• Title/Summary/Keyword: 순간 화재

Search Result 69, Processing Time 0.02 seconds

A Characteristics of Smoke Layer Formation Affected Periodicity of Fire Plumes (Plume의 주기성이 연층형성에 미치는 영향)

  • 한용식;김명배;오광철;신현동
    • Fire Science and Engineering
    • /
    • v.16 no.2
    • /
    • pp.38-42
    • /
    • 2002
  • This experiment is to understand a characteristics of smoke layer formation affected periodicity of fire plumes. The ON-OFF jet was used to constitute the oscillating flow, which was formed by a mixture of nitrogen gas with kerosene particles. The instantaneous images was obtained by digital video camera using laser sheet technique. The results were confirmed that the smoke layer in the near fire source comprise vortices which are formed by impingement from the periodicity of fire plume. The periodic impinging of plumes were thickened the smoke layer and produced the back-flow.

A Visualization of Smoke Front under a Horizontal Plate (평판하 연기선단의 가시화)

  • 한용식;김명배;오광철;유상필
    • Fire Science and Engineering
    • /
    • v.15 no.1
    • /
    • pp.41-46
    • /
    • 2001
  • The flow induced by a vertically impinging circular jet under a horizontal plate is investigated by visualization technique, using kerosene smoke in nitrogen gas to visualize the vortex flow and impinging flow. The light source was the sheet beam of Ar-Ion laser. The vertical and horizontal images scattering of kerosene smoke were recorded by the high speed CCD camera and the video camera. The instantaneous velocity of the vortex and the mean velocity of the smoke front were measured from the acquisited images.

  • PDF

Study on the Flash Point and Spontaneous Ignition Determination of 2-Propanol and O-xylene Mixtures (2-프로판올과 O-xylene 혼합물질의 인화점과 자연발화 측정에 관한 연구)

  • Kim, Tae-Young;Mok, Yeon-Su;Choi, Jae-Wook
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2011.11a
    • /
    • pp.360-363
    • /
    • 2011
  • 본 연구는 2-Propanol과 O-xylene의 혼합물의 인화점과 자연발화에 관한 연구이다. 인화점의 경우 2-Propanol과 O-xylene의 혼합비를 변화하여 측정하였으며, 2-Propanol은 $12^{\circ}C$를 구하였고, O-xylene는 $32^{\circ}C$를 구하였다. 자연발화의 경우 2-Propanol과 O-xylene의 농도를 변화시켜 혼합한 시료를 만들어 최저발화온도와 순간발화온도를 측정하였다.

  • PDF

The tracking of a smoke front under a ceiling by a laser sheet and thermocouples (Laser와 열전대를 이용한 연기선단의 위치 추적 비교에 관한 연구)

  • 김명배;한용식;윤명오;김진곤
    • Fire Science and Engineering
    • /
    • v.12 no.3
    • /
    • pp.11-20
    • /
    • 1998
  • A new experimental technique using a laser sheet and thermocouples is introduced to evaluate an intuitive criterion for tracking of a smoke front using thermocouples. From synchronized photos of the smoke front along with temperature signals, the intuitive criterion is shown to be acceptable. Smoke visualization by a laser sheet proves to have several advantages over the conventional techniques such as the use of smoke generators.

  • PDF

An Investigation of Quantitative Risk Assessment Methods for the Thermal Failure in Targets using Fire Modeling (화재모델링을 이용한 목표 대상물의 열적 손상에 대한 정량적 위험성 평가방법의 고찰)

  • Yang, Ho-Dong;Han, Ho-Sik;Hwang, Cheol-Hong;Kim, Sung-Chan
    • Fire Science and Engineering
    • /
    • v.30 no.5
    • /
    • pp.116-123
    • /
    • 2016
  • The quantitative risk assessment methods for thermal failure in targets were studied using fire modeling. To this end, Fire Dynamics Simulator (FDS), as a representative fire model, was used and the probabilities related to thermal damage to an electrical cable were evaluated according to the change in fire area inside a specific compartment. 'The maximum probability of exceeding the damage thresholds' adopted in a conservative point of view and 'the probability of failure' including the time to damage were compared. The probability of failure suggested in the present study could evaluate the quantitative fire risk more realistically, compared to the maximum probability of exceeding the damage thresholds with the assumption that thermal damage occurred the instant the target reached its minimum failure criteria in terms of the surface temperature and heat flux.

Estimation of Chemical Flame Height based on Fuel Consumption in a Fire Field Model (필드모델에서 연료소모에 기초한 화학적 화염높이 산정)

  • Kim, Sung-Chan
    • Fire Science and Engineering
    • /
    • v.30 no.2
    • /
    • pp.92-97
    • /
    • 2016
  • The present study has been conducted to estimate the chemical flame height based on fuel consumption in fire field model. The calculation algorithms based on cumulative fraction of HRRPUL and fuel concentration along the z axis were applied to the results predicted by Fire Dynamics Simulator (FDS) version 6.3.2 and the mean chemical flame height was obtained by time averaging of instantaneous flame height with the algorithms. The mean flame height calculated by fuel concentration was quite well matched with that of cumulative value of HRRPUL within 10% over-prediction. This study contribute to a more detailed understanding of fire behavior and quantitative evaluation of flame height in the computational fire model.

