Performance of Fire Extinguishing of Water Mist Nozzle for Power Transformer Fire Scenario

주 변압기실 화재시나리오에 적용한 미세물분무 노즐의 소화성능

  • Published : 2006.12.31

Abstract

Fire extinguishing experiment was conducted with water mist nozzle in case of the pool fire, cascade fire and spray fire on flammable liquid of class B whether water mist system can be effective system for power transformer fire scenario. In the event of a pool fire, flow rate and time to extinguish was inclined to be increased according to the obstruction rate of ignition space. Furthermore, the performance of fire extinguishing depended upon the spraying angle of the nozzles. In case of cascade fire, the effect of extinguishment was began to show from a combustion pan filled with fuel and fuel flowing plate later on.

Keywords

References

  1. Mawhinney, J.R., B.Z. Dlugogorski and A.K. Kim, 'A Closer Look at the Fire Extinguishing Properties of Water Mist', Fire Safety Science Proceedings of Fourth International Symposium, pp. 47-60, 1994
  2. Liu, Z.G., A.K. Kim and J.Z. Su, 'Examination of Performance of Water Mist Fire Suppression Systems under Ventilation Conditions' J of Fire Prot. Eng., Vol. 11, No. 3, pp. 164-193, 2001 https://doi.org/10.1106/3VE8-WWT4-C3U4-FEH9
  3. Liu, Z.G., A.K. Kim, D.W. Carpenter and P.L. Yen, 'Extinguishment of Liquid Fuel Fires by Local Application of Water Mist' The Combustion Institute/ Canada Section, 2001 Spring Technical Meeting, 13-16, pp. 21.1-21.4., 2001
  4. 최병일, 한용식, 김명배, '변전소 주 변압기 실 미분무수 소화시스템 성능평가를 위한 화재시나리오' 한국화재소방학회지, 제19권, 제3호, pp. 52-57, 2005
  5. P. Andersson and G. Holmstedt, 'imitations of Water Mist as a Total Flooding Agent' J. of Fire Prot. Engr., Vol. 9, No. 4, pp. 31-50, 1999
  6. B. Yao, F. Weicheng and Guangxuan Liao, 'Interaction of Water Mists with a Diffusion Flame in a Confined Space' Fire Safety J., Vol. 33, No. 2, pp.129-139, 1999 https://doi.org/10.1016/S0379-7112(99)00020-X
  7. J.R. Mawhinney and S. Robert, 'Water Mist Fire Suppression Systems' NFPA Handbook. 2nd Ed. Sec. 6 Cha. 15, pp. 216-248, 1997
  8. Mawhinney, J.R., and S. Robert, 'Water Mist Fire Suppression Systems' NFPA Handbook. 2nd Ed. Sec. 6 Cha. 15, pp. 216-248, 1997