• Title/Summary/Keyword: normalized generator

Search Result 34, Processing Time 0.022 seconds

Analysis of Partial Discharge in High Voltage Motor Model Coils (고압전동기 모델 코일의 부분방전 분석)

  • Kim, Hee-Dong;Kong, Tae-Sik
    • Proceedings of the KIEE Conference
    • /
    • 2005.07c
    • /
    • pp.2091-2093
    • /
    • 2005
  • Five model coils of 6.6kV motor were manufactured with several defects. These stator coils have artificial defects such as void of groundwall insulation, removal of semi-conductive coating and damage of strand insulation. Epoxy-mica coupler(80 pF) was connected to five model coil terminals, respectively The voltage applied to the coils was 3.81kV, 4.76kV, 6.0kV and 6.6kV. Partial discharge(PD) tests performed in the laboratory and shield room. Digital PD detector (PDD) and turbine generator analyzer(TGA) were used to measure PD activity. TGA summarizes each plot with two quantities such as the normalized quantity number(NQN) and the peak PD magnitude(Qm). The PD levels in pC were measured with PDD. PD patterns of model coils were indicated the internal and slot discharges. PD patterns coincide with both PDD and TGA.

  • PDF

Analysis of Insulation Aging in Operating High Voltage Motors (운전중인 고압전동기에서 절연열화 분석)

  • Kim, Hee-Dong;Ju, Young-Ho
    • Proceedings of the KIEE Conference
    • /
    • 2005.07c
    • /
    • pp.2175-2178
    • /
    • 2005
  • During normal machine operation, partial discharge(PD) measurements were performed with turbine generator analyzer(TGA) in five high voltage motors(rated 6.6kV). These high voltage motors were installed with 80pF capacitive couplers at the terminal box. The PD patterns were displayed two dimensional and three dimensional. TGA summarizes each plot with two quantities such as the normalized quantity number(NQN) and the peak PD magnitude(Qm). Off-line PD measurements were conducted on five motors. These motors were energized to 3.81kV. The PD levels in pC were measured with a conventional digital PD detector. The comparison of positive to negative PD indicates whether the defect elements of PD are within the insulation or on the insulation surface. Internal discharges were generated in phase A, B and C of COP-B and pulv.-B, in phase B of Pulv. C and in phase C of Pulv.-D motor. Discharge at conductor surface was discovered in phase A of Pulv. D motor. Slot discharges occurred in three phases of Pulv. E motor.

  • PDF

Influence of Design of Turbulence Generator on Flow Behavior in Pilot Headbox

  • Youn Hye Jung;Lee Hak Lae;Chin Seong Min
    • Journal of Korea Technical Association of The Pulp and Paper Industry
    • /
    • v.36 no.5 s.108
    • /
    • pp.1-10
    • /
    • 2004
  • The geometry of headboxes is of great importance in obtaining good formation, even basis weight profile and fiber orientation. Therefore, many attentions have been made to examine the influence of the geometry of headboxes on the flow behavior. In this study, to evaluate flow behavior in headboxes, three types of turbulence generators were examined using pilot headbox. Velocity profiles in MD and CD were measured using a pressure monitoring system and flow in headboxes was visualized by dye injection method. CD velocity profiles at three different locations inside the slice of Type A headbox showed that the velocity increased downstream to slice exit and had a pattern with four humps due to the persisting wall effect of step diffusors. Results from the evaluation of normalized velocity profile and flow visualization showed that L-shaped Type C headbox caused a large pressure drop but it lacked in flow stabilizing ability.

