• 제목/요약/키워드: Total leakage current

검색결과 98건 처리시간 0.022초

누설전류의 파고분포 분석에 의한 새로운 피뢰기 진단기술 및 장치 (New Diagnostic Technique and Device for Lightning Arresters by Analyzing the Wave Height Distribution of Leakage Currents)

  • 길경석;한주섭;송재영;조한구;한문섭
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제52권12호
    • /
    • pp.562-567
    • /
    • 2003
  • Lightning arresters are deteriorated by repetition of protective operation against overvoltages or impulse currents in environments of its use. If a deteriorated arrester is left in power lines, it can lead to an accident such as a line to ground fault even in a normal system. Therefore, it is necessary to eliminate the deteriorated arrester in advance by checking the soundness of arresters on a regular basis, and to ensure the reliability of power systems by preventing accidents. Various deterioration diagnostic techniques and devices are suggested, and most of which measure leakage current components as an indicator of arrester ageing. However, the techniques based on the magnitude of leakage current measure simply RMS or peak value of leakage current components and do not provide detailed information needed in the diagnosis. In this study, we found that the wave height distributions of the total leakage currents are remarkably changed or a new wave height are produced with the progress of arrester deterioration. To propose a new technique for the diagnosis, we designed a leakage current detection unit and an analysis program which can measure leakage current magnitudes and analyze wave height distributions. From the experimental results, we confirmed that the proposed technique by analyzing the wave height distribution can simply diagnose the mode of defects such as a partial damage and an existence of punctures in arresters as well as deterioration of arresters.

뇌충격전류에 의한 산화아연형 피뢰기 소자의 전기적 특성변화 (Change of Electrical Characteristics of ZnO Arrester Blocks by Lightning Impulse Current)

  • 길경석;한주섭;박영호
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제48권7호
    • /
    • pp.550-555
    • /
    • 1999
  • This paper deals with the effect of lightning impulse current on electrical characteristics of ZnO blocks used in distribution lightning arrester. The electrical characteristics of ZnO blocks are degraded by overtime impulse current, and the degraded ZnO block is brought to a thermal runaway and finally destroyed. It is therefore important to estimate the change of electrical characteristics of ZnO blocks. In this study, an impulse current generator which can produce 8/20$[\mus]$, 3[㎄] and 4/10$[\mus]$, 5[㎄] waveform is designed and fabricated to simulate the lightning impulse current of power systems. Total energy applied to the ZnO blocks at each time is 739[J] in 8/20$[\mus]$, and 523[J] in 4/10$[\mus]$, impulse current, respectively. From the experimental results, the 3rd harmonic of the leakage current increases continuously with the number of applied impulse current, but no significant changes in residual voltage and in reference voltage are observed until the ZnO block is destroyed. Also, it is confirmed that the main factor on degradation of ZnO blocks is rather the total energy applied to ZnO blocks than the peak value of the impulse current.

  • PDF

GIS용 피뢰설비의 전문가 시스템 설계에 관한 연구 (A Study on the Design of an Expert System for Diagnosing GIS Arrester)

  • 한주섭;김일권;길경석;류길수;김태진;김정배
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2005년도 추계학술대회 논문집 Vol.18
    • /
    • pp.319-320
    • /
    • 2005
  • This paper describes the principles and structures of an expert system for arrester diagnosis. The expert system analyzes and decides the arrester condition by total leakage current, its harmonic component, and temperature because the deterioration of arresters appeared in an increase of leakage current and surface temperature of it. Additionally, influence of system voltage harmonics and ambient temperatures on leakage current changes were considered in the design. The expert system is consisted of a data acquisition module and a computer for monitoring. The acquired analog data are digitalized and transmitted to the computer by an optical link which is free from interference.

  • PDF

경년에 따른 배전용 피뢰기의 열화특성 (Characteristics analysis of field aged distribution surge arresters)

  • 조성수;김주용;김찬영;송일근;박중신
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 E
    • /
    • pp.2323-2325
    • /
    • 1999
  • This paper presents characteristics of the aged and new 18kV surge arresters. In order to investigate aging characteristics, we measured total leakage current and resistive leakage current using specially made leakage current measurement system and also investigated $tan{\delta}$ of the arresters and microstructure of the elements. Through the investigation we found that all of the arresters does not aged for 2 years field operation.

  • PDF

누설전류의 제3고조파 분석에 의한 ZnO소자의 열화진단기술 (A Technique of Deterioration Diagnosis for ZnO Element by Analyzing the 3rd order Harmonics- of Leakage Current)

  • 이복희;강성만
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1998년도 하계학술대회 논문집 E
    • /
    • pp.1740-1742
    • /
    • 1998
  • This paper describes the technique of deterioration diagnosis for ZnO element. Due to the non-linear resistance of ZnO block, the total leakage current contains harmonics when arrester deteriorated. The most significant harmonics is the 3rd order component. So, it can be used as an indicator of the arrester condition. An iron core, which has a very high relative permeability, is used for increasing detection sensitivity and the 3th order harmonics of leakage current was detected by band-pass circuit. And we have verified the reliability and performance of the sensing device through several laboratory tests.

  • PDF

산화아연형 피뢰기 소자의 뇌충격전류에 의한 특성 변화 (Change of the Characteristics of ZnO Arrester Blocks by Lightning Impulse Current)

  • 한주섭;송재용;길경석
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1998년도 추계학술대회 논문집 학회본부 C
    • /
    • pp.907-909
    • /
    • 1998
  • This paper describes the effect of impulse current on degradation of ZnO blocks. In this study, an impulse current generator which can produce 8/20 [${\mu}s$], 3 [kA] and 4/10 [${\mu}s$], 5 [kA] waveform is designed and fabricated to simulate the lightning impulse current. The residual voltage, reference voltage, and leakage current flowing to the ZnO blocks are observed. The experimental results show that the leakage current increases continuously with the number of applied impulse current, but no significant changes in residual voltage and in operating voltage are observed until the ZnO block is destroyed. Also, it is confirmed that the main factor on degradation of ZnO blocks is rather the total energy applied to ZnO blocks than the peak value of the impulse current.

