• Title/Summary/Keyword: 성정

Search Result 805, Processing Time 0.023 seconds

Evaluation of Damage from Reclosing Scheme for Power Transfromer (재폐로방식이 전력용 변압기에 미치는 영향 평가)

  • O, Jeong-Hwan;Yun, Sang-Yun;Im, Seong-Jeong;Kim, Jae-Cheol
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.48 no.3
    • /
    • pp.177-183
    • /
    • 1999
  • This paper presents how to evaluate the transformer damage caused by reclosing scheme at the distribution substation. We describe a quantitative relationship between the reclosing scheme and the number of fault current flowing through transformer wsing the probability of a reclosing success/failure. The transformer damage from reclosing scheme is presented using a weight function and a damage function. A weight function is associated with the number of reclosing attempts and the reclosing deadtime to consider cumulative stress caused by reclosing scheme. A damage function is associated with a transformer impact ratio and a transformer functional life. In the case study, the transformer damage is simulated for the probability of a reclosing success. And the evaluation of transformer damage using KEPCO's operation data is performed.

  • PDF

Intelligent Reclosing Scheme to reduce a Damage of Power Equipments (전력설비 피해 감소를 위한 지능형 재폐로방식에 관한 연구)

  • 임성정;김재철
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.15 no.1
    • /
    • pp.112-117
    • /
    • 2001
  • This paper presents an intelligent reclosing scheme to reduce a damage of power equipments in power distribution systems. As the number of reclosing shot increases, an power supply reliability is improved, but an impact of electric facilities by fault currents is accumulated. The proposed scheme determines the number of reclosing shots and its intervals according to ilie magnitude of fault current. Therefore, this scherre reduces a harm of electric facilities and muntains the power supply reliability. Case studies is performd to verify the effectiveness of the proposed scheme using field operation data.

  • PDF

Advanced Reclosing Schemes in Power Distribution Systems Considering Power Quality (전력품질을 고려한 배전시스템에서의 개선된 재폐로방식에 관한 연구)

  • Im, Seong-Jeong;Kim, Jae-Cheol
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.51 no.1
    • /
    • pp.1-6
    • /
    • 2002
  • This paper proposes an advanced reclosing scheme to improve power quality in power distribution systems. When a fault occurs in distribution system, the proposed schema determines the number of reclosing shots and its intervals according to the magnitude of fault current. Thus, an advanced reclosing scheme takes account of the power quality problem in customer\`s and the damage in electric facilities. To verify the effectiveness of the proposed scheme, a numerical simulation that calculates various indices to consider the reliability and the other effects on electric facility, in carried out with actual field data.

Fabrication of LTCC Tape and Its Microwave Dielectric Properties (LTCC Tape 제조 및 고추파 유전특성 평가)

  • Lee, Kyoung-Ho;Choi, Byung-Hoon;Ahn, Dal;Sung, Jung-Hyun
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2001.11a
    • /
    • pp.382-385
    • /
    • 2001
  • In the previous study, a new LTCC material in the PbWO$_4$-TiO$_2$-B$_2$O$_3$-CuO system was introduced. The developed material can be sintered at 850$^{\circ}C$ and its dielectric properties are $\varepsilon$$\sub$r/=20-25, Qxf$\sub$o/=30000∼500000Hz, and $\tau$$\sub$f/=0.2∼30ppm/$^{\circ}C$, respectively Therefore this material can be used as a LTCC substrate material for fabrication of multilayered high frequency communication module set. In present study, using this material, tape casting condition was established. With this condition, a multilayered resonator was fabricated and its electrical properties were examined. In present study, an antenna-duplexer module was also fabricated. Frequency characteristics of as-fabricated antenna-duplexer module was compared with simulation results.

  • PDF

Impact of auto-reclosing on Customer systems (재폐로에 의한 수용가측의 영향)

  • Rim, Seong-Jeong;Oh, Jung-Hwan;Kim, Jae-Chul;Kim, Il-Dong;Han, Kyung-Nam;Kim, Yeong-Han
    • Proceedings of the KIEE Conference
    • /
    • 1996.07b
    • /
    • pp.740-742
    • /
    • 1996
  • This paper analyzes the Impact of customer system at the transients due to auto-reclosing on 22.9kV distribution lines. The various factors affecting this phenomena are analyzed In detail through parametric studies. These factors Include the fault current, fault location, reclosing angle, capacitor bank size, and customer load characteristics. The impacts of these transients on customer system are described and available to identify the optimal auto-reclosing scheme.

  • PDF

Harmonic analysis of Battery Energy Storage System on distribution system (전지전력저장시스템의 배전시스템 연계시 고조파 분석)

  • Kim, Young-Sung;Ryoo, Young-Don;Rim, Seong-Jeong;Kim, Jae-Chul;Kim, Eung-Sang;Ko, Yo
    • Proceedings of the KIEE Conference
    • /
    • 1996.07b
    • /
    • pp.856-858
    • /
    • 1996
  • This paper describes a simulation model to analyze the interconnection operation of battery energy storage system(BESS) and utility system. The computer model used to these analysis composed by using PSCAD/EMTDC. The impacts experienced at load side are studied when occur faults in utility system, and also harmonics analysis are implemented. Results of these study are available to design the harmonic filter.

  • PDF

Partitioning Technique for Equivalents of Power System (전력계통 등가화를 위한 지역분할기법)

  • Han, Soung-Ho;Rim, Seong-Jeong;Yoon, Yong-Han;Kim, Jae-Chul
    • Proceedings of the KIEE Conference
    • /
    • 1993.07a
    • /
    • pp.112-114
    • /
    • 1993
  • This paper presents a partitioning technique for equivalent models to large scale power system. The proposed partitioning technique is utilized by using a heuristic approach based on distributed array processor and the coherent groupings of generator buses. In this paper the reduced Ward-PV method considering the characteristics of buses is used to equivalent models of external system. The technique is demonstrated on New England system with 39 buses, 46 lines and 10 generators.

  • PDF

An Expert System on Local Load Shedding with Priority (우선도를 고려한 지역부하 차단에 관한 전문가시스템)

  • Yoon, Yong-Han;Rim, Seong-Jeong;Han, Soung-Ho;Kim, Jae-Chul
    • Proceedings of the KIEE Conference
    • /
    • 1993.07a
    • /
    • pp.70-72
    • /
    • 1993
  • This paper presents an expert system that sheds loads considering priority in the localized SCADA power systems during an emergency states. The proposed algorithm uses neural networks to detect local load shedding location and heuristic rules to determine load shedding amounts. The proposed expert system is demonatrated at one of the model system which incorporates two localized SCADA power system. It is operated under workstation.

  • PDF