Browse > Article

A Study on the Characteristics of Electric Shock in Water due to the Leakage of Submerged Electric Facility  

김두현 (충북대학교 안전공학과)
강동규 (충북대학교 안전공학과)
Publication Information
Journal of the Korean Society of Safety / v.17, no.3, 2002 , pp. 61-65 More about this Journal
Abstract
A study on the characteristics of electric shock in fresh water due to the leakage of submerged electric facility is conducted by using a reduced scale model at a scale of 1:10 in laboratory. Electric potential as a function of distance from leakage source, type of the leakage source, magnitude of the source voltage, submerged depth and diameter of a copper rod electrode is measured. On the basis of safety standard, separation for guarantee of safety is determined by the measured potential. Also supposing that body resistance is 500[$\Omega$], the human reaction was estimated by calculating body current for some shock duration. Thus, in this paper, the hazard of the electric shock is assessed by introducing representative safety factors, body voltage and body current due to leakage source.
Keywords
electric shock; leakage, separation; body voltage; body current;
Citations & Related Records
연도 인용수 순위
  • Reference
1 Baldev Thapar, Victor Gerez, and Vijay Singh, 'EfFective Ground Resistance of the Human Feet in High Voltage Switchyards,' IEEE Trans. on Power Deliveiy, Vol. 8, No. 1, Jan. 1993
2 김두현, 강동규, 김상철, '저전압에서 통전전류를 이용한 인체의 동저항 측정 및 예측,' 산업안전학회지, Vol. 16, No. 1, pp. 37-42, 2001
3 김두현, 강동규, '그래프법을 이용한 안전기준에 의한 감전위험성 평가,' 산업안전학회지, Vol. 16, No. 3, pp. 53-60, 2001
4 L. E. Virr, BSc, PhD, CEng FIEE, 'Increased electric shock risk underwater due to electrode con -figuration and insulating boundaries,' IEE Pro-ceedings, Vol. 5, No. 5, 1990
5 人間工學 handbook 編輯委員會編, 人間 工學handbook, 金原出版株式會社, 1966
6 勞渤省 産業安全硏究所, 産業安全硏究新 安全資料, 1970
7 Kim, Doo-Hyun . Kang, Dong-Kyu Kim, Sang-Ryull Park, Yang-Birm, 'Estimation of Permissible Body Voltage and Body Current Considering Re-duction Factor for Ground Resistance of the Feet,' Journal of the KllS, Vol. 16, No. 5, 2001
8 한국전기안전공사 부설 전기안전시험연구원, 배선기구류의 감전위험성 연구, 한국전기안전공사, 1999
9 김두현외, 전기안전공학, 동화기술, 1995
10 ANSI/IEEE Std 1048, IEEE Guide for Protective Grounding of Power Lines, 1990