Analysis of Insulation Quality in Large Generator Stator Windings

  • Kim, Hee-Dong;Kong, Tae-Sik;Ju, Young-Ho;Kim, Byong-Han
    • Journal of Electrical Engineering and Technology
    • /
    • v.6 no.3
    • /
    • pp.384-390
    • /
    • 2011
  • To evaluate the condition of stator winding insulation in generators that have been operated for a long period of time, diagnostic tests were performed on the stator bars of a 500 MW, 22 kV generator under accelerated thermal and electrical aging procedures. The tests included measurements of AC current (${\Delta}I$), dissipation factor ($tan{\delta}$), partial discharge (PD) magnitude, and capacitance (C). In addition, the AC current test was performed on the stator winding of a 350 MW, 24 kV generator under operation to confirm insulation deterioration. The values of ${\Delta}I$, ${\Delta}tan{\delta}$, and PD magnitude in one stator bar indicated serious insulation deterioration. In another stator bar, the ${\Delta}I$ measurements showed that the insulation was in good condition, whereas the values of ${\Delta}tan{\delta}$ and PD magnitude indicated an incipient stage of insulation deterioration. Measurements of ${\Delta}I$ and PD magnitude in all three phases (A, B, C) of the remaining generator stator windings showed that they were in good condition, although the ${\Delta}tan{\delta}$ measurements suggested that the condition of the insulation should be monitored carefully. Overall analysis of the results suggested that the generator stator windings were in good condition. The patterns of PD magnitude in all three phases (A, B, C) were attributed to internal discharge.

Analysis of Insulation Condition in High Voltage Motor Stator Windings Following Cleaning and Insulation Reinforcement (세척과 절연보강에 따른 고압전동기 고정자 권선의 절연상태 분석)

  • Kim, Hee-Dong
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.25 no.6
    • /
    • pp.474-480
    • /
    • 2012
  • Diagnostic tests were performed on two high voltage(HV) motor stator windings. These tests included the measurement of insulation resistance, polarization index, AC current, dissipation factor($tan{\delta}$) and partial discharge(PD) magnitude. Surface contamination of HV motor stator windings has an effect on the AC current and $tan{\delta}$. When the stator windings were finished cleaning and insulation reinforcement, the increase rate of AC current(${\Delta}I$) and dissipation factor(${\Delta}tan{\delta}$) were very small compared to those before cleaning. However, the PD magnitude remained the same. These tests show that cleaning and insulation reinforcement of HV motor stator windings can reduce the insulation failure.

Characteristics of Insulation Diagnostic in Traction Motor Stator Windings (견인전동기 고정자 권선의 절연진단 특성)

  • Kim, Hee-Dong;Kim, Chung-Hyo;Park, Young;Park, Hyun-June
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2006.11a
    • /
    • pp.336-338
    • /
    • 2006
  • Diagnostic tests are used to evaluate the insulation condition of stator windings in traction motor. These tests included ac current, tan delta and maximum partial discharge. The insulation condition of stator windings was assessed by three test items. The stator windings of traction motor were m good condition. After completing the diagnostic tests, the stator windings of traction motors were subjected to gradually increasing ac voltage, until the insulation punctured. No.5 stator windings failed near rated voltage of 18.9 kV. The breakdown voltage of No.1 stator windings was 13.0. The failure was located m a line-end coil at the exit from the core slot.

  • PDF

Evaluation of Insulation Performance for Stator Winding of the Inverter Driven Induction Motor According to Impregnation Methods (함침기법에 따른 인버터 구동 유도전동기 고정자 권선의 절연성능 평가)

  • Hwang, Don-Ha;Kang, Dong-Sik;Lee, In-Woo;Kim, Dong-Hee;Lee, Kwang-Sik
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2006.05a
    • /
    • pp.487-492
    • /
    • 2006
  • Inverter driven induction motors with high speed switching and advanced PWM techniques are widely used for variable speed applications. Recently, the insulation failures of stator winding have attracted much concern due to high dv/dt of IGBT PWM inverter output. In this paper, the detailed insulation test results of 26 low-voltage induction motors are presented. Six different types of insulation techniques are applied to 26 motors. The insulation characteristics are analyzed with partial discharge, inception voltage, AC current, and dissipation factor tests. Also, breakdown tests by high voltage pulses are performed. From the above test data the effects due to different wires and insulation techniques on the insulation characteristics of low-voltage induction motors are compared and analyzed. The insulation technique to enhance the insulation strength is suggested from the test results.

  • PDF

A Study on the New Criteria for Assessing the Insulation Deterioration of Generator Stator Winding (발전기 고정자 권선의 새로운 절연열화 판정기준 설정에 관한 연구)

  • Hwang, D.H.;Kim, Y.J.;Kim, J.B.;Jeon, J.W.;Kim, H.G.;Park, J.J.
    • Proceedings of the KIEE Conference
    • /
    • 1997.07e
    • /
    • pp.1692-1695
    • /
    • 1997
  • This paper describes the relationship between the various non-destructive parameters and the breakdown voltage for the 17 kV, 300 MVA and the 22 kV, 500 MVA generators stator bars with polyester and epoxy/mica insulation respectively. Also, this study reports the results of an investigation into the factors which can assess the insulation condition of generator stator winding. Furthermore, a new parameter, Partial Discharge Index(PDI), is introduced as the valuable parameter for the assessment of insulation condition. The ratio between partial discharge increment and the stepwise voltage increment from the Discharge Inception Voltage (DIV) at the characteristic or resonant frequency band shows the close relationship between the breakdown voltage and PDI.

