• 제목/요약/키워드: electric shock hazard

검색결과 28건 처리시간 0.019초

지상과 수중에서 전격에 의한 위험성 평가 (Hazard Assessment by Electric Shock both on the Ground and in the Water)

  • 김두현;강동규;이종호
    • 한국안전학회지
    • /
    • 제19권2호
    • /
    • pp.26-33
    • /
    • 2004
  • This study presents a hazard assessment of the human body exposed to electic shock considering various parameters which affect severity of the electric shock. The present study has two research objectives; one is no analyze hazards of the human body by the elctric shock both on the ground and in the water. The other is to understand the mechnism of the electric shock. In order to achieve these objectives the hazard of shock is estimated by comparing with physiological effects of electric curren througn the human body according to variation of shock parameters of shock circuits. The shock parameters adopted in this paper consist of body resistance, resistance of protective equipment, ground resistance, shock duration, depth of gound surface layer, relection factor, permissible touch voltage, body current and body voltage. Besides, safety standard determining hazard degree of the human body is introduced. And hazard of the human body due to the electric shock is quantitatibely assessed in consideration of data obtained by the method suggested herein, and final results are presented and discussed.

그래프법을 이용한 안전기준에 의한 감전위험성 평가 (An Assessment of Electric Shock Hazard by Safety Criteria Using Graphical Method)

  • 김두현;강동규
    • 한국안전학회지
    • /
    • 제16권3호
    • /
    • pp.53-60
    • /
    • 2001
  • This paper presents a graphical method for hazard assessment of electric shock by safety criteria. For the human body to be safety actual body current should not exceed safety criteria, i.e. allowable body current. The assessment method presented in this paper is based m the safety criteria of the IEEE Standard 80 as well as the IEC 479-1. The hazard can be assessed in terms of alterable touch voltages instead of alterable body current. Thus, the hazard assessment of given electric shock condition is referred to a procedure by which the actual touch voltages are compared with the allowable (safe) touch voltages. Since the IEC 479-1 safety criteria are nonlinear, the graphical method is presented for the hazard assessment. Body current and body voltage are calculated with the allowable touch voltage. A comparison of the safety criteria of two widely accepted standards, i.e. the IEEE Std 80 End the IEC 479-1 is proposed. Also Thevenin equivalent resistance is obtained from electric shock model expressed by two-port earth-grid-foot system. On the basis of calculated results, the allowable touch voltage, the body current and the body voltage we can conduct the hazard or safety assessment and estimate the severity of electric shock.

  • PDF

보안등의 감전 위험성에 관한 실태조사 (A Research on the Actual Conditions of the Electric Shock Hazard of a Guard Lamp)

  • 장태준;정연하;노영수;곽희로;최충석
    • 조명전기설비학회논문지
    • /
    • 제19권4호
    • /
    • pp.32-38
    • /
    • 2005
  • 본 논문에서는 보안등의 감전 위험성의 실태를 파악하기 위하여 세 지역에서 보안등을 조사하였다. 취득된 데이터에 의거하여 보안등의 실태를 감전 위험성 측면에서 정밀하게 분석하였다. 조사결과, 많은 보안등은 규정이 미비하여 올바르게 설치되어 있지 않기 때문에 감전의 위험성이 증가되는 것으로 밝혀졌다. 따라서 감전 예방의 관점에서 보안등 시설의 설치 및 관리에 대한 구체적인 규정을 설정하는 것이 필요하다.

가로등설비 누전시 건조상태와 침수상태에 대한 전위분포 분석 (The Analysis on the Electric Potential Distribution of Dry and Submerged Condition by Electric Leakage in Street Lamp)

  • 홍성호;박상태;김상철
    • 한국안전학회지
    • /
    • 제23권6호
    • /
    • pp.44-50
    • /
    • 2008
  • This paper presents study on the electric potential distribution when have a short in street lamp. In order to measure electric potential testing ground is built in. A experiment is conducted to simulate dry and submerged situation of street lamp. The street lamp is leaked by artificial means. And electric potential is measured in grounded street lamp and street lamp alone. The results show that touch voltage of grounded street lamp is possible more high than street lamp alone. And the electric shock hazard is high because high electric potential is distributed near submerged street lamp. Also if street lamp is submerged ground is not useful to decrease electric shock hazard.

수중에서의 감전 메카니즘 특성에 관한 연구 (A Study on the Characteristic of Electric-Shock Mechanism in the Water)

  • 도범성
    • 한국방재학회 논문집
    • /
    • 제7권5호
    • /
    • pp.111-118
    • /
    • 2007
  • 최근에 들어와 가로등에 의한 감전사고가 지속적으로 발생하고 있다. 특히 집중호우로 인해 가로등이 침수될 경우 누전에 의한 감전 사고는 매우 높다. 전기감전사고가 발생할 경우 사고전압을 분석해 보면 주로 220V의 저압시설물에서 발생되고 있으나 이에 대한 위험성을 충분히 인식하지 못하고 있는 실정이다. 가로등 시설물의 사용전압 220V는 주로 일반인이 쉽게 접촉할 수 있는 도로변에 시설되어 있기 때문에 감전사고의 위험성은 매우 높은 편이다. 그러나 가로등 침수로 인해 누전이 발생했을 경우 누전체에서의 거리변화에 따른 수중전위분포가 인체에 미치는 영향을 연구하는 사례는 미약한 실정이다. 본 논문에서는 수중에서 누전이 발생했을 경우에 인체에 미치는 영향과 수중전위분포를 분석하고 수중에서 누전체와의 거리 및 깊이에 따른 변화가 어떻게 인체에 영향을 주는지 실험을 통하여 감전경로와 감전메카니즘을 비교 분석하고자 한다.

