• 제목/요약/키워드: Winding insulation

검색결과 254건 처리시간 0.032초

발전기 고정자 권선의 부분방전 특성을 이용한 절연진단 연구 (A Study on Insulation Diagnosis by Partial Discharge Spectroscopy of Generator Stator Winding)

  • 강동식;김용주;김길용
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1993년도 하계학술대회 논문집 B
    • /
    • pp.584-587
    • /
    • 1993
  • Mica, which have a good thermal and electrical characteristics, while will cleave easily at these layers. In order to bond mica materials soldily, mica/epoxy composite insulation materials were developed for generator stator winding. There are lots of problems such as delamination and partial discharge of these insulation materials caused by mechanical, electrical and thermal aging. Several experiments have been conducted in order to find the useful diagnostic parameters from the partial discharge phenomena by applying a new measurement techniques. this paper deals with the partial discharge pulse characteristics, which may be a useful diagnostic concept in predicting insulation condition of generator stator insulation materials. Long term insulation aging test shows that partial discharge phase angle an magnitude are identified as one of the main key techniques for insulation diagnosis on generator stator winding.

  • PDF

고압전동기 고정자권선의 부분방전 특징추출 (Feature Extraction of Partial Discharge for Stator Winding of High Voltage Motor)

  • 박재준;김희동;이동윤
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 추계학술대회 논문집 전기물성,응용부문
    • /
    • pp.112-116
    • /
    • 2004
  • On-line monitoring of fault discharge is an important approach for indicating the condition of electrical insulation of stator winding in high voltage motor. In this paper, several key aspects of on-line monitoring system are discussed, involving the characteristics of fault discharge of stator winding in high voltage motor, spectrum analysis of four simulation fault signals, feature extraction of internal fault discharge from apply voltage to breakdown. The study of the partial discharge activities allows to highlight the ageing stage in the winding fault under test. During the life of the winding insulation fault, the shape of PD signal change relating to the ageing stage. The ageing of stator winding insulation fault of high voltage motor is investigated based on the characteristics of partial discharge pulse distribution and statistical parameters, such as maximum, skewness and kurtosis using discrete wavelet transform coefficients.

  • PDF

고압전동기 고정자권선의 건조상태에 따른 절연특성 변화사례 고찰 (Example study of the insulation characteristic change according to the dryness condition in high voltage motor stator winding)

  • 공태식
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2008년도 제39회 하계학술대회
    • /
    • pp.2056-2057
    • /
    • 2008
  • This paper is purpose to understand the insulation properties of the high voltage motor stator winding according to the different dryness conditions. we carried out the three times insulation diagnosis test for the same motor stator winding. the first test object is the contaminated winding, second is the washed-out, and natural dried during the 24 hours, and the last is the heating dried in 110$^{\circ}C$ during the 48 hours. the insulation diagnosis tests are consist of the megger, the polarization index, the AC current test, the dissipation factor test and the partial discharge test, we analyzed and made a comparison of the three cases test result.

  • PDF

발전기 고정자 권선 절연재 흡습 특성에 관한 실험적 연구 (An Experimental Study of Water Absorption Characteristics for Generator Stator Winding Insulation)

  • 배용채;이대성;김희수;김연환;이현
    • 대한기계학회:학술대회논문집
    • /
    • 대한기계학회 2004년도 춘계학술대회
    • /
    • pp.426-431
    • /
    • 2004
  • Leaking water coolant into stator electrical insulation is a growing concern for the aging water-cooled generator since leaks in the generator water-cooled stator winding can affect machine availability and insulation life. But a domestic techniques of such field are insufficient and depend wholly on GE or TOSHIBA technique. Therefore this paper introduces measuring principle and developed measuring system, which has been used to detecting wet absorption. We accomplished the experiment with a stator promotion of virtue which is used in actual power plant. Also, Experimental method of generator stator winding, which is investigated into wet absorption test.

  • PDF

고압유도전동기 절연특성시험의 신뢰도 평가 (Evaluation of Insulation Diagnostic Test Reliability for Stator Winding of High Voltage Induction Motor)

  • 이광호;김현일;곽희진;오봉근
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 하계학술대회 논문집 C
    • /
    • pp.1838-1841
    • /
    • 2004
  • This test was performed to assess the correlation between insulation diagnostic tests and breakdown voltage strength of the stator winding of 6.6kV class induction motor in insulation deterioration condition which have been in service for 5 years after being installed in 1998. The insulation diagnostic tests include resistance, polarization index(P.I), dissipation factor(${\triangle}tan{\delta}$), maximum partial discharges(Qmax) and AC breakdown test. we evaluated the correlation between insulation diagnostic test and AC breakdown test for stator winding of high voltage induction motor.

