Browse > Article
http://dx.doi.org/10.4313/JKEM.2008.21.2.182

A Study on the Series Arc Detection in Low-voltage Wiring Systems  

Kim, Il-Kwon (한국해양대학교 전기전자공학부)
Park, Dae-Won (한국해양대학교 전기전자공학부)
Choi, Su-Yeon (한국해양대학교 전기전자공학부)
Park, Chan-Yong (한국해양대학교 전기전자공학부)
Kim, Hwang-Kuk (한국해양대학교 전기전자공학부)
Kil, Gyung-Suk (한국해양대학교 전기전자공학부)
Publication Information
Journal of the Korean Institute of Electrical and Electronic Material Engineers / v.21, no.2, 2008 , pp. 182-187 More about this Journal
Abstract
This paper dealt with the detection algorithm of series arcing, which is a cause of electric fires in low-voltage wiring systems. To find the distinguished electrical features of series arc, we simulated series arcing by the arc generator specified in UL1699. An electric heater, an inverter-controlled vacuum cleaner, and a phase-controlled incandescent lamp were used as loads to generate series arcing. A high-pass filter (HPF) with the low cut-off frequency of 3 kHz at -3 dB was fabricated and applied to separate the series arc signal from the AC voltage source. The experiment showed that the high frequency signal generates randomly during series arcing, and the phase-controlled incandescent lamp produces high frequency pulses even in normal state. In this case, the magnitude, the width, and the randomness of high frequency signal should be analyzed to estimate series arcing precisely.
Keywords
Series arc; Detection technique; Indoor wiring system; Electric fires; UL1699; Arc discharge signal;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 김향곤, 길형준, 김동욱, 김동우, 최충석, '전기기기용 비닐절연전선에서의 직렬 아크에 의한 열화 특 성 분석', 한국전기전자재료학회 2006하계학술대 회논문집, p. 234, 2006
2 이상호, 오홍석, '전기화재 예방을 위한 EFPCD 동작 특성에 관한 연구', 한국화재.소방학회, 16 권, 3호, p. 8, 2002
3 G. D. Gregory and G. W. Scott, 'The arc-fault circuit interrupter : an emerging', IEEE Trans. on Industry Applications, Vol. 34, No. 5, p. 928, 1998   DOI   ScienceOn
4 G. D. Gregory, K. Wong, and R. F. Dvorak, 'More about arc-fault circuit interrupters', IEEE Trans. on Industry Applications, Vol. 40, No. 4, p. 1006, 2004   DOI   ScienceOn
5 KESCO, 'A Statistical Analysis on the Electric Accident', KESCO Report, Vol. 15, p. 7, 2006
6 KOSHA, 'Prevention Countermeasure Research of the Accident which is caused by in Electric Arc', KOSHA 2006 Report, p. 24, 2006
7 오홍석, 이상호, 김풍래, '전기화재 예방에 관한 연구', 한국화재.소방학회 춘계학술논문발표회, p. 134, 2002   과학기술학회마을
8 Underwriters Laboratories, 'UL1699-Standard for Arc-Fault Circuit-Interrupters', p. 49, 2006
9 C. Li, F. Dawson, H. Kojori, C. Meyers, and E. Yue, 'Arc Fault Detection and Protection- Opportunities and Challenges', SAE Technical Papers, 2003-01-3037, p. 591, 2003