• Title/Summary/Keyword: gas mixture explosion

Search Result 52, Processing Time 0.033 seconds

A Study on The Ignition Limit of Flammable Gases by Discharge Spark of Resistive Circuit (저항회로의 개폐불꽃에 의한 폭발성 가스의 점화한계에 관한 연구)

  • Lee Chun-Ha
    • Journal of the Korean Institute of Gas
    • /
    • v.1 no.1
    • /
    • pp.106-112
    • /
    • 1997
  • This study measured the ignition limits of methane-air, propane-air, ethylene-air, and hydrogen-air mixture gases by discharge spark of D.C. power resistive circuit. The used experimental device is the IEC type spark ignition test apparatus, it consists of explosion chamber and supply -exhaust system of mixture gas. Mixture gases (methane-air, propane-air, ethylene-air, and hydrogen-air) were put into explosion chamber of IEC type spark ignition test apparatus, then it was confirmed whether ignition was made by 3,200 times of discharge spark between tungsten electrode and cadmium electrode. The ignition limits were found by increasing or decreasing the value of current. For the exact experiment, the ignition sensitivity was calibrated before and after the experiment in each condition. The ignition limits were found by changing the value of concentration of each gas-air mixture in D.C. 24 [V] resistive circuit. As the result of experiment, it was found that the minimum ignition limit currents exist at the value of methane-air 8.3 [$Vol\%$], propane-air 5.25[$Vol\%$], ethylene-air 7.8 [$Vol\%$], and hydrogen-air 21[$Vol\%$] mixture gases. For each the minimum ignition concentration of gases, the relationships between voltage and minimum ignition current were found. The results are as follows. - The minimum ignition limits are decreasing in the order of methane, propane, ethylene, and hydrogen. - The value of ignition current is inversely proportional to the value of source voltage. - The minimum ignition limit currents increase sharply at more than 2 [A]. The reason is caused by overheating the electrode.

  • PDF

Influence of Mixture Non-uniformity on Methane Explosion Characteristics in a Horizontal Duct (수평 배관의 메탄 폭발특성에 있어서 불균일성 혼합기의 영향)

  • Ou-Sup Han;Yi-Rac Choi;HyeongHk Kim;JinHo Lim
    • Korean Chemical Engineering Research
    • /
    • v.62 no.1
    • /
    • pp.27-35
    • /
    • 2024
  • Fuel gases such as methane and propane are used in explosion hazardous area of domestic plants and can form non-uniform mixtures with the influence of process conditions due to leakage. The fire-explosion risk assessment using literature data measured under uniform mixtures, damage prediction can be obtained the different results from actual explosion accidents by gas leaks. An explosion characteristics such as explosion pressure and flame velocity of non-uniform gas mixtures with concentration change similar to that of facility leak were examined. The experiments were conducted in a closed 0.82 m long stainless steel duct with observation recorded by color high speed camera and piezo pressure sensor. Also we proposed the quantification method of non-uniform mixtures from a regression analysis model on the change of concentration difference with time in explosion duct. For the non-uniform condition of this study, the area of flame surface enlarged with increasing the concentration non-uniform in the flame propagation of methane and was similar to the wrinkled flame structure existing in a turbulent flame. The time to peak pressure of methane decreased as the non-uniform increased and the explosion pressure increased with increasing the non-uniform. The ranges of KG (Deflagration index) of methane with the concentration non-uniform were 1.30 to 1.58 [MPa·m/s] and the increase rate of KG was 17.7% in methane with changing from uniform to non-uniform.

A STUDY ON THE EXPLOSION SAFETY ASSESSMENT OF HYDROCARBON REFRIGERANT REFRIGERATOR

  • Oh, Kyu-Hyung;Kim, Min-Kyu;Chu, Euy-Sung;Lim, Byung-Han;Kim, Man-Hoe;Park, Yoon-Ser
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 1997.11a
    • /
    • pp.289-296
    • /
    • 1997
  • This paper discribes an experimental explosion risk assessment study on refrigerators containing flammable hydrocarbon refrigerant. A refrigerator used in this study is a larder fridge type, 215 liter in volume. The hydrocarbon refrigerant used in the refrigerator is iso-butane(C$_4$H$_{10}$). For the explosion safety assessment of the refrigerator, temperature of compressor, cooling air circulation fan motor, defrost heater and inner lamp were measured during the operation. And to confirm the ignitablity of flammable gas by the electric spark of the switches of the refrigerator, ON-OFF test of all switches were conducted with compulsorily near the stoichiometric concentration atmosphere of iso-butane-air mixture. As the result of experiment above mentioned and another experiment for the explosion safety assessment, we can conclude that explosion hazard in connection with the use of hydrocarbon refrigerant was few.w.