  • PDF

고압유도전동기 절연특성시험의 신뢰도 평가 (Evaluation of Insulation Diagnostic Test Reliability for Stator Winding of High Voltage Induction Motor)

  • 이광호;김현일;곽희진;오봉근
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 추계학술대회 논문집 전기설비전문위원
    • /
    • pp.46-49
    • /
    • 2004
  • This test was performed to assess the correlation between insulation diagnostic tests and breakdown voltage strength of the stator winding of 6.6kV class induction motor in insulation deterioration condition which have been in service for 5 years after being installed in 1998. The insulation diagnostic tests include resistance, polarization index(P.I), dissipation factor(${\Delta}tan{\delta}$). maximum partial discharges(Qmax) and AC breakdown test. we evaluated the correlation between insulation diagnostic test and AC breakdown test for stator winding of high voltage induction motor.

  • PDF

수력 발전기 권선에서의 운전중 부분방전 측정기법 (On-line partial discharge measurement techniques of hydro-generator windings)

  • 황동하;김진봉;김용주;박명수;김택수
    • 대한전기학회논문지
    • /
    • 제45권2호
    • /
    • pp.294-300
    • /
    • 1996
  • In hydro-generator, a groundwall insulation of stator windings gradually deteriorates due to mechanical, thermal, electrical and environmental stresses. These stresses combine to result in loose windings, delamination of the stator insulation and/or electrical tracking of the endwinding, all of which can lead to stator insulation failures. Conventionally, off-line tests such as partial discharge measurement, DC/AC current and .DELTA.tan.delta. tests has been used for estimation of winding condition. However, off-line test requires large power supply and generator outage. In addition, major cause of insulation problems such as loose wedges and slot dischages may not be found with off-line diagnoses. This paper introduces the on-line partial discharge measurement techniques using frequency spectrum analyzer(FSA) for the generator stator windings. The experimental results from the UIAM #1 hydro-generator confirms a optimistic application of on-line generator diagnosis method as a reliable tool for evaluation of winding condition.

  • PDF

수력발전기의 절연보강 전${\cdot}$후 절연상태 비교평가 (Assessment of Insulation Condition between Diagnosis and Impregnation for Hydro-Generator)

  • 변일환;이은웅
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 하계학술대회 논문집 B
    • /
    • pp.1124-1126
    • /
    • 2004
  • The measurements were performed to assess the insulation deterioration condition of the stator winding of Dae-Cheong hydro-generator ${\sharp}2$ which had been in service after being constructed 1980. After repair of the stator winding insulation. we conducted insulation diagnostic tests which include resistance, polarization index(P. I). AC current, dissipation factor($Tan{\delta}$) and partial discharges ($Q_{max}$). The results of diagnostic tests were compared to the previous records. On the basis of these test results. this paper tried to present the importance of insulation repair for the generator stator winding.

  • PDF

수력발전기 고정자권선의 절연열화 분석 (A study on the Analysis of Insulation Aging for Generator stator windings)

  • 변두균;오봉근;강동식;임기조
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2005년도 제36회 하계학술대회 논문집 C
    • /
    • pp.2072-2074
    • /
    • 2005
  • This test was performed to assess the insulation condition of the stator winding of 3.45kV hydro generator in insulation deterioration condition which was due to long service period(30years) since installed We extracted 12 stator wingdings from the hydro generator core, cut the stator windings into three parts(Middle winding part, slot winding part, end wingding part), and evaluated the insulation condition to know the deterioration condition of each parts. This insulation diagnostic tests include AC current, dissipation factor, and partial discharg test.

  • PDF

대용량 수차발전기의 절연진단과 절연보수 상관관계 평가 (Assessment of Insulation Condition between Diagnosis and Impregnation for Hydro-Generator)

  • 오봉근;정진달;이광호;김현일;곽희진
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 춘계학술대회 논문집 전기설비전문위원
    • /
    • pp.39-41
    • /
    • 2004
  • The measurements were performed to assess the insulation deterioration condition of the stator winding of Dae-Cheong hydro-generator #2 which had been in service after being constructed 1980. After repair of the stator winding insulation, we conducted insulation diagnostic tests which include resistance, polarization index(P.I), AC current, dissipation factor($Tan\delta$) and partial discharges ($Q_{max}$). The results of diagnostic tests were compared to the previous records. On the basis of these test results, this paper tried to present the importance of insulation repair for the generator stator winding.

  • PDF