Change of Electrical Characteristics of ZnO Arrester Blocks by Lightning Impulse Current

뇌충격전류에 의한 산화아연형 피뢰기 소자의 전기적 특성변화

  • 길경석 (한국해양대 공대 전기공학과) ;
  • 한주섭 (한국해양대 공대 전기공학과) ;
  • 박영호 (한국해양대 공대 전기공학과)
  • Published : 1999.07.01

Abstract

This paper deals with the effect of lightning impulse current on electrical characteristics of ZnO blocks used in distribution lightning arrester. The electrical characteristics of ZnO blocks are degraded by overtime impulse current, and the degraded ZnO block is brought to a thermal runaway and finally destroyed. It is therefore important to estimate the change of electrical characteristics of ZnO blocks. In this study, an impulse current generator which can produce 8/20$[\mus]$, 3[㎄] and 4/10$[\mus]$, 5[㎄] waveform is designed and fabricated to simulate the lightning impulse current of power systems. Total energy applied to the ZnO blocks at each time is 739[J] in 8/20$[\mus]$, and 523[J] in 4/10$[\mus]$, impulse current, respectively. From the experimental results, the 3rd harmonic of the leakage current increases continuously with the number of applied impulse current, but no significant changes in residual voltage and in reference voltage are observed until the ZnO block is destroyed. Also, it is confirmed that the main factor on degradation of ZnO blocks is rather the total energy applied to ZnO blocks than the peak value of the impulse current.

Keywords

References

  1. IEEE Trans. on Power Delivery v.4 no.1 Applying metal-oxide surge arresters on distribution systems S. S. Kershaw;G. L. Gaibrois;K. B. Stump
  2. IEEE Trans. on Power Delivery v.10 no.2 An improved non-inductive impulse voltage measurement technique for ZnO surge arresters A. Haddad(et al)
  3. IEEE Trans. on Power Delivery v.3 no.3 Maintenance of surge arrester by portable arrester leakage current detector S. Shirakawa(et al)
  4. '98 대한전기학회 추계학술대회 논문집 v.C 뇌충격전류에 의한 산화아연형피뢰기 소자의 전기적 특성변화 길경석;한주섭;송재용
  5. IEEE Trans. on Power Delivery v.5 no.4 New method for measurement of the resistive leakage currents of metal-oxide surge arrester in service J. Lundquist(et al)
  6. 日本電氣學會電力 · エネルギ一部門大會 酸化亞鉛形避雷器の漏れ電流檢出方式の提案 岡藤伸夫(外 3人)
  7. IEEE Trans. on Power Delivery v.7 no.3 Methods for analyzing the performance on gapless metal oxide surge arresters O. Nigol
  8. ANSI/IEEE C62.11-1987 IEEE Standard for Metal-Oxide Surge Arresters for AC Power Circuits The Institute of Electrical and Electronics Engineers Inc.
  9. Technical Committee No. 37 Surge Arresters, Metal Oxide Surge Arresters Without Gaps for AC System International Electrotechnical Commission
  10. IEEE Trans. on Power Delivery v.8 no.1 Comparison of different test methods to assess the thermal stresses of metal oxide surge arresters under pollution conditions A. Bargigia(et al)
  11. Operational Amplifiers and Linear Integrated Circuits Robert F. Coughlin(et al)
  12. IEEE Trans. on Power System v.PWRD-1 no.2 A procedure for estimating the lifetime of metal oxide surge arresters for AC application W. G. Carlson(et al)