• 제목/요약/키워드: water mist fire suppression system

검색결과 42건 처리시간 0.031초

Parametric Study on Water Mist Nozzles for Fire Suppression System Based on CFD Methods

  • Jung, In-Su;Park, Tae-Gyu;Chung, Hee-Taeg
    • 한국분무공학회지
    • /
    • 제15권3호
    • /
    • pp.124-130
    • /
    • 2010
  • Numerical simulation has been performed to investigate the mist flow characteristics through the fire suppression nozzles for the design purposes. The commercial softwares, FLUENT and the fire dynamic simulator, FDS with the proper modelings were chosen as the numerical tools. In order to find optimal conditions in sense of the main performances of nozzles, the spray characteristics were analyzed both inside and outside of the nozzles. Geometric factors of the injecting orifices, i.e., diameter and chamfered angle were chosen as the simulation parameters for design application. From the present numerical results, 1.0c nozzles, whose orifice-diameter was 1 mm, having the chamfered angles were shown as the best performance of the fire suppression.

랙크식 창고에 대한 미분무 시스템 적용성 실험 (Experiments of Water Mist System Application for Rack Storage)

  • 명상엽;김종훈
    • 한국재난정보학회 논문집
    • /
    • 제16권4호
    • /
    • pp.627-637
    • /
    • 2020
  • 연구목적: 랙크식 창고의 대표적 가연물인 CEP에 대하여 미분무 소화설비의 적용성을 알아보기 위하여 본 실험적 연구를 수행하였다. 연구방법:먼저 본 실험에 사용된 미분무수 소화설비가 유류화재 소화가 가능한지 확인을 수행하였다. 그 후, CEP 박스를 유류화재실험과 동일한 소규모 공간에 적재한 후, 개구부의 열림 및 닫힘, 그리고 닫힘 상태에서의 내부 적재물을 증가시키는 3가지 시나리오를 대상으로 실험을 수행하였다. 시나리오는 미분무수 소화에 중요한 영향요소인 개구부와 공간크기조건을 고려하여 설정되었다. 연구결과:유류화재에 대한 소화시험에서는 문의 열림과 닫힘 상태, 모두에서 화재가 잘 진압되는 것으로 나타났다. 동일 공간조건에서 CEP 가연물의 화재 시 개구부의 열림 상태에서는 화재가 진압되지 않았다. 개구부를 닫은 경우 화재는 진압되었지만, 일부 잔염이 확인되었다. 결론: 유류화재 진압실험에서 미분무수 소화설비가 개구부 열림과 닫힘 상황 모두에서 유효한 소화능력을 보여주었다. 하지만 CEP화재에 대해서는 닫힘 상태에서만 유효한 소화능력을 보여주었으며, 재 발화의 가능성이 있음이 나타났다.

주 변압기실 화재시나리오에 적용한 미세물분무 노즐의 소화성능 (Performance of Fire Extinguishing of Water Mist Nozzle for Power Transformer Fire Scenario)

  • 이경덕
    • 한국안전학회지
    • /
    • 제21권6호
    • /
    • pp.46-54
    • /
    • 2006
  • Fire extinguishing experiment was conducted with water mist nozzle in case of the pool fire, cascade fire and spray fire on flammable liquid of class B whether water mist system can be effective system for power transformer fire scenario. In the event of a pool fire, flow rate and time to extinguish was inclined to be increased according to the obstruction rate of ignition space. Furthermore, the performance of fire extinguishing depended upon the spraying angle of the nozzles. In case of cascade fire, the effect of extinguishment was began to show from a combustion pan filled with fuel and fuel flowing plate later on.

