과열도 변화에 의한 $NH_3$ 냉동장치의 성능특성 연구

The Study on Performance Characteristics due to the Superheat Temperature of $NH_3$ Refrigeration System

  • 전상신 (조선대학교 기계공학과 대학원) ;
  • 권일욱 (조선대학교 기계공학과 대학원) ;
  • 하옥남 (조선대학교 기계공학과)
  • 발행 : 2004.04.28

초록

Nowadays CFCs and HCFCs refrigerants are restricted because it cause depletion of ozone layer. Accordingly, this experiment apply the $NH_3$ gas and not CFCs and HCFCs for refrigerant to study the performance characteristic from the superheat control and improve the energy efficiency from the high performance. The condensing pressure of refrigeration system is increased from 14.5bar to 16bar by 0.5bar and superheat temperature is increased from $0^{\circ}C$ to $10^{\circ}C$ by $1^{\circ}C$ at each condensing pressure. As the result of experiment, when the superheat temperature is $1^{\circ}C$ at each condensing pressure, the refrigeration system has the high performance.

키워드