• Title/Summary/Keyword: fire simulations

Search Result 231, Processing Time 0.023 seconds

Study on the Method of Stack Effect Mitigation by the Elevator Shaft Pressurization at High-rise Buildings (고층건물에서 승강기 승강로 가압을 통한 연돌효과 저감 방법에 대한 연구)

  • Kim, Jin-Soo;Lee, Eui-Pyeong
    • Fire Science and Engineering
    • /
    • v.25 no.6
    • /
    • pp.178-183
    • /
    • 2011
  • In cold season, the elevator systems in super high-rise buildings would make noises at the door-gaps on high floors, and the elevator doors on the 1st floor would suffer from opening/closing trouble due to the pressure differences. Such pressure differences are also the main driving power of smokes through the hoistway in the case of fire. In addition, the pressure differences should be overcome to use the elevator systems as a measure of emergency escape. This paper reviews the way of hoistway pressurization to reduce the adverse influences. Simulations achieved a good result close to the requirements of NFPA 92A and IBC 2012 under the condition that the hoistway should be pressurized after pressure equalizing between floors and hoistway with the openings through the hoistway wall.

A Study on Performance Improvement Measures of Pressurized Smoke Control Systems for Exit Passageways of High-Rise Buildings (고층건축물의 피난경로 가압제연시스템 성능개선대책에 관한 연구)

  • Son, Bong-Sae;Kim, Jin-Soo
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.21 no.12
    • /
    • pp.703-714
    • /
    • 2009
  • One of the biggest problems in smoke control systems for high-rise buildings is stack effect, but there are no recognized methods or measures to solve the problem of stack effect as yet. The stack effect can be overcome by forming the uprising current inside the stair hall properly, but there is a limit to the height in supplying into the stair hall the smoke control air volume to be supplied to a floor in case of escape from fire. The limit to the height can be extended by over-coming the stack effect by pressurizing the stair hall and the ancillary room simultaneously. It can also be anticipated that the stack effect can be overcome by connecting the air supply shaft to the stair hall at the top. As a result of computer simulations using a network type of tool, it is found that adequate performance can be achieved by pressurizing the stair hall only for a building of 190m or less, and up to 360m when pressurizing the stair hall and the ancillary room simultaneously. In all those cases, however, an overpressure venting damper is required which operates within a suitable range for venting the overpressure outside.

On the Development of the Generic CFCS for Engineering Level Simulation of the Surface Ship (공학수준 수상함 지휘무장통제체계 범용 모델 개발방안 연구)

  • Jung, Young-Ran;Han, Woong-Gie;Kim, Cheol-Ho;Kim, Jae-Ick
    • Journal of the Korea Institute of Military Science and Technology
    • /
    • v.14 no.3
    • /
    • pp.380-387
    • /
    • 2011
  • In this paper, we considered the authoritative representation of Command and Fire Control System(CFCS) for the surface ship that was the engineering level model to develop system specifications and to analyze operational concepts on the concept design phase and to analyze military requirements, effectiveness and performance for the system. The engineering level model of CFCS can be used in simulation independently of the surface ship's type, and also it takes reuse, interoperability, and extension into consideration. The detailed sub-models, internal and external data interface, data flow among each sub-model, sensor and weapon models about the engineering level model of CFCS was defined. It was verified via engineering level simulations according to the V&V process.

Performance Improvement Approach to Naval Gun Fire Control System Based on Linear Target Tracking Filter with Radar Line-of-sight Measurements (레이다 시선 측정치를 활용하는 선형 표적 추적필터 기반 함포 사격제원계산장치 성능향상 방법)

  • Uisuk Suh
    • Journal of the Korea Institute of Military Science and Technology
    • /
    • v.27 no.4
    • /
    • pp.446-456
    • /
    • 2024
  • This paper addresses a novel approach to performance enhancement of the naval gun fire control system(FCS) by using the projectile tracking filter without any distortion of radar measurements. Under the assumption that the maneuvering between the projectile and the ship equipped with the radar is not quite large, this method is based on the concept of polar-coordinate target tracking, which separates the range estimation filter and the direction cosine estimation filter. Note that using polar-coordinates allows tracking to be performed in the same coordinate system from which the radar line-of-sight(LOS) measurements are obtained, unlike the conventional tracking process in Cartesian. Also, it is easy to implement in real-time and guarantees consistent estimates due to its linear filter structure. With the help of the above method, therefore, the proposed filter is able to improve the overall performance of FCS which requires stability of projectile estimates within a short engagement time. The effectiveness of the presented scheme is validated through computer simulations.

