• Title/Summary/Keyword: indoor wiring

Search Result 18, Processing Time 0.023 seconds

Extraction of Series Arc Signals Based on Wavelet Transform in an Indoor Wiring System

  • Ji, Hong-Keun;Cho, Young-Jin;Wang, Guoming;Hwang, Seong-Cheol;Kil, Gyung-Suk
    • Transactions on Electrical and Electronic Materials
    • /
    • v.18 no.4
    • /
    • pp.221-224
    • /
    • 2017
  • This paper dealt with the extraction of series arc signals based on wavelet transform in order to improve the accuracy of arc detection in indoor wiring systems. Three types of arc sources including a cord-cord, a terminal-cord, and an outlet-plug were fabricated to simulate typical arc defects. An arc generator fabricated according to UL 1699 was used to generate arcs. The optimal mother wavelet was selected as bior1.5 by calculating the correlation coefficients between the detected single current pulse and the wavelet. The detected arc current signals were then decomposed into eight levels using the discrete wavelet transform that implements the multi-resolution analysis method. By analyzing the decomposed components, the detail components D6, D7, and D8 were associated with arc signals, which were used for signal reconstruction. From the result, it was verified that the proposed method can be used for the extraction of the series arc signal from the AC mains, which is expected to be applied to further analysis of arc signals in indoor wiring systems.

A Study on Intelligent Technique for Correlation Application of Overcurrent and Leakage Current Signals in the Indoor Wiring (옥내배선에서 과전류와 누전 신호의 상관관계 적용을 위한 지능형 기법 연구)

  • Kim, Doo-Hyun;Kim, Eun-Jin;Kim, Sung-Chul
    • Journal of the Korean Society of Safety
    • /
    • v.30 no.4
    • /
    • pp.14-19
    • /
    • 2015
  • The purpose of this paper is to study the correlation application that electrical fire causes occurs for overcurrent and leakage current signals in the indoor wiring. In the order to purpose, the causes data of overcurrent, or leakage current of electrical fire are drawn out referring to past studies, consulting with experts and experimental data. The correlation application was then applied with fuzzy logic of intelligent technique. To check the reliability and performance of the correlation application, modified center of area(CoA) was adopted to calculate the possibility that electrical fire occurs, whose value was then compared to the results. The chance of electrical fire calculated is higher when two causes of fire are put into the CoA of the correlation application of this paper than that of when each cause is separately put into the CoA. The correlation application developed in this study enables better analysis on possible electrical fire due to overcurrent, or leakage current and provides managers with the possibility of electrical fire so that they can better manage at a time of overcurrent, or leakage current.

Detection Technique of Tracking at Indoor Wiring using Neural Net work (신경회로망을 이용한 옥내배선의 트랙킹 검지 기법)

  • 최태원;이오걸;김석순;이수흠;정원용
    • Fire Science and Engineering
    • /
    • v.9 no.1
    • /
    • pp.3-9
    • /
    • 1995
  • This paper is a study to dectect the tracking owing to deterioration of indoor wiring, and to prevent the electrical fire. After analysing the harmonics of waveshapes in load current and tracking current by FFT, a method of identifying the tracking was developed by using neural network. Fluoscent lamp, witch was mostly used in indoor, was chosen as the load used in this study. When the learning number in neural network was more then 30,000 times, an excellent neural net-work which could correctly identify the tracking was established. Therefore, the result of this study can be utilized as a basic material in various measuring instruments, such as an hotline inslation tester, earth tester in vehicles, and tracking fire alarm device, witch can detect the tracking under the condition of hotline.

  • PDF

Studies on Generation and Detection of Discharge Signals in a Low-voltage Outlet (저압용 전열수구에서 방전 신호의 발생과 검출에 관한 연구)

  • Kil, Gyung-Suk;Song, Jae-Yong;Seo, Hwang-Dong;Moon, Seung-Bo;Cho, Young-Jin;Hwang, Don-Ha
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.54 no.11
    • /
    • pp.498-502
    • /
    • 2005
  • The objectives of this paper are to provide information on the characteristics of the discharge signals in a low-voltage indoor outlet. Most of electrical fires are caused by short circuits, overheating of wires, deterioration and incomplete connection of wiring devices. The last two cases are predictable before the occurrence of fire because of its slow progress. We have simulated the discharge signals caused by the deterioration and incomplete connection of wiring devices using aged outlets. From the experimental data, we could characterize the frequency spectrums of the discharge signals depending on the cases. The higher frequency components of the signal are attenuated by the capacitance and inductance of power lines as the measuring point is getting away from the discharges. Main frequency components of the discharge signal are existent at 600kHz - 1.5MHz in incomplete connections and at 210H7z - 8MHz in deteriorations of the outlet.

Electrical and Fire Prevention Measures through Improvement of Indoor Wiring, Outlets and Plugs (옥내배선, 콘센트 및 플러그 개선을 통한 전기화재 예방대책)

  • Jeung, Sueng Hyo;An, Hui-Seok;Lee, Yong-Su;Kim, Chang-Eun
    • Journal of the Korea Institute of Construction Safety
    • /
    • v.1 no.1
    • /
    • pp.31-39
    • /
    • 2018
  • It is reported that about 20 % of all fires in Korea are caused by the electric equipment and installations. In complex and large-scale buildings, the sizes of electric fires are becoming larger as property damage and casualties increase. Among the causes of various electric fires, fire by short circuit accounts for about 71.5% of overall fires, and in the classification by electric equipment and installation, fire caused by wiring and wiring equipment accounts for approximately 38.3% of overall fires. The purpose of this study is to propose methods to prevent electric fires due to short circuit by improving indoor wiring currently in use and to find the fundamental measures to prevent wiring equipment caused fires by improving the socket and plug which are commonly used in wiring equipment. It is expected that the electric fire prevention measures presented through this study can be used as a measure to protect many people and properties by eliminating the root cause of electric fire.

