Browse > Article

A Study on Hybrid Heating System with Anti-Superheating Devices  

Park, Youn-Cheol (Faculty of Mechanical Energy and System Engineering, Cheju National University)
Ko, Gwang-Soo (Department of Mechanical Engineering, Cheju National University)
Han, Yu-Ry (Department of Mechanical Engineering, Cheju National University)
Publication Information
Journal of the Korean Solar Energy Society / v.27, no.2, 2007 , pp. 19-27 More about this Journal
Abstract
The previous study was conducted to develop an air source multi heat pump system that could be operated with the solar collector and air source heat exchangers as heat source of the system. There is a winter-sowing problems in air source multi heat pump system when the outdoor temperature goes down under freezing point. The winter-sowing problem was solved by adapting R-22 refrigerant as working fluid in the previous study. However, when the system operated at high temperature, another problems are come out such as overheating of the solar collector outlet which lead to the superheat of the compressor inlet of the heat pump system. The condition could deteriorates a compressor in some case. In this study, we installed the anti-superheating devices on the previously developed system. As results of system performance test, COP of the system with anti-superheating technique is 2.4. It is a little improved COP compare to previous study's 2.23. In the results of multi heat source heating system, during operating solar collector, COP is relatively high between $200\;W/m^2$ and $400\;W/m^2$ solar intensity. It is recommended to extend the study on performance optimization with balancing the solar collect and capacity of compressor at higher solar irradiation conditions.
Keywords
heat pump; winter-sowing; anti-superheating;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 Y. H. Kang, Y. S. Yang, 'Development of Solar Technology in Korea,' Solar Energy, Vol. 18, No. 2, pp. 1-7, 1998   DOI   ScienceOn
2 C. D. Kim, I. J. Hwang, T. W. Lee, J. Lee 'Performance of a Heat Pump System with Solar Thermal Storage,' SAREK 1999 Winter Conference, pp. 265-272, 1999
3 J. Y. Kim, G. S. Ko, Y. C. Park, 'A Study on the Operating strategic for Solar Assisted Heating System with Refrigerant as Working Fluid,' Journal of the Korea Solar energy Society, Vol. 25, No. 4, pp. 37-44, 2005
4 C. D. Kim, L. W. Nam J. Lee, 'An Operation Characteristics Study of the Solar Source Inverter Heat Pump,' SAREK 1999 Summer Conference, pp. 521-526, 1999
5 H. Z. Abou-Ziyan, M. F. Ahmed, M. N. Metwally and H. M. Abd E-Hameed, 'Solar-assisted R22 and R134a Heat Pump Systems for Low-temperature Applications ,' Applied Thermal Engineerirg, Vol. 17, No. 5, pp. 455-469, 1997   DOI   ScienceOn
6 Xu Guoying, Zhang Xiaosong, Deng Shiming, 'A Simulation Study on the Operating Performance of a Solar-air Source Heat Pump Water Heater,' Applied Thermal Engineering, Vol. 26, pp. 1257-1265, 2006   DOI   ScienceOn
7 G. S. Ko, J. Y. Kim, Y. C. Park, 'Solar Assisted and Air Heat Source using Multi Source Heat Pump System,' The Korea Society Power System Engineering 2005 Winter Conference, pp. 67-72, 2005