목조문화재 보존을 위한 소방시설에 대한 고찰 (Consideration on Fire-prevention Facilities for Wooden Cultural Heritages)

  • 김태구
    • 보존과학연구
    • /
    • 통권31호
    • /
    • pp.155-171
    • /
    • 2010
  • Wooden cultural heritages have many factors of fires and structural characteristics vulnerable to the fire extinguishing. Also, they are surrounded with forests and so remote from fire stations, which make it difficult to handle it quickly when fires break out. Wooden cultural heritages made of wood materials belong to the general fire in a Class A. Taking characteristics such as a smoldering and a backfire from the that fire of wooden materials into consideration, extinguishing the fire by the cooling system is the most effective. If the fire can't be put out at the early stage, it is almost impossible to protect wooden cultural heritages from the fire, because wooden structures can be destroyed in a high temperature and in a short time and it takes around average 7 minutes to reach its peak of flames in the process of a fire. According to the geographical and environmental situation of the cultural heritages, currently, the fire-prevention facilities such as the auto fire detector for the prompt detection, the water mist fire suppression system for the 1st early and urgent fire suppression and the outdoor fire hydrant and the water curtain etc. for the 2nd full-scale suppression and the prevention of the fire gaining force are being installed for the wooden cultural heritages.

  • PDF

변압기실 화재에 대한 미분무수 소화시스템의 적용 - 소화특성을 중심으로(Part 1) (Application of Water Mist System for a Power Transformer Room - Fire Extinguishment(Part 1))

  • 한용식;최병일;김명배
    • 한국화재소방학회논문지
    • /
    • 제19권4호
    • /
    • pp.32-36
    • /
    • 2005
  • 고전력 변압기에 설치되어있는 가스계 소화설비는 초기 화재에는 대응할 수 있지만 소화후 다시 발화되는 화재에 대하여는 아무런 대책이 될 수 없다. 따라서 초기 소화와 재발화된 화재의 소화 또는 재발화 방지가 가능한 소화 및 냉각시스템이 변압기에 필요할 것이다. 이러한 시스템으로 미분무수 설비가 선택되었으며, 본 연구에서는 주로 소화특성에 대하여 기술한다. 시험 대상으로 특정한 고압과 저압시스템을 선정하여 그 소화능력을 비교하였다. 변압기실은 약 $10m\times10m\times$의 공간이며 변압기의 크기는 이 공간의 $7\%$정도이다. 실물규모의 소화실험이 6개의 화재시나리오 (2개의 분무화재, 3개의 풀 화재, 1개의 흐름화재)에 의하여 수행되었으며, 고압시스템이 저압시스템에 비하여 산소희석 및 냉각효과 측면에서 우수한 소화특성을 나타내었다.

증점제를 함유한 미분무수의 목재화재 소화효과 (Efficiency of Water Mist Suppression System Containing Viscosity Agent to Extinguish Wood Cribs Fire)

  • 김민형;신창섭
    • 한국안전학회지
    • /
    • 제29권4호
    • /
    • pp.78-84
    • /
    • 2014
  • Viscosity agents were added to water to improve extinguishing performance of low pressure water mist suppression system on wood cribs fire, and a small scale wood cribs fire experiment was conducted to measure the extinguishing performance. CMC and agar were used for viscosity agent and as the amount of viscosity agent enlarges, it showed the increase of the viscosity of aqueous solution and the decrease of the fluidity. On wood cribs fire experiment, the extinguishing efficiency was improved with supplemental viscosity agent as it enhanced the adhesive time of aqueous solution on the wood, and therefore expanded the contact time of fire surface. The surface tension of aqueous solution was decreased with the addition of agar which to be assumed as an increase factor of extinguishing efficiency. By the extinguishing experimental result, the most effective extinguishing agent was CMC 0.6 wt.%, with the flame suppression time and the extinguishing time were reduced by 70s and 93s respectively at this concentration.

지하철 객차 내 환기 속도가 고압 미세물분무 화재제어 시스템의 성능에 대한 실험평가 (An Experimental Evaluation for the Effect of Ventilation Velocity in Subway Train on Performance of a High Pressure Water Mist Fire Suppression)

  • 김동운;배승용;김동석;박원희;유홍선
    • 한국철도학회:학술대회논문집
    • /
    • 한국철도학회 2007년도 춘계학술대회 논문집
    • /
    • pp.1307-1312
    • /
    • 2007
  • This experiments are performed to investigate the effect of ventilation velocity on a high pressure water mist fire suppression in subway train. The experiment is conducted in half scale modeled train of a steel-welled enclosure (8.0m*2.4m*2.1m). The ventilation velocity is controlled by the ventilation duct through an inverter in the range of 0 to 2 m/s. The coverage-radius and an injection angle of an high pressure water mist system are measured. The mist nozzle with 7-injection holes is operated with pressure 80 bar. The heptane pool fires are used. The fire extinguishment times and the temperatures are measured for the ventilation velocities. In conclusion, because the momentum of injected water mist is more dominant than that of ventilation air, the characteristics of water mist, the fire extinguishment times and the temperatures are affected very little by ventilation velocity.