건설업에서의 감전재해 감소 방안을 위한 연구 (A Study on the Decreasing Method of Electric Shock Accident in the Construction Industry)

  • 최상원
    • 한국안전학회지
    • /
    • 제29권3호
    • /
    • pp.28-33
    • /
    • 2014
  • Regarding the characteristics of fatal electric shock accident during the past 10 years, fatalities occurred more frequently in July & August, and AM 10-12 PM & 14-16. Also, the electric shock accident is occurred more frequently in the age group from 30 to 40. Especially, the fatal electric shock accident in construction industry covered more than half of total industry. Therefore, it is strongly requested for the protection technology of an electric shock from the low voltage electric path, grounding method and workers. The aim of this study is to propose the policy about the equipment performance standards and/or worker's safety standards to revise the standards for preventing electric shock accidents on safety workings.

최근 감전재해의 발생특성과 재해원인 분석연구 (A Study on the In-depth Analysis of Cause and Characteristic for Recent Electric Shock Accident)

  • 최상원
    • 한국안전학회지
    • /
    • 제29권2호
    • /
    • pp.7-11
    • /
    • 2014
  • The electric shock victims were predominantly male, and more than half of the victims were found in companies with less than five employees in terms of the scale of company, and also more than half of victims had less than one month of experience for work experience. Considering the category of industry, more than half of the victims were engaged in construction, and considering the subcategory of industries, more than 60% of electric shock victims were found in building and other construction works. This study intended to conduct an in-depth analysis on the cause of electric shock accidents to provide basic data for policy proposing taking into considering the characteristics such as the electric shock path, low voltage, grounding and protection of workers. Also this study conducted an in-depth analysis of electric shock accidents for the past eleven years taking into account the necessity of a long-term plan.

가로등설비 누전시 전위분포에 대한 실험연구 (The Experimental Study on the Electric Potential Distribution by Electric Leakage in Street Lamp)

  • 박상태;이복영;홍성호;최충석;길형준;한운기
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2005년도 춘계학술대회논문집
    • /
    • pp.222-227
    • /
    • 2005
  • This paper presents study on the electric potential distribution when have a short in skeet lamp. In order to measure electric potential testing ground is built in. A experiment is conducted to simulate dry and submerged situation of street lamp. The street lamp is leaked by artificial means. And electric potential is measured in grounded street lamp and street lamp alone. The results show that touch voltage of grounded street lamp is possible to more high than street lamp alone. And the electric shock hazard is high because high electric potential is distributed near submerged street lamp. Also if street lamp is submerged ground is not useful to decrease electric shock hazard.

  • PDF

침수된 전기설비의 누전으로 인한 수중에서의 감전특성에 관한 연구 (A Study on the Characteristics of Electric Shock in Water due to the Leakage of Submerged Electric Facility)

  • 김두현;강동규
    • 한국안전학회지
    • /
    • 제17권3호
    • /
    • pp.61-65
    • /
    • 2002
  • A study on the characteristics of electric shock in fresh water due to the leakage of submerged electric facility is conducted by using a reduced scale model at a scale of 1:10 in laboratory. Electric potential as a function of distance from leakage source, type of the leakage source, magnitude of the source voltage, submerged depth and diameter of a copper rod electrode is measured. On the basis of safety standard, separation for guarantee of safety is determined by the measured potential. Also supposing that body resistance is 500[$\Omega$], the human reaction was estimated by calculating body current for some shock duration. Thus, in this paper, the hazard of the electric shock is assessed by introducing representative safety factors, body voltage and body current due to leakage source.

공중욕조에서의 FLUX3D에 의한 전위분포 해석 및 인체의 전격위험성 평가 (Electric Shock Risk Assessment of the Human Body and Potential Distribution Analysis by FLUX3D in a Public Bathtub)

  • 김두현;김성철;이종호;김한상;김종민
    • 한국안전학회지
    • /
    • 제22권2호
    • /
    • pp.41-46
    • /
    • 2007
  • This paper considers the electrical shock risk of the human body due to underwater leakage current in such places of public baths. Many submerged electric facilities in a public bath may create a severe electric shock hazard for the human body, since wet body in an accidentally energized bathtub can result in low electrical resistance through the human body for leakage or fault currents. Therefore a major consideration, in the context of electrical safety underwater, is the shock risk to the bather as a result of electric current flowing through the water in bathtub. To assess the electric shock risk and to analyze the potential distribution in a bathtub, 2 different situation cases are set up, then experimental and simulation methods are adopted. The validity of 2 cases of simulation and experiment data in a bathtub for electric distribution underwater are compared and analyzed. Also electric shock risk assessment underwater in a real public bathtub by simulation program package, Flux 3D, was conducted herein, and the results are presented and discussed.