• 제목/요약/키워드: transformers

검색결과 1,166건 처리시간 0.031초

퍼지 패턴 분류와 뉴럴 네트워크를 이용한 지능형 유중가스 판정 시스템 (Intelligent Diagnosis System for DGA Using Fuzzy Pattern Classification and Neural Network)

  • 조성민;권동진;남창현;김재철
    • 전기학회논문지
    • /
    • 제56권12호
    • /
    • pp.2084-2090
    • /
    • 2007
  • The DGA (Dissolved Gases Analysis) technique has been widely using for fault diagnosis of the power transformers. Some electric power utility company establishes the criteria of DGA to improve reliability, because of difference of operation environment and design of power transformer. In this paper, we introduce intelligent diagnosis system for DGA result of KEPCO (Korea Electric Power Cooperation). This system can classify patterns type of gases ratio that frequently occurs in recent result of gases analysis using Fuzzy Inference. The classification of Patterns let us know that major causes of gases generation based on type of patterns. Finally, Neural Network based on patterns diagnose transformer. NN was trained using result data of DGA of actually faulted transformers recently. Result of intelligent diagnosis system is right well in comparison with actual inner inspection of transformers.

철심 코어형 전자식 전압 변성기 개발 (Development of the iron-cored electronic voltage transformer)

  • 강용철;박종민;장성일;김연희;최정환;김용균;송인준;안용호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2008년도 제39회 하계학술대회
    • /
    • pp.138-139
    • /
    • 2008
  • An iron-cored voltage transformer(VT) is usually used to obtain the standard low voltage signal for protection and measurement. Generally, the iron-cored transformers have errors due to the hysteresis characteristics of the iron-core. An error compensating algorithm for iron-cored instrument transformer can improve the accuracy of conventional voltage transformers. This paper describes the iron-cored electronic voltage transformer having the error compensating algorithm. The innovative product composes an iron-cored VT and an intelligent electronic device(IED) having the error compensating algorithm. The test results of the iron-cored electronic voltage transformers in Korea Electro-technology Research Institute(KERI) are presented.

  • PDF

변압기내 부분방전 탐지 및 위치검출 (Detection and Location of Partial Discharge in Transformers)

  • 곽희노;김재철;황선주;권태원;윤용범
    • 한국조명전기설비학회지:조명전기설비
    • /
    • 제6권4호
    • /
    • pp.53-59
    • /
    • 1992
  • This paper describes an instrument for the detection and geometric location of partial discharge (PD) source in transformers. This instrument measures electric current pulses and ultrasonic pulses simultaneously, counts the number of electrical pulses and determines the geometric location of PD in transformers. It was found that there is a relationship between partial discharge magnitude and pulse repetition rate when the applied test voltage and oil temperature were varied. Through the laboratory test using model transformer, it was clarified that this detector could be used for detecting and locating PD in the transformer.

  • PDF

트랜스포머를 이용한 고전압 펄스 발생 장치의 설계와 측정평가에 관한 연구 (Study for the Design and Measurement of the High Voltage Pulse Generator Using Transformers)

  • 김영주
    • 조명전기설비학회논문지
    • /
    • 제26권1호
    • /
    • pp.82-86
    • /
    • 2012
  • High-capacity high-voltage pulse generator that can be used for environmental clean-up was developed using transformers. High-voltage pulse is consists of the primary wave and the harmonic wave which are increased as a series circuit using transformers to make pulses. Each transformer has a band-pass characteristics. The output voltage of the pulse width 50[%] was decided. The output voltage of high-voltage pulse generator device was measured as 1.4[kV] (Peak-to-Peak).

압전 트랜스포머를 적용한 네온관용 인버터에서의 Pspice 모델을 이용한 특성분석 (An Analysis of Neon Tube Inverters with Piezoelectric Transformers Using Pspice Model)

  • 윤정원;김윤호;박경수;곽형찬
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2002년도 전력전자학술대회 논문집
    • /
    • pp.701-706
    • /
    • 2002
  • Typically, dimensions of the power circuit depend on magnetic components, heat sink, and smoothing capacitor, etc. For the miniaturization of the power circuit, one of the solutions is that bulky magnetic transformer in previously used is replaced by a piezoelectric transformer. Therefore, since many systems are attempted to apply the piezoelectric transformers, a new piezoelectric material is tending to be developed continuously. In this paper, an analysis of neon tube inverters with piezoelectric transformers are presented by Pspice modeling. Simulation results show that it is possible to apply a piezoelectric transformer to neon tube inverters with high conversion efficiency