Analysis for Electrical Fire Possibility Using Fuzzy Logic with Input Variables of Overcurrent and Saturation Time in the Indoor Wiring (전기배선에서 과전류와 포화시간을 입력변수로 갖는 퍼지기반 전기화재가능성 분석)

  • Kim, Eun-Jin;Kim, Doo-Hyun;Kim, Sung-Chul
    • Journal of the Korean Society of Safety
    • /
    • v.30 no.6
    • /
    • pp.34-39
    • /
    • 2015
  • The study is aimed to develop fuzzy logic system that has overcurrent and saturation time as input variable and possibility of electrical fire as output variable by making bad conductor area with physical damage to indoor wiring. Most previous studies focused on thermal characteristics depending on the current size and no study considered the current size and saturation time at the same time. Therefore, the paper made into account current value and saturation time together. To this end, it created bad conductor area half the size of IV conductor (1.6 mm) on purpose and transmit electrical current from 10A to 60A by unit of 2A to find out the thermal characteristics and saturation time for current. Based on the data that came out, the study applied fuzzy logic and established the current and saturation time as input variable and chance of fire as output variable. As a result, the center of area of the system that depended only on the existing current value was 75 while the system that applied both current and saturation time presented the chance of fire at 92. It is found that the chance of bad conductor area and deteriorated insulation of electrical wire had current and saturation time as important variables. The data can be used as basic data like deteriorated wire insulation or operation features of circuit breaker in investigating the cause of electrical fire.

Issues and Improvement Methods of the Bridge Tab in Customer Premises Telecommunications Facilities for High-Speed Communication Network (초고속통신망을 위한 구내통신 설로설비의 브릿지 탭의 문제점과 개선 방안)

  • Min, Gyeong-Ju;Hong, Jae-Hwan;Nam, Sang-Sig;Kim, Jeong-Ho
    • The KIPS Transactions:PartC
    • /
    • v.13C no.7 s.110
    • /
    • pp.881-888
    • /
    • 2006
  • The position of the bridged tap is determined by that of the outlet in most modern apartments, since most of the indoor wiring utilizes the bus wiring structure when deploying the indoor communication line. These bridged taps deteriorate transmission performance in the specific frequency at the time of high-speed multimedia communication, which uses a high frequency bandwidth, since the duality of return loss worsens and line attenuation increases rapidly. As a result, analysis on this phenomenon is required. In this study, the test model is created by modeling the intercommunication facility of the apartment that is the most representative residential house type, and by understanding the structure and the environment of the indoor wiring. Also, how the bridge tap affects performance is analyzed when the VDSL service is provided, so that problems of intercommunication lines can be identified and methods for improving the proper intercommunication line can be suggested, which is suitable for accommodating high-speed multimedia service of the future.

A Study on the High Speed Interruption of Parallel Arcing (병렬아크의 고속차단에 관한 연구)

  • Kil, Gyung-Suk;Ji, Hong-Keun;Park, Dae-Won;Kim, Il-Kwon;Kim, Young-Il;Cho, Young-Jin
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.22 no.12
    • /
    • pp.95-100
    • /
    • 2008
  • Conventional Earth Leakage Circuit Breakers (ELCBs) have defects of a breaking failure or a long breaking-time against parallel arc current. In this paper, breaking characteristics of conventional ELCBs were analyzed by simulation of parallel arc in a low-voltage indoor wiring system, and an air-core current sensor and a signal converter being most available for parallel arc detection were developed and applied to a conventional ELCB. The proposed tripped the ELCB regardless of the location of parallel arc. The breaking-time was in ranges of $1.74{\sim}8.3[ms]$ depending on the phase of arc generation, which is about 5 times as fast as conventional ELCBs with the breaking-time of 50[ms].

A Study on the Series Arc Detection in Low-voltage Wiring Systems (저압배선계통에서 직렬아크의 검출에 관한 연구)

  • Kim, Il-Kwon;Park, Dae-Won;Choi, Su-Yeon;Park, Chan-Yong;Kim, Hwang-Kuk;Kil, Gyung-Suk
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.21 no.2
    • /
    • pp.182-187
    • /
    • 2008
  • This paper dealt with the detection algorithm of series arcing, which is a cause of electric fires in low-voltage wiring systems. To find the distinguished electrical features of series arc, we simulated series arcing by the arc generator specified in UL1699. An electric heater, an inverter-controlled vacuum cleaner, and a phase-controlled incandescent lamp were used as loads to generate series arcing. A high-pass filter (HPF) with the low cut-off frequency of 3 kHz at -3 dB was fabricated and applied to separate the series arc signal from the AC voltage source. The experiment showed that the high frequency signal generates randomly during series arcing, and the phase-controlled incandescent lamp produces high frequency pulses even in normal state. In this case, the magnitude, the width, and the randomness of high frequency signal should be analyzed to estimate series arcing precisely.

A Field Study on the Standard of Electric Branch Circuit and Receptacle in Apartment (공동주택의 분기회로 및 콘센트 수 기준설정에 관한 조사연구)

  • 정지열;김채규;김호식
    • The Proceedings of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.5 no.2
    • /
    • pp.67-76
    • /
    • 1991
  • This study showes suitable number of branch circuit and receptacle in residential apartments and houses by surveying and analyzing using practic of consents and domestic electic machinery, layout of indoor furniture This results will offer optimum design of wiring equipment, increse saftety and convienience when residents use domestic electic machinery and interior wiring devices.

  • PDF