  • PDF

Insulation Properties of Unaged Stator Winding Bars for Turbine Generators (터빈 발전기용 비열화 고정자 권선 바의 절연 특성)

  • Kim, Tae-Hee;Kang, Myung-Guk;Lee, Jai-Kwun
    • Proceedings of the KIEE Conference
    • /
    • 2005.07c
    • /
    • pp.2097-2099
    • /
    • 2005
  • Class-F and class-B insulating materials based on the resin rich type mica-epoxy composites for the stator windings in large turbine generators have been developed by DHIC. In recent, stator winding bars applied with prototype insulation tapes and commercially available resin rich groundwall tapes were produced through the same manufacturing processes as the real bars. Comparative tests to obtain the insulation properties of both bars were carried out such as IR/PI. dissipation factor and partial discharge at room temperature. In this paper, the manufacturing processes and the insulation properties of the bars which were not aged are presented.

  • PDF

A study on insulation characteristics with AC Breakdown Test for Stator Winding of 3.3kV class Induction Motor (절연파괴시험을 통한 3.3kV 유도전동기의 절연특성 연구)

  • Lee, Dong-Geun;Lee, Kwang-Ho;Choi, Kyo-Nam;Kim, Hyun-Il;Kwak, Hee-Jin;Oh, Bong-Keun
    • Proceedings of the KIEE Conference
    • /
    • 2005.07c
    • /
    • pp.2118-2122
    • /
    • 2005
  • This test was performed to assess the corelation of insulation deterioration condition with breakdown voltage of the stator winding of 3.3kV class induction motors which have been in service for 10 years after being installed in 1993. The insulation diagnostic tests include resistance, polarization index(P.I), dissipation factor$({\Delta}tan{\delta})$, maximum partial discharges (Qmax) and AC breakdown test. we evaluated the corelation of insulation diagnostic test with AC breakdown test for stator wilding of high voltage induction motor.

  • PDF

Properties of Electrical Performance on Stator Coil of Traction Motor by Accelerated lest using Transient Surge (과도서지를 이용한 가속열화 시험법에 따른 견인전동기 고정자 코일의 전기적 특성 변화)

  • 박현준;장동욱;이길헌;최종선;김저우
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.16 no.9
    • /
    • pp.783-789
    • /
    • 2003
  • The winding problems of traction motor are the major determinant of motor's life. The root cause of winding failure is gradual deterioration of the insulation due to thermal, electrical, mechanical and environmental stresses. The aging of the insulation reduces the electrical and mechanical strength of the insulation. At same point, a voltage surge or mechanical shock from a traction motor start will fracture or break down the insulation. To achieve the expected life usually requires extensive laboratory evaluation of the insulation systems and the use of accelerated aging tests. There are several nondestructive test available for checking, the condition of motor insulation, the probable extent of aging, and the rate of which aging is taking place. So the insulation characteristics of stator coil were each analyzed by measurement of dielectric loss(tan$\sigma$), capacitance and partial discharge. The method of diagnosis is able to analyze the insulation condition and evaluate the life of the traction motor.

Analysis of Insulation Characteristics for Stator Winding after Insulation Reinforcement (수력발전기 고정자권선의 절연보강 후 절연특성 분석)

  • Oh, Bong-Keun;Choi, Kyo-Nam;Choi, Hyung-Cheol;Lim, Kee-Joe
    • Proceedings of the KIEE Conference
    • /
    • 2006.05a
    • /
    • pp.71-73
    • /
    • 2006
  • Our company(KOWACO) has periodically performed off-line diagnostic test for 14 hydro generators (rated 11 kV over) for 15 years. In this paper, we summarized results of dissipation factor tip-up test and partial discharge test about these generators. Among these, we chose two generators and performed insulation reinforcement (cleaning and varnish Painting). We compared change of insulation condition for the stator winding based upon off-line diagnostic test result before and after repair. Test result shows that insulation condition was improved after insulation reinforcement. This insulation reinforcement has a function to reduce cause of deterioration, so we can know that it extends lifetime of generator and it is a very important factor for stable operation of facilities.

  • PDF

A Study on the Insulation Characteristics for Stator Windings of IGBT PWM Inverter-Fed Induction Motors

  • Hwang, Don-Ha;Kang, Dong-Sik;Kim, Yong-Joo;Lim, Tae-Hoon;Bae Sung-Woo;Kim Dong-Hee;Ro Chae-Gyun
    • Journal of Power Electronics
    • /
    • v.3 no.3
    • /
    • pp.159-166
    • /
    • 2003
  • The winding insulation of low-voltage induction motors in adjustable-speed drive system with voltage-fed Inverters is substantially stressed due to the uneven voltage distribution and excessive voltage stress (dv/dt), which result in the premature insulation breakdown In this paper, the detailed insulation test results of 26 low-voltage induction motors are presented. Six different types of insulation techniques are applied to 26 motors. The insulation characteristics are analyzed with partial discharge, discharge inception voltage, AC current, and dissipation factor tests Also, insulation breakdown tests by high voltage pulses are performed, and the corresponding breakdown voltages obtained.