  • PDF

직렬 연결된 두개의 트랜스포머를 갖는 새로운 위상천이 풀 브릿지 컨버터 (A New Phase Shift Full Bridge Converter with Serially Connected Two Transformers)

  • 구관본;김태성;문건우;윤명중
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2002년도 전력전자학술대회 논문집
    • /
    • pp.370-373
    • /
    • 2002
  • A new phase shift full bridge converter(PSFB) with serially connected two transformers is proposed. It is well suited for applications in the communication equipment of a few hundred watts. The main features of the proposed converter are a wide input voltage range, an easiness to meet the requirement for zero voltage switching (ZVS) condition at a light load, and a small output voltage ripple. Furthermore, it features high power density since serially connected two transformers can replace both a main transformer and an output inductor. A mode analysis and experimental results are presented to verify the validity of the proposed converter.

  • PDF

과부하 및 경년 변압기 절연유 열화 특성 분석 연구 (Analysis of Aging Characteristics in Oil Immerged Pole Transformer)

  • 이병성;송일근;이재봉;박동배;한상옥
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2002년도 춘계학술대회 논문집 유기절연재료 전자세라믹 방전플라즈마 일렉트렛트 및 응용기술
    • /
    • pp.203-207
    • /
    • 2002
  • In order to evaluate the aging of mineral oil immersed distribution transformers, it gathered some insulation oil in over loaded and long time(exceed their service life, 13yrs.) aged transformers in the field, we measured moisture content, acid number, dielectric strength of the oil as defined in KS C 2101 standard. And also, it had been measured dielectric constant, specific resistant, $tan{\delta}$ on aged transformer oil at from $10^{\circ}C$ to $130^{\circ}C$. These results are compared with a new mineral oil. From this study, it can be considered that the analysis of mineral oil may be suitable for evaluation of life expectancy in distribution transformers

  • PDF

Investigation of Rise Time and Overshoot in Pulse Transformers with Different Topologies for Electromagnetic Trigger of SCRs

  • Lv, Gang;Zeng, Dihui;Zhou, Tong
    • Journal of Power Electronics
    • /
    • 제18권3호
    • /
    • pp.902-909
    • /
    • 2018
  • This study investigates the influences of different core parameters on the dynamic performances, such as rise time and overshoot, in pulse transformers for the triggering circuit of SCRs. First, a simplified transformer equivalent circuit, which emerges from a standard transformer equivalent circuit, is developed to analyze the step response. Second, the relations between the dynamic performances and the parasitic parameters are calculated by the simplified equivalent circuit. Third, the variations of rise time and overshoot, which are vital to the stability of triggering SCRs, with different core parameters, such as mechanic dimensions and topologies, are comprehensively investigated by analyzing the parasitic parameters. Finally, prototype transformers are fabricated to experimentally validate the analysis. The presented method can practically instruct the design of a pulse transformer for triggering SCRs.

로고스키 코일과 초음파 센서를 이용한 변압기내 부분방전 탐지 및 위치검출 (Detection and Location of Partial discharge in Transformers Using Logoski coil and Ultrasonic sensor)

  • 곽희로;김재철;김웅상;한민구;권태원;윤용범
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1990년도 하계학술대회 논문집
    • /
    • pp.279-282
    • /
    • 1990
  • This paper describes an nstrument for the detection and geometric location of partial discharge(PD) sources in transformers. This instrument measures electric current pulses and ultrasonic pulses simultaneously, counts the number of electrical pulse and determines the geometric location of PD in transformers. It was found that there is a relationship between partial discharge magnitude and pulse repetition rate when the applied test voltage and oil temperature were varied. Through the laboratory test using model transformer, it was clarified that this detector could be used, satisfactory for detecting and locating of PD in the transformer.

  • PDF

변압기에서 저압충격시험기를 이용한 권선변형 측정 (Winding Deformation Measurement using Low-voltage Impulse Tester in Transformers)

  • 조국희;강동식;김광화;권동진;윤진열
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1997년도 하계학술대회 논문집 E
    • /
    • pp.1737-1739
    • /
    • 1997
  • We describe the characteristic of LVI test system and methods to detect the deformation of windings in the power transformers. As the front rise time of recurrent-surge generator pulse less than 1000ns and the peak value of pulse is about 500V, we have the good results of detecting winding deformation in the LVI test of transformer. And we discuss the application of LVI test method and the condition of RSG pulse through results of in one and three pole transformers under Lab. tests.

  • PDF