Development of Digital Twin and Intelligent Monorail Robot for Road Tunnel Smart Management (도로 터널 스마트관리를 위한 디지털 트윈 및 지능형 레일 로봇 개발)

  • Youngwoo Sohn;Jaehong Park;Eung-Ug Kim;Young Sik Joung
    • Journal of the Korean Society of Industry Convergence
    • /
    • v.27 no.1
    • /
    • pp.25-37
    • /
    • 2024
  • The objective of this study was to create intelligent rail robots that are optimized for facility management and implement digital twin systems for smart road tunnel management. An autonomous surveillance system is formed by combining the sensing platform consisting of railing robots, fixed cameras and environmental detection sensors with the digital twin data platform technology for tunnel monitoring and early fire suppression. In order to develop mobile rail robots for fire extinguishing, we also designed and manufactured robots for extinguishing & monitoring and fire extinguishing devices, and then we examined the optimization of all parts. Our next step was to build a digital twin for road tunnel management by developing continuous image display system and implementing 3D modeling. After constructing prototypes, we attempted simulations by configuring abnormal symptom scenarios, such as vehicles fires. This study's proposal proposes high-accuracy risk prediction services that will enable intelligent management of risks in the tunnel with early response at each stage, using the data collected from the intelligent rail robots and digital twin systems.

Influence of Radiant Heat Flux on Combustion Properties of Flame Retardant Cable (케이블의 난연성능에 따른 복사 열유속이 연소물성에 미치는 영향)

  • Mun, Sun-Yeo;Hwang, Cheol-Hong
    • Fire Science and Engineering
    • /
    • v.33 no.3
    • /
    • pp.29-36
    • /
    • 2019
  • The combustion properties required for fire simulations of multi-layer, multi-component flame retardant cables were measured using a cone calorimeter. The CO and soot yields combustion efficiencies of the flame retardant cables were investigated. TFR-8 (flame retardant PCV and XLPE added), TFR-CVV-SB (flame retardant PCV and general PVC), and VCTF, which are excellent in the flame retardancy of cables, were considered. As the main result, the CO yield (yCO) of the TFR-8 and TFR-CVV-SB flame retardant cables increased by 23% and 16%, respectively, with increasing incident radiation heat flux from 25 kW/㎡ to 50 kW/㎡. On the other hand, the CO yield of VCTF was not influenced significantly by the changes in radiant heat flux. Finally, the soot yield and combustion efficiency increased as the sheath material (flame retardant performance) was strengthened. Therefore, in a fire environment where various heat fluxes coexist, attention should be paid to the top of the application of the combustion property of the flame retardant cable.

Experimental and Numerical Studies on Heat/Smoke Behavior due to a Fire on Underground Subway Platform (II) - Numerical Approach - (지하철 역사 승강장 화재발생시 열/연기 거동 분석을 위한 실험 및 수치 연구(II) - 수치적 접근 -)

  • Chang, Hee-Chul;Kim, Tae-Kuk;Park, Won-Hee;Kim, Dong-Hyeon
    • Fire Science and Engineering
    • /
    • v.20 no.3 s.63
    • /
    • pp.15-20
    • /
    • 2006
  • In this study the flow characteristics of smoke and heat on a bank type platform of the underground subway station are studied numerically by considering two different emergency operation modes. Effects of the natural flow through the tunnel and the stair ways are considered in the numerical simulations by using the measured velocities presented in Part I as the boundary condition. Distributions of heat, smoke, visible range and toxic gas on the platform are analysed for different smoke extraction flowrates corresponding to the two different emergency operation modes. The numerical results show that the extraction flowrate affects the smoke control performance significantly by improving the smoke removal performance as the extraction flowrate is increased.