  • PDF

직류+60[Hz] 교류 중첩전압에 대한 ZnO 피뢰기 소자의 전기적 특성 (Electrical Characteristics of ZnO Surge Arrester Elements Subjected to the Mixed DC and 60[Hz] AC Voltages)

  • 이복희;양순만
    • 조명전기설비학회논문지
    • /
    • 제26권4호
    • /
    • pp.41-47
    • /
    • 2012
  • This paper deals with the electrical characteristics related to power loss, equivalent resistance, and leakage currents flowing through new and deteriorated zinc oxide(ZnO) arrester elements subjected to the mixed DC and 60[Hz] AC voltages. The test specimens were deteriorated by 8/20[${\mu}s$] impulse current of 2.5[kA]. The leakage current-applied voltage($I-V$) characteristic curves of ZnO surge arrester elements were measured as a parameter of the ratio of the peak of 60[Hz] AC voltage to the peak of total voltage. As a consequence of test results, in case of the same applied voltage, the leakage currents flowing through the deteriorated ZnO arrester elements were higher than those flowing through the new ZnO surge arrester elements. The cross-over phenomenon in $I-V$ curves of ZnO surge arrester elements measured as a parameter of the mixed ratio of DC and AC voltages was observed at the low current domain. The effect of DC voltage on the leakage current flowing through ZnO surge arrester elements is pronounced at the same magnitude of test voltages. In addition, the larger the applied number of 8/20[${\mu}s$] impulse current of 2.5[kA] is, the greater the power loss is, in particular, the more severe the power loss increases at higher applied voltages.

수배전계통의 여러 가지 고장조건에서 피뢰기에 흐르는 누설전류 (Leakage Currents Flowing through Lightning Surge Arresters under Various Fault Conditions in Receiving and Distribution Power Systems)

  • 이복희;길형준;강성만;최휘성
    • 조명전기설비학회논문지
    • /
    • 제18권5호
    • /
    • pp.132-139
    • /
    • 2004
  • 수배전계통의 고장에는 1선 지락, 선간 단락, 2선 지락 등의 고장이 있다. 가공 배전 계통에서 일어나는 대부분의 고장은 1선 지락이며, 피뢰기는 이러한 고장에 의한 빈번한 과전압에 의해 스트레스를 받는다. 본 논문에서는 수배전계통에서 일어날 수 있는 고장을 모의하여 여러 가지 고장에 의해 피뢰기에 흐르는 누설전류의 특성에 대하여 조사하였다. 결과적으로, $\pm$10[%] 범위의 전압변동률에 의해서 피뢰기에 흐르는 누설전류는 거의 변화가 없었다. 성능이 우수한 접지 시스템 하에서는 전압변동률은 피뢰기의 긴 시간동안의 동작에 별 영향을 줄 수가 없었다. 하지만, 1선 지락 고장에서 피뢰기에 흐르는 누설전류의 최대값은 비효과적인 접지 시스템의 운전 전압에서의 누설전류와 비교하였을 때 140배 이상이 되었다. 그러나 선간 단락과 2선 지락 고장의 경우에는 피뢰기의 누설전류에 거의 영향을 미치지 못했다.

철도용 피뢰기의 열화진전에 관한 연구 (A Study on the Deterioration Progress of Railway Arresters)

  • 길경석;한주섭;한문섭
    • 한국철도학회:학술대회논문집
    • /
    • 한국철도학회 2004년도 춘계학술대회 논문집
    • /
    • pp.1393-1395
    • /
    • 2004
  • Arresters are the best protective device on electrical power systems against transient overvoltages generated by lightning and/or switching operation. Nonetheless, arresters will be deteriorated due to absorption of moisture in the environments of its use, repetition in the protective operation to overvoltages, and some defects at manufacturing. It is therefore important to estimate the electrical characteristic changes of ZnO blocks. In this paper, an accelerated deterioration test by a standard lightning impulse current was carried out to extract parameters needed for diagnosing arrester deterioration, and leakage current components were measured. Total energy applied to the ZnO blocks at each time is 1,050[J] in 8/20[${\mu}s$] impulse current. From the experimental results, we proposed electrical parameters and leakage current level to diagnose arrester soundness.

  • PDF

서지 보호기의 열화 특성과 온라인 진단장치 (Deterioration Characteristics and an On-Line Diagnostic Equipment for Surge Protective Devices)

  • 박경수;왕국명;황성철;김선재;길경석
    • 한국전기전자재료학회논문지
    • /
    • 제29권10호
    • /
    • pp.635-640
    • /
    • 2016
  • This paper dealt with the deterioration characteristics and an on-line diagnosis equipment for SPDs (surge protective devices). An accelerated aging test was carried out using a $8/20{\mu}s$ standard lightning impulse current to analyze the changes of electrical characteristics and to propose the diagnostic parameters and the criterion for deterioration of ZnO varistor which is the core component of SPDs. Based on the experimental results, an on-line diagnosis equipment for SPD was fabricated, which can measure the total leakage current, reference and clamping voltage. The leakage current measurement circuit was designed using a low-noise amplifier and a clamp type ZCT. A linear controller, the leakage current measurement part and a HVDC were used in the measurement of reference voltage. The measurement circuit of clamping voltage consisted of a surge generator and a coupling circuit. In a calibration process, measurement error of the prototype equipment was less than 3%.