해석 프로그램을 이용하여 구축하였다. 수치적 모델은 수리 열 연계해석을 수행하여 열이류, 대류, 전도를 모두 모사한다. SCW 모델은 미국과 국내에서 계측된 현장 데이터를 통하여 검증하였다. 비교 결과 본 연구에서 구축된 수치해석 모델은 정확하게 SCW의 거동을 예측할 수 있는 것으로 나타났다. 검증된 수치해석 모델은 동반논문에서 매개변수연구에 활용되었다.