Electrical Measurement of SOx Dew Point

SOx노점의 전기적 측정

  • 전영남 (조선대학교 공과대학 환경공학과) ;
  • 용기중 (교통안전진흥공단 자동차성능시험연구소) ;
  • 채지우 (인하대학교 공과대학 기계공학과)
  • Published : 1995.11.01

Abstract

When combustion gas is cooled down below the dew point of sulfuric acid vapor in the heat recovery systems, condensation occurs. Since the condensed sulfuric acid solution causes low-temperature corrosion in materials, it is important to measure the SOx dew point by electric measurement. In this study, two kinds of probes having electric gaps of 1mm or 2mm were used. and experiments were carried out by the parameters of sulfuric acid vapor and water vapor concentration. The changes of electric current caused by sulfuric acid condensed on the surface of probe according to the cooling rate and the probe head surface temperature were sudied. The opimum cooling rate was decreased with the increasing of water vaper concentration regardless of sulfuric acid concentration. The sensitivity of electric current is improved for the narrower gap(1mm) of ring electrodes, but it rarely affects the SOx dew point measuring of different probes according to the change of cooling rate.

Keywords