Abstract
A water mist system was considered as a possible alternative to a gaseous suppression system that can not prevent re-ignition after fire extinguishment for a power transformer room. This study deals with the fire suppression capability of the water mist systems. High-and low-pressure water mist systems were examined to compare efficiency of both systems. The power transformer examined in this study occupied about $7\%$ of a $10m\times10m\times$ transformer room. Full-scale suppression tests were performed for six different fire scenarios: two spray fires, three pool fires and one cascade fire. The fire suppression test results demonstrated that the high-pressure system was superior to the low-pressure system, especially considering oxygen depletion and the ambient temperature distribution.
고전력 변압기에 설치되어있는 가스계 소화설비는 초기 화재에는 대응할 수 있지만 소화후 다시 발화되는 화재에 대하여는 아무런 대책이 될 수 없다. 따라서 초기 소화와 재발화된 화재의 소화 또는 재발화 방지가 가능한 소화 및 냉각시스템이 변압기에 필요할 것이다. 이러한 시스템으로 미분무수 설비가 선택되었으며, 본 연구에서는 주로 소화특성에 대하여 기술한다. 시험 대상으로 특정한 고압과 저압시스템을 선정하여 그 소화능력을 비교하였다. 변압기실은 약 $10m\times10m\times$의 공간이며 변압기의 크기는 이 공간의 $7\%$정도이다. 실물규모의 소화실험이 6개의 화재시나리오 (2개의 분무화재, 3개의 풀 화재, 1개의 흐름화재)에 의하여 수행되었으며, 고압시스템이 저압시스템에 비하여 산소희석 및 냉각효과 측면에서 우수한 소화특성을 나타내었다.