An Experimental Study on Heat Transmission Characteristics of the Conventional and Prefabricated Ondol

기존온수온돌과 조립식 온수온돌의 전열특성에 관한 실험적 연구

  • Published : 1995.11.01

Abstract

The objectives of this study are to find out and to analyze the heat transmission characteristics of the conventional and prefabricated Ondol systems. To compare the thermal characteristics of these Ondol, a real sized Ondol model is set in a chamber. Hot water whose temperature is varied from $45^{\circ}C$ to $60^{\circ}C$ with $5^{\circ}C$ interval is supplied to each Ondol system. At that time the temperature distribution of floor surface, the amount of supplied heat, the heat radiation aspect and the heat loss from the floor to the underground are measured and analyzed simultaneously. As a result, even if the supplied hot water temperature to the prefabricated Ondol panel is lower by about $5^{\circ}C$ than that of the conventional Ondol panel, the net radiant effect is same. Heat radiation efficiency of the prefabricated Ondol panel is over 5% better than that of the conventional Ondol panel. It takes 12 hours for the conventional Ondol and 45 minutes for the prefabricated Ondol, respectively to reach steady state.