  • PDF

PIV Measurements on the Flame Initiation and Propagation under Gas Explosions by Electrostatic Discharge Energies in a Confined Chamber with an Obstacle (장애물이 있는 챔버 내부의 정전기 방전 에너지에 의한 가스 폭발시 초기화염과 화염전파 특성에 대한 PIV 계측)

  • Park, Dal-Jae;Lee, Seok-Hwan;Sung, Jae-Yong;Lee, Young-Soon
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.33 no.9
    • /
    • pp.682-687
    • /
    • 2009
  • In order to investigate the effects of three different electrostatic discharge energies on gas explosions, a high-speed PIV system has been applied. The present study paid attention to the flame initiation by the gas explosions and its propagation at the existence of an obstacle within a chamber. Three different ignition energies such as 0.56 mJ, 52.87 mJ and 112.5 mJ were used. It is found that the ignition kernel is bent by the electrostatic discharge during the flame initiation. Tangential velocities of unburnt mixture ahead of initially propagating flame fronts are increased with increasing ignition energy, which makes the flame propagation faster before it reaches the obstacle. Although the flame speed was found to be less sensitive to the ignition energies, the flame developments were different. The effects of the energies on explosion pressures were also discussed.

Electrostatic Discharge and the Minimum Ignition Energy Measurement of Three-Component Flammable Gas Mixtures (정전기(靜電氣) 방전(放電)과 삼성분계(三成分系) 가연성(可燃性) 혼합기체(混合氣體)의 최소점화(最小點火) Energy 측정(測定)에 관한 연구(硏究))

  • Lee, Gwan-Hyung;Choi, Sang-Won;Chung, Jae-Hee;Lee, Duck-Chool
    • Proceedings of the KIEE Conference
    • /
    • 1997.07e
    • /
    • pp.1819-1823
    • /
    • 1997
  • When flammable gases are mixed with air or oxygen in the explosion concentration range and are ignited by sufficiently large electrostatic discharge energy, they may explode causing severe disaster in workplaces. The minimum ignition energy (MIE) of single gas-air mixtures has been already investigated by many researchers, but the MIE of mixtures of more than three substances is not examined yet. The purpose of this study is to investigate the MIE of several three-component gas mixtures experimentally. The result of our experiment shows that the MIE of some gas mixtures is quite different from that we expected based on the characteristics of individual gas-air mixture.

  • PDF

Experimental Study on the Characteristics of Brown Gas (브라운가스의 특성에 대한 실험적 연구)

  • Kim Chang-Hee;Oh Kyu-Hyung;Kang Kyung-Soo;Park Chu-Sik;Bae Ki-Kwang;Kim Jong-Won
    • Proceedings of the Korea Society for Energy Engineering kosee Conference
    • /
    • 2006.05a
    • /
    • pp.262-262
    • /
    • 2006
  • The characteristics of Brown gas was experimentally studied in view of efficiency and flame propagation. For this study, the Brown gas stack with 7 cells was manufactured following the Brown gas related patents and reports. All measuring equipments were re-tested and calibrated by Korea Laboratory Accreditation Scheme (KOLAS) certified laboratories. Since the amount of produced gas is most crucial in determining the efficiency, we adopted two gas collecting methods such as bottle trap method and wet gas meter method. The energy efficiency of our own fabricated stack was measured to be 75%, which is comparable to general alkaline water electrolysis efficiency. In order to analyze the flame propagation characteristics of Brown gas, we measured the flame propagation pressure, velocity, and shape by using strain type pressure sensor, optical sensor, and high speed camera in conjunction with Schliren system, respectively. From the experimental results, it was found that the flame propagation behavior of Brown gas was almost the same as that of hydrogen and oxygen mixture gas in 2:1 molar ratio. Moreover, from the high speed camera analysis, we concluded that Brown gas flame exhibits explosion behavior as does mixture gas ($H_{2}:O_{2}=2:1$).

