Experiments of Water Mist System Application for Rack Storage  

Myoung, Sang-Yup (Department of Fire and Disaster Prevention, Osan University)
Kim, Jong-Hoon (H2K Solution Inc.)
Publication Information
Journal of the Society of Disaster Information / v.16, no.4, 2020 , pp. 627-637 More about this Journal
Abstract
Purpose: This experimental study was conducted to find out whether a water-mist fire suppression system can be applied to C.E.P., a representative combustible material of a rack storage. Method: First, it was confirmed whether the water-mist fire-extinguishing system used in this experiment was capable of extinguishing oil fires. After that, the C.E.P. boxes were loaded in the same small space as used in the oil fire experiment, and then the experiment was conducted on three scenarios; door opening, door closing, and door closing and increasing the internal load. The scenario was set considering the opening and space size conditions, which are important factors for the water-mist fire suppression. Result: Oil fire suppression tests have shown that fires are well extinguished in both the door open and closed conditions. In case of a fire of C.E.P. boxes in the same space condition as an oil fire, the fire was not extinguished in the door open condition. Fires were extinguished in the case with the door closed condition, but the afterglow was confirmed. Conclusion: In the oil fire suppression test, a water-mist fire suppression system extinguished a fire in both the door open and closed conditions. However, for the C.E.P fire, it was possible to extinguish only under the door closed condition, and there was a possibility of re-ignition.
Keywords
C.E.P.; Water-mist; Fire; Experiment; Vent;
Citations & Related Records
연도 인용수 순위
  • Reference
1 FMDS 8-9 Loss Prevention Data Sheets (2015). Storage of Class 1, 2, 3, 4 AND PLASTIC COMMODITIS, pp. 27-45.
2 Lake, J. D. (2010) Automatic Sprinkler systems Handbook 7th Edition, National Fire Protection Association, Quincy, Massachusetts, United States, pp. 659-686.
3 Kim, J.H., Joung, W,I., Lee, Y.J., Myoung, S.Y., Kim, W.H. (2017). "Water flow and spray experiments of in-rack sprinkler at rack storage." Proceedings of 2017 Spring Annual Conference, Korean Institutes of Fire Science & Engineering, Daegu, pp. 193-194.
4 Kim, W.H., Lee, Y.J. (2016). "A field survey of rack-type warehouse for commodity classification system in Korea." 2016 Fire Science and Engineering, Vol. 30. No. 2, pp 98-105.   DOI
5 National Fire Safety Code 103 (2015). Fire Safety Code for Automatic Sprinkler System. pp154-187.
6 NFPA 13 (2016). Standard for the Installation of Sprinkler System, Nation Fire Protection Association, pp. 82, 141-143.