• Title/Summary/Keyword: 수력발전기

Search Result 73, Processing Time 0.158 seconds

Assessment of Insulation Condition between Diagnosis and Impregnation for Hydro-Generator (수력발전기의 절연보강 전${\cdot}$후 절연상태 비교평가)

  • Byun il-hwan;Lee Eun-Woong
    • Proceedings of the KIEE Conference
    • /
    • summer
    • /
    • pp.1124-1126
    • /
    • 2004
  • The measurements were performed to assess the insulation deterioration condition of the stator winding of Dae-Cheong hydro-generator ${\sharp}2$ which had been in service after being constructed 1980. After repair of the stator winding insulation. we conducted insulation diagnostic tests which include resistance, polarization index(P. I). AC current, dissipation factor($Tan{\delta}$) and partial discharges ($Q_{max}$). The results of diagnostic tests were compared to the previous records. On the basis of these test results. this paper tried to present the importance of insulation repair for the generator stator winding.

  • PDF

Partial Discharge Property of Hydrogenerator Stator Windings (수력발전기 고정자 권선에서 부분방전 특성)

  • Kim, Hee-Dong
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2000.05a
    • /
    • pp.86-90
    • /
    • 2000
  • Partial discharge(PD) tests were performed when the hydrogenerator(rated 11kV and 25MVA) was shut down(off-line). Six cable couplers were installed in the ring bus as well as within hydrogenerator terminal box. PD tests were conducted using partial discharge analyzer(PDA) and digital partial discharge detector(PDD). PDA showed that the normalized quantity number(NQN) and the partial discharge magnitude increased with increase of ac voltage. Slot discharges were discovered in three phases(A, B and C) at the rated voltage. PDA and PDD test results are in accordance with the pattern and magnitude of partial discharge. This hydrogenerator stator windings were in good condition.

  • PDF

A study on the Analysis of Insulation Aging for Generator stator windings (수력발전기 고정자권선의 절연열화 분석)

  • Byun, D.G.;Oh, B.K.;Kang, D.S.;Lim, K.J.
    • Proceedings of the KIEE Conference
    • /
    • 2005.07c
    • /
    • pp.2072-2074
    • /
    • 2005
  • This test was performed to assess the insulation condition of the stator winding of 3.45kV hydro generator in insulation deterioration condition which was due to long service period(30years) since installed We extracted 12 stator wingdings from the hydro generator core, cut the stator windings into three parts(Middle winding part, slot winding part, end wingding part), and evaluated the insulation condition to know the deterioration condition of each parts. This insulation diagnostic tests include AC current, dissipation factor, and partial discharg test.

  • PDF

Development of the On-line Partial Discharge Measuring Sensor and System on Stator Windings for Hydro Generator (수력발전기 고정자권선용 운전중 부분방전 측정 센서 및 시스템 개발)

  • Kang, D.S.;Sun, J.H;Hwang, D.H.;Yun, Y.H.;Seo, I.S.;Shin, B.C.;Klm, H.I.;Lee, K.H.
    • Proceedings of the KIEE Conference
    • /
    • 2005.11c
    • /
    • pp.103-106
    • /
    • 2005
  • A lot of R&D on the diagnosis of stator winding insolation for large rotating machines has been carried out since the 1970s. The on-line partial discharge measurement has proved to be an effective technique in the evaluation of the state of stator insulation in high voltage rotating machines. The purpose of this paper is to describe the method of the on-line partial discharge measurement on stator windings for hydro- generator with ceramic sensor and measuring system. We developed ceramic coupling sensor, partial discharge measuring system, terminal box and index parameters.

  • PDF

The Analysis of Over Current Relay in Wind Power Generator (풍력발전기의 과전류 보호설비 특성 분석)

  • OK, Yeon-Ho;Choi, Jaeho;Jeong, Han-Sang
    • Proceedings of the KIPE Conference
    • /
    • 2015.07a
    • /
    • pp.109-110
    • /
    • 2015
  • 신 재생에너지원은 수력 태양광 풍력등 여러 가지가 있으나 보호계전기 정정은 신 재생에너지원의 특성과 관계없이 시행되고 있다. 본 논문에서는 풍력발전기에 대해 기존 시행한 과전류 계전기(50/51)의 Pick-Up, 한시, 순시에 대하여 정정 값을 검토하고 신재생에너지원과 상관없이 동일하게 적용하고 있는 과전류 계전기에 대해 문제가 없는지 분석하고 그 대안을 제안하고자 한다. 본 논문에서 사용된 정정은 송전회사인 한국전력공사의 기준으로 하였으며 실제 설치된 보호계전기의 제작자 특성 곡선을 적용하였다.

  • PDF

Modeling and Fault Simulation of Hydro Generator Control System (수력 발전기 제어설비의 모델링과 사고 시뮬레이션)

  • Park, Chul-Won
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.29 no.4
    • /
    • pp.102-107
    • /
    • 2015
  • In this paper, the generator control system by using PSCAD/EMTDC was modeled and several faults simulation were performed. The generator control system is composed of generator, turbine, exciter and governor. The parameters of generator control system model were obtained from field power plant. And then, the various transient phenomena through obtained several signal of developed modeling were analyzed.