  • PDF

A Study of Establishment of the Infrastructure for Consequence Analysis of Metallic Dust Explosion (금속성 분진폭발의 영향 분석을 위한 기반구축에 관한 연구)

  • Jang, Chang Bong;Lee, Kyung Jin;Moon, Myong Hwan;Baek, Ju Hong;Ko, Jae Wook
    • Journal of the Korean Institute of Gas
    • /
    • v.21 no.4
    • /
    • pp.84-91
    • /
    • 2017
  • Recent years have witnessed the increased usage of flammable metals, such as aluminum or magnesium, in wide range of high-tech industries. These metals are indispensable for the improvement of physical properties of materials as well as the design capability of the final product. During the process, unwanted metal dusts could be released to the environment. This can lead to an occupational health and safety issues. Due to their flammable nature, more serious problem of an explosion can happen in extreme cases. The explosion is the combustion of tiny solid particles and vapor mixture, caused by pyrolysis. This complex composition makes engineering analysis more difficult, compared to simple gas explosions or vapor cloud combustions. The study was conducted to assess this light metal dust explosion in an effort to provide the bases for a risk assessment. Dust explosion characteristics of each material was carefully evaluated and an appropriate analysis tool was developed. A comprehensive database was also constructed and utilized for the calibration of the developed response model and the verification for its accuracy. Subsequently, guidelines were provided to prevent dust explosions that could occur in top-notch industrial processes.

Prediction of Damage Area due to Explosion of LNG-Hydrogen Mixed Gas (도시가스-수소 혼합가스의 누출사고 영향범위 분석)

  • Chan-sik, Yoon;Jin-du, Yang;Gil-soo, Na;Sung-Hyun, Im;Ki-young, Kim;Eun-ki, Choi
    • Explosives and Blasting
    • /
    • v.40 no.4
    • /
    • pp.27-34
    • /
    • 2022
  • The government is promoting various policies to reduce greenhouse gas emissions for carbon neutrality, one of the key tasks is to revitalize the hydrogen economy. As one of these policies the government has formulated a plan to incorporate hydrogen into existing city gas pipes, and aims to commercialize 20% hydrogen mixing by 2026. In preparation for the commercialization of city gas and hydrogen mixture, this study quantitatively predicts the scale of damage and the range of impact in the event of leakage of these two gas mixtures. The quantitative damage prediction method is to calculate the damage conversion distance through the calculation of the TNT equivalent by setting the leakage amount of the gas mixture in the event of an accident under a virtual scenario.

A Study on the Ignition of Hydrogen-Air Mixture Gas by Spark of Rechargeable Battery (2차 전지의 방전에 의한 수소-공기 혼합가스의 점화에 관한 연구)

  • Lee Chun-Ha;Kwon Byung-Cuck;Oh Jong-ryong
    • Journal of the Korean Society of Safety
    • /
    • v.19 no.3 s.67
    • /
    • pp.32-39
    • /
    • 2004
  • This papers describes on the experimental consideration for the intrinsically-safe explosion-proof capability of rechargeable battery's body about main item rechargeable battery and cellular phone battery which is selling in domestic that IEC(International Electrotechnical Commission) recommend the measurement of ignition limit by short circuit of rechargeable battery and temperature increase test to use a explosion grade Group IIC type of explosion-proof type apparatus test an object of hydrogen gas. Because of that there are many different results for existence or nonexistence for ignition by different company and different types. It is concluded that the maximum of self temperature increasing by spark circuit of rechargeable battery is $180^{\circ}C$ in case of Nickel-Hydrogen and $110^{\circ}C$ in case of Nickel-Cadmium. The reaction of cellular battery for external temperature have following processes. It is confirmed that the temperature of reaction is rise slantly as the ambient temperature rising, then exterior shape of one is swell up and change when the temperature of ambient reach to about $130\~140^{\circ}C$, and when reach to about $160^{\circ}C$ the battery is blown up. Therefore, it is considered that have to be in considering selection of rechargeable battery using in itself due to different ignition limits of various rechargeable battery when the portable electric containing rechargeable battery are designed, produced and used, the characteristics and the proper safety factors of devices.

Consequence Analysis by Different DME-LPG Mixture Fuels (DME-LPG 혼합연료에 따른 사고결과 피해예측)

  • Park, Dal-Jae;Lee, Young-Soon
    • Journal of the Korean Institute of Gas
    • /
    • v.15 no.2
    • /
    • pp.57-62
    • /
    • 2011
  • DME(Dimethyl Ehther) is considered as an attractive fuel in terms of clean, environmentally friendly form of energy, multi-source and multi-purpose. As the physical properties of DME are almost similar to LPG, DME can be mixed with LPG and DME-LPG mixture fuels seem to be employed without major remodeling of the existing LPG supply infrastructure. However, little attention has been given to the effect of different DME-LPG mixture fuels on consequence analysis to adjacent facilities, buildings and etc. In this work, the consequence analysis by different DME-LPG mixture fuels has been done. The results were discussed in terms of release rate, jet fire, vapor cloud explosions, BLEVEs and etc. It was found that the consequences estimated from fire and explosion scenarios assumed were almost similar for both LPG and DME 20 %.