Effect of Ignition Location on a Vented Deflagration of Hydrogen-air Mixtures in Semi-confined Space (반밀폐공간 내 점화원의 위치가 수소-공기 혼합물 벤트폭연에 미치는 영향)

  • UNGGI YOON;BYOUNGJIK PARK;INJU HWANG;WOOKYUNG KIM;YANGKYUNG KIM
    • Journal of Hydrogen and New Energy
    • /
    • v.35 no.4
    • /
    • pp.415-427
    • /
    • 2024
  • Explosion experiments were conducted using a rectangular concrete structure filled with hydrogen-air mixture (29.0%). In addition, the effect of ignition location on explosion was investigated. The impact on overpressure and flame was increased with the increasing distance of the ignition source from the vent. Importantly, depending on the ignition location the incident pressure was up to 24.4 times higher, while the reflected pressure was 8.7 times higher. Additionally, a maximum external overpressure of 30.01 kPa was measured at a distance of 2.4 m from the vent, predicting damage to humans at the injury level (1% fatality probability). Whereas, no significant damage would occur at a distance of 7.4 m or more from the vent.

Development of Arc Fault Interruption Control Circuit of Fault Voltage Sensing Type (사고전압 감지형 아크차단 제어회로 개발)

  • Kwak, Dong-Kurl;Byun, Jae-Ki;Lee, Bong-Seob
    • Fire Science and Engineering
    • /
    • v.27 no.2
    • /
    • pp.1-5
    • /
    • 2013
  • This paper studies on an arc fault interruption control circuit (AFICC) of fault voltage sensing type. The proposed voltage sensing type AFICC (VST_AFICC) is an electrical fire prevention apparatus that operates the existing circuit breaker with sensing the instantaneous voltage drop of line voltage when occurs electrical faults. The existing Earth Leakage Circuit Breaker (ELB), Molded_case Circuit Breaker (MCCB), and Residual Current Protective Devices (RCDs) used in low voltage distributing system don't have protective capability from electric arc faults to be a major factor of electrical fire. In this paper to improve such problems, a new VST_AFICC using the distortion of voltage waveform when occurs electrical faults is proposed to prevent electrical fire. There is characteristic that the control method of proposed apparatus is different from previous current sensing type. The proposed AFICC has merit that is manufactured by small size and light weight. The practicality of a new VST_AFICC is also verified through various operation analysis.

Revision of the Input Parameters for the Prediction Models of Smoke Detectors Based on the FDS (FDS 기반의 연기감지기 예측모델을 위한 입력인자 재검토)

  • Jang, Hyo-Yeon;Hwang, Cheol-Hong
    • Fire Science and Engineering
    • /
    • v.31 no.2
    • /
    • pp.44-51
    • /
    • 2017
  • Accurate predictions of the activation time for smoke detectors using a fire simulation is are required to ensure the reliability of the RSET (Required Safe Egress Time) calculation in the process of PBD (Performance-Based Design). The objective of this study was to enhance the accuracy of input parameters for the numerical models of smoke detector based on the FDS. To this end, a Fire Detector Evaluator (FDE) developed in previous studies was improved. The uniformities of flow and smoke inside the FDE were improved and accurate measurements of the obscuration per meter (OPM) related to detector operation were also performed through a decrease in the forward scattering of smoke particles. The input parameters using the improved FDE showed a significant difference from the previous FDE quantitatively. In particular, a larger difference was found in a photoelectric detector compared to an ionization detector. Considering that the operating conditions of smoke detectors are affected by the detector type, combustibles, smoke particulars, and color, the database (DB) on the input parameters for various detectors and combustibles should be built to improve the reliability of PBD in future studies.

Measurements of Flame Temperature and Radiation Heat Flux from Pool Fire with Petroleum Diesel Fuel (디젤연료의 액면화재로부터 화염온도와 복사열 측정)

  • Lim, Woo-Sub;Choi, Jae-Wook
    • Fire Science and Engineering
    • /
    • v.21 no.3
    • /
    • pp.78-83
    • /
    • 2007
  • Diesel, a kind of petroleum, which is used in vehicles, vessels, boilers etc causes great damage when a fire happens, because it has higher caloric value than gasoline or kerosene has at burning. Therefore, pool fire experiment was carried using diesel which is sold on the gas station and radiation heat flux that occurs from flame and inner temperature of flame at burning was estimated. The maximum instantaneous flame temperature of diesel was more than $900^{\circ}C$, and the average of maximum flame temperature was $800^{\circ}C$ which occurred at 0.5 H/D distance from the surface of inflammable liquid, the distance has more long that has the lower the temperature of flame. In case of radiation heat flux, it grew to vary according to the size and amount of sample. When the size of a container for experiment was 0.5 m and sample layer was 13 mm and 20 mm, the radiant heat was 92.29 kW and 117.43 kW each. When the container was 1.0 m, it was 364.35 kW and 405.88 kW each.