Unit Commitment Considering Variable Power of Hydro and Pumped Storage Hydro Units (수력 및 앙수발전기의 가변출력운전을 고려한 기동전지 계획에 관한 연구)

  • 송길영;이범;김용하
    • The Transactions of the Korean Institute of Electrical Engineers
    • /
    • v.43 no.3
    • /
    • pp.351-362
    • /
    • 1994
  • This paper presents a new method for solving a long term unit commitment problem including hydro and pumped storage hydro units in a large scale power system. The proposed method makes it possible to get variable power of hydro and pumpde storage hydro units and results in the better unit commitment with good convergency. Moreover this paper proposes an unit commitment algorithm to consider variable power of these units effectively by Lagrangian Relaxation method. By applying the proposed method to the test system and the real system, it is verified the usefulness of this method.

Reliability Improvement of Insulation Diagnosis Using the Hydro-Generator On-Line Partial Discharge Monitoring System (수력발전기 On-line 부분방전 측정 시스템을 이용한 절연상태 진단의 신뢰성 향상)

  • Ok, Yeon-Ho;Lee, Eun-Woong;Lim, Jae-Il;Park, Ji-Kun;Kwak, Won-Ku;Lee, Jae-Heung;Shin, Jae-Pil;Shin, Byoung-Chol
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.58 no.4
    • /
    • pp.469-475
    • /
    • 2009
  • Accident dangerousness of domestic hydro power generators which are operated in Korea is on the increase because of use at the long term. On this, the Off-line diagnosis techniques developed to the On-line by continued domestic technical development since 2000. Especially, On-line insulation diagnosis of domestic hydro power generator is possible by localization of partial electric discharge sensor and On-line insulation diagnosis system. This paper shows the diagnosis result that is applied localized Ceramic Coupler and PDMS-HG(Partial Discharge Monitoring System for Hydro Generator) at four Chung-ju hydro Generator used for 25 years. Particularly, the confidence of insulation diagnosis is improved by using high frequency filter and sampling the partial discharge signals which occur in site. For reviewing the confidence of On-Line insulation diagnosis system, we measured the outside noises and partial discharge signals during practical operation by using the partial discharge diagnosis system of the Full A/D process. And we reviewed the confidence of the On-Line insulation diagnosis system by comparing and analyzing these data.

Site Evaluation and Application of the On-line and Off-line Test for the 13[kV] Class Hydropower Generator Stator Windings (13[kV]급 수력발전기 고정자 권선의 운전 및 정지 중 진단시험 현장적용 평가 및 분석)

  • Chang, Jeong-Ho;Lee, Dong-Keun;Lee, Heung-Ho
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.25 no.11
    • /
    • pp.73-82
    • /
    • 2011
  • The solid insulation system of stator windings in high voltage rotational machines is usually aging in accordance with long time operation. The partial discharge test have been known to check whether insulation deterioration exist or not, and the PD test can effectively diagnose a solid insulation condition regardless of during operation(on-line) or not(off-line). The on-line PD measurement have proven to be a successful technique in monitoring stator insulation condition nowadays. This paper describes the characteristics of comparing the on-line PD measurement data using PDMS-HG(Partial Discharge Monitoring System for Hydro-electric Generator) installed in field with the off-line diagnosis measurement data(insulation resistance, winding resistance, PI, ${\Delta}tan{\delta}$ and PD) on hydro generator(13[kV]) stator windings. These results make good use of managing rotational machines through evaluating the solid insulation condition of stator windings.

Comparision Of On-line and Off-line PD Testing For High Voltage Rotating Machine Stator Bar (고전압회전기 고정자권선의 On-line 및 Off-line 부분방전시험 특성비교)

  • Oh, Bong-Keun;Kim, Hyun-Il;Han, Chang-Dong;Baek, Hyun-Soon;Lim, Kee-Joe
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.351-352
    • /
    • 2007
  • 부분방전이 고체절연시스템에서 대부분의 절연고장과 관련된 징후를 알 수 있으므로 부분방전시험은 고전압회전기 고정자권선의 절연특성을 효과적으로 진단할 수 있다. 부분방전시험은 다른 고전적인 절연시험법과는 다르게 고전압회전기가 운전중(On-line)인 상태와 정지중(Off-line)인 상태에서 모두 측정이 가능한 장점이 있다. 정지중 부분방전시험은 고정자권선 절연상태를 평가할 수 있는 잘 알려진 시험법이다. 최근에는 운전중 부분방전시험이 권선의 절연상태를 모니터링하는데 효과적인 방법으로 운영자에게 고장징후를 알려주고, 예측보전이 가능하도록 도움을 주고있다. 이 논문에서는 수력발전기에 설치되어 운영중인 운전중 진단시스템의 각 상별 부분방전데이터를 바탕으로 정지상태에서 운전중 및 정지중 진단시스템을 이용하여 부분방전을 측정하고 시험결과를 분석하였으며, 운전중 시험과 정지중 시험의 유사성과 차이점을 확인할 수 있었다.

  • PDF