Implementation of TFDR system with PXI type instruments for detection and estimation of the fault on the coaxial cable (동축 케이블의 결함 측정에 있어서 PXI 타입의 계측기를 이용한 개선된 TFDR 시스템의 구현)

  • Choe, Deok-Seon;Park, Jin-Bae;Yun, Tae-Seong
    • Proceedings of the KIEE Conference
    • /
    • 2003.11b
    • /
    • pp.91-94
    • /
    • 2003
  • In this paper, we achieve implementation of a Time-Frequency Domain Reflectometry(TFDR) system through comparatively low performance(100MS/s) PCI extensions for Instrumentation(PXI). The TFDR is the general methodology of Time Domain Reflectometry(TDR) and Frequency Domain Reflectometry(FDR). This methodology is robust in Gaussian noises, because the fixed frequency bandwidth is used. Moreover, the methodology can get more information of the fault by using the normalized time-frequency cross correlation function. The Arbitrary Waveform Generator(AWG) module generates the input signal, and the digital oscilloscope module acquires the input and reflected signals, while PXI controller module performs the control of the total PXI modules and execution of the main algorithm. The maximum range of measurement and the blind spot are calculated according ta variations of time duration and frequency bandwidth. On the basis of above calculations, the algorithm and the design of input signals used in the TFDR system are verified by real experiments. The correlation function is added to the TDR methodology for reduction of the blind spot in the TFDR system.

  • PDF

Implementation of a Labview Based Time-Frequency Domain Reflectometry Real Time System for the Load Impedance Measurement (부하 임피던스 측정을 위한 랩뷰기반 시간-주파수 영역 반사파 실시간 시스템 구현)

  • Park, Tae-Geun;Kwak, Ki-Seok;Park, Jin-Bae;Yoon, Tae-Sung
    • Proceedings of the KIEE Conference
    • /
    • 2006.07d
    • /
    • pp.1803-1804
    • /
    • 2006
  • The purpose of this paper is to implement a Labview based TFDR Real Time system through the instruments of Pci eXtensions for Instrumentation(PXI). The proposed load impedance measurement algorithm was verified by experiments via the implemented real time system. The TFDR real time system consisted of the reference signal design, signal generation, signal acquisition, algorithm execution and results display parts. To implement real time system, all of the parts wore programmed by the Labview which is one of graphical programming languages. In the application software implemented by the Labview we were able to design a suitable reference signal according to the length and frequency attenuation characteristics of the target cable and controled the arbitrary waveform generator(ZT500PXI) of the signal generation part and the digital storage oscilloscope(ZT430PXI) of the signal acquisition part. By using the TFDR real time system with the terminal resistor on the target cable, we applied to the load impedance measurements. In the proposed load impedance algorithm a normalized time-frequency cross correlation function and a cross time-frequency distribution function was employed to calculate the reflection coefficient and phase difference between the input and the reflected signals.

  • PDF

Analysis of Partial Discharge in High Voltage Motor Model Coils (고압전동기 모델 코일에서 부분방전 분석)

  • Kim, Hee-Dong
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.55 no.4
    • /
    • pp.178-182
    • /
    • 2006
  • Five model coils of 6.6 kV motor were manufactured with several defects. These stator coils have artificial defects such as void of groundwall insulation, removal of semi-conductive coating and damage of strand insulation. Epoxy-mica coupler(80 pF) was connected to five model coil terminals. The voltage applied to the coils was 3.81 kV, 4.76 kV, 6.0 kV and 6.6 kV, respectively. Partial discharge(PD) tests performed in the laboratory and shield room. Digital PD detector(PDD) and turbine generator analyzer(TGA) were used to measure PD activity. TGA summarizes each plot with two quantities such as the normalized quantity number(NQN) and the peak PD magnitude(Qm). The PD levels in pC were measured with PDD. PD patterns of model coils were indicated the internal and slot discharges. PD patterns are consistent with the result of measurement using PDD and TGA instruments. AC breakdown test was performed on five model coils in order to confirm the result of PD measurements. All the failures were located in a line-end coil at the exit from the core slot.

Analysis of On-Line Partial Discharge Patterns in High Voltage Motor Stator Windings (고압전동기 고정자 권선의 운전중 부분방전 패턴 분석)

  • Kim, Hee-Dong;Ju, Young-Ho
    • Proceedings of the KIEE Conference
    • /
    • 2003.07c
    • /
    • pp.1824-1827
    • /
    • 2003
  • During normal machine operation, partial discharge(PD) measurements were performed with turbine generator analyzer(TGA) in two high voltage motors. Two 6.6kV motors were installed with 80pF capacitive couplers at the terminal box. The PD patterns were displayed two dimensional and three dimensional. TGA summarizes each plot with two quantifies such as the normalized quantity number(NQN) and the peak PD magnitude(Qm). Off-line PD measurements were conducted on one 4.16kV motor. The motor was energized to 2.4kV, 3.0kV, 3.5kV and 4.16kV, respectively. The PD levels in pC were measured with a conventional digital PD detector. The comparison of positive to negative PD indicates whether the defect elements of PD are within the insulation or on the insulation surface. Discharge at conductor surface was discovered in No. 1 motor. Internal discharges were generated in phase A, B and C of No. 2 motor, Slot discharges occurred in three phases of No. 3 motor.