Effects of Char Produced from Burning Wood Combustibles on Thermal Pyrolysis (목재 가연물의 연소 시 생성되는 탄화가 열분해에 미치는 영향)

  • Hong, Ter-Ki;Ryu, Myung-Ho;Lee, Jong Won;Park, Seul-Hyun
    • Fire Science and Engineering
    • /
    • v.33 no.5
    • /
    • pp.7-12
    • /
    • 2019
  • To investigate the influence of the char layer formed during the combustion process on the pyrolysis of wood combustibles, ISO 5660-1 cone calorimetry experiments and Fire dynamics simulator (FDS) simulations were performed, and the results from these two methods were compared. The wood combustible selected as the fuel for this study, Douglas fir, has been widely used for the production of building materials, furniture, etc. The heat release rate (HRR) measured from the cone calorimetry experiment was in good agreement with the result predicted by the FDS simulation. However, the FDS simulation failed to predict the heat released by the smoldering combustion process, due to the absence of the char surface reaction in the model. The FDS simulation results clearly indicate that the char layer formed on the surface of combustibles produces a thermal barrier which prevents heat transfer to the interior, thickening the thermal depth and thus reducing the pyrolysis rate of combustibles.

Numerical Study on the characteristics of fire driven flow for smoke ventilation system operating in the deeply underground subway station (대심도 지하역사에서의 화재시 급 배기 동작유무에 따른 열 연기 거동 분석)

  • Jang, Yong-Jun;Kim, Hag-Beom;Lee, Chang-Hyun;Jung, Woo-Sung
    • Proceedings of the KSR Conference
    • /
    • 2008.11b
    • /
    • pp.66-72
    • /
    • 2008
  • In this study, transient 3D numerical simulations were performed to analyze the characteristics of fire driven flow for smoke ventilation system operating conditions in the deeply underground subway station. The smoke flow patterns were compared and discussed under smoke fan operating mode and off mode in the platform. Soongsil Univ. station(line number 7)was chosen for simulation which was the one of the deepest underground subway stations in the each lines of Seoul. The geometry for model is 365m in length include railway, 23.5m for width, 47m for depth. Therefore 10,000,000 structured grids were used for fire simulation. The parallel computational method for fast calculation was employed to compute the heat and mass transfer eqn's with 6 CPUs(Intel 3.0GHz Dual CPU, 12Cores) of the linux clustering machine. The fire driven flow was simulated with using FDS code in which LES method was applied. The Heat release rate was 10MW and The Ultrafast model was applied for the growing model of the fire source.

  • PDF

A Study on Measures to Improve Smoke Control Performance in Case of Fire in a Clean room as an LCD Manufacturing Process (LCD 제조공정 클린룸의 화재시 CFD를 이용한 제연성능 개선대책에 관한 연구)

  • Son, Bong-Sei;Jang, Chan-Hee
    • Fire Science and Engineering
    • /
    • v.26 no.5
    • /
    • pp.41-47
    • /
    • 2012
  • As a core process in the manufacture of state-of-the-art industrial technologies such as semiconductor and LCD, a clean room is the most important process which can affect the performance and quality of products drastically. Nevertheless, scientific research on comprehensive safety measures from a fire protection standpoint is not being carried out in Korea. This study aims to derive measures to improve smoke control systems by identifying performance and problems of smoke systems installed in clean rooms as an LCD manufacturing process and analyzing fire and evacuation simulations considering several scenarios. As a result of analysis of fires and smoke in a clean roomas an LCD manufacturing process, it is found to be necessary to stop air handling units through interlocking in case of a fire and exhaust smoke out of the room through the top of FAB in consideration of buoyancy of smoke. It is also found to be necessary to install quick response sprinkler heads and accessories to accelerate the response time, because the heat-accumulating performance of sprinkler heads decreases in this application. Despite its low density of dwelling due to the automation process, clean room is characterized by an array of complex production equipment and working environment requiring dustproof clothes, which makes it difficult to acquire evacuation safety performance. Thus, thorough control of danger factors in processes and periodic education and training are required. It is also necessary to establish a level of domestic technologies equivalent to the level of standards of advanced countries in fire protection.