  • PDF

방사특성 변화에 따른 미세물분무의 소화특성 (Extinguishing Charactristics of Water Mist by Discharge Properties)

  • 이경덕;신창섭
    • 한국화재소방학회논문지
    • /
    • 제15권4호
    • /
    • pp.41-48
    • /
    • 2001
  • 할론소화약제는 유류화재 및 전기화재의 진압에 가장 효과적으로 널리 사용되어 왔으나, 이들은 오존층파괴지수와 지구온난화지수가 높아 환경문제를 야기하고 있다. 이러한 환경에 악영향을 주지 않는 대체기술의 하나로 관심을 끌며 연구되기 시작한 소화방법이 미세물분무를 이용한 소화설비이며, 미세물분무는 스프링클러의 살수입자에 비해 물입자가 작고 표면적이 크기 때문에 화염면에서의 증발 및 냉각특성이 우수하며, 산소의 농도를 감소시키는 질식작용이 우수하다. 본 연구는 미세물분무 소화설비의 설계를 위한 기초단계로 유류화재에 대한 미세물분무의 입자크기, 유량밀도, 방사분포, 방사압력 및 화재의 크기에 따른 화염의 소화특성을 측정하였다. 그 결과 액체 poo l화재의 소화시간은 유량밀도가 증가함으로서 짧아지고, 유량밀도가 0.5$\pm$0.05ml/$\textrm{cm}^2$ . min이하인 경우 입자크기가 증가함으로서 짧아졌다. 또 방사주기를 변화시켜 실험한 결과 n-heptane 화재에 대하여 간헐적으로 방사한 미세물분무가 소화에 효과적이었으며, 이때 연속방사와 비교하여 화재를 소화하기 위해 필요한 물의 총량은 1/4로 감소하였다.

  • PDF

중저압 노즐을 이용한 사찰 및 목조 문화재용 미분무 패키지 소화설비 개발 (Development for the Water Mist Package Having a Low Pressure Nozzles on Wooden Cultural Properties and Temples)

  • 김태환;명상엽
    • 한국화재소방학회논문지
    • /
    • 제24권4호
    • /
    • pp.62-68
    • /
    • 2010
  • 우리나라의 목조문화재는 구조적 특성상 화재에 매우 취약하고, 최근 들어 산불 및 방화 등의 이유로 많은 문화재들이 화재로 손실되고 있다. 따라서 본 연구 개발은 소량의 소화용수 사용이 가능한 중저압용 미분무 노즐과 그 패키지 소화 시스템을 개발하여 물로 인한 최소한의 피해와 최대의 소화효과와 더불어 최고의 화재안전 시스템을 개발하였다. 목조문화재 건축물의 특성을 고려하여 건축물의 내부와 외부에서 각각 적용 가능한 두 가지 형태의 중저압 미분무 노즐을 개발하였다. 외부용 노즐은 13~14bar의 압력에 서 30~35l/min의 유량을 갖고 있으며, 내부용 노즐은 14~15bar의 압력에서 25~30l/min 유량을 갖는 노즐을 설계 개발하였다. 개발된 노즐의 성능을 평가하기 위하여 궁궐 모양의 대표적인 목조문화재 실무크기인 가로 4.9m, 세로 4m, 높이 6.6m의 모형을 목재로 제작하였고 화재 시나리오를 만들어 실증화재 소화 실험을 실시하였다. 실증화재 실험결과 $200{\mu}m$의 물방울 입자 크기를 갖는 중저압 노즐이 한 적응성이 있는 것으로 나타났으며, 완전소화에는 실패하더라도 소방대가 출동할 때까지 연소확대가 되지 않도록 화재를 억제해 줄 수 있을 것으로 나타났다.