  • PDF

Analysis of Insulation Condition in High Voltage Motor Model Coils (고압전동기 모델 코일의 절연상태 분석)

  • Kim, Hee-Dong;Kong, Tae-Sik;Kim, Byeong-Rae
    • Proceedings of the KIEE Conference
    • /
    • 2003.07c
    • /
    • pp.1612-1614
    • /
    • 2003
  • 80pF capacitive couplers were connected to six 6.6kV motor model coil terminals. The voltage applied to the coils were 3.81kv, 4.76 kV and 6.6kV, respectively. These stator coils have various types of artificial insulation defects such as large voids, semi-conductive coating damage and strand insulation fault. Digital PD detector(PDD) and turbine generator analyzer(TGA) were used to measure PD activity. TGA summarizes each plot with two quantities such as the normalized quantity number(NQN) and the peak PD magnitude(Qm). The PD levels in PD were measured with a conventional digital PD detector. Most of the defect mechanism of large motor stator winding can be associated with PD patterns such as internal and slot discharges. PD patterns coincide with PDD and TGA. These instruments have an input bandwidth of 40-400kHz and 0.1-350MHz. Surge testing detects faults in inter-turn winding of high voltage motor model coils.

  • PDF

A Technique of Watermark Generation and Similarity Embedding for Still Images Based on Cross Reference Points (교차참조점에 기반한 정지영상의 워터마크 생성 및 유사성 삽입 기법)

  • Lee, Hang-Chan
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.56 no.8
    • /
    • pp.1484-1490
    • /
    • 2007
  • The Cross Reference Point(CRP) is a robust method for finding salient points in watermarking systems because it is based on the geometrical structure of a normalized image in order to avoid pointing error caused by digital attacks. After normalization of an image, the 100 CRPs are calculated. Next, the 100 blocks centered by CRPS are formed. These 100 blocks are arranged using a secrete key. Each boundary of 50 out of 100 blocks is surrounded by 8 blocks which are selected by the ordered number of a preceding block. This number is a seed of random number generator for selecting 8 out of 50 blocks. The search area of a center block is formed by a secrete key. The pixels of a center block are quantized to 10 levels by predefined thresholds. The watermarks are generated by the 50 quantized center blocks. These watermarks are embedded directly in the remaining 50 blocks. In other words, 50 out of 100 blocks are utilized to generate watermarks and the remaining 50 blocks are used to watermark embedding. Because the watermarks are generated in the given images, we can successfully detect watermarks after several digital attacks. The reason is that the blocks for the generation and detection of watermarks are equally affected by digital attacks except for the case of local distortion such as cropping.

Echo Canceller with Improved Performance in Noisy Environments (잡음에 강인한 반향 제거기 연구)

  • 이세원;박호종
    • The Journal of the Acoustical Society of Korea
    • /
    • v.22 no.4
    • /
    • pp.261-268
    • /
    • 2003
  • Conventional acoustic echo cancellers using ES algorithm have simple structure and fast convergence speed compared with those using NLMS algorithm, but they are very weak to external noise because ES algorithm updates the adaptive filter taps based on average energy reduction rate of room impulse response in specific acoustical condition. To solve this problem, in this paper, a new update algorithm for acoustic echo canceller with stepsize matrix generator is proposed. A set of stepsizes is determined based on residual error energy which is estimated by two moving average operators, and applied to the echo canceller in matrix from, resulting in improved convergence speed. Simulations in various noise condition show that the proposed algorithm improves the robustness of acoustic echo canceller to external noise.