• 제목/요약/키워드: Static series compensator

검색결과 56건 처리시간 0.026초

Enhancement of Interface Flow Limit using Static Synchronous Series Compensators

  • Kim Seul-Ki;Song Hwa-Chang;Lee Byoung-Jun;Kwon Sae-Hyuk
    • Journal of Electrical Engineering and Technology
    • /
    • 제1권3호
    • /
    • pp.313-319
    • /
    • 2006
  • This paper addresses improving the voltage stability limit of interface flow between two different regions in an electric power system using the Static Synchronous Series Compensator (SSSC). The paper presents a power flow analysis model of a SSSC, which is obtained from the injection model of a series voltage source inverter by adding the condition that the SSSC injection voltage is in quadrature with the current of the SSSC-installed transmission line. This model is implemented into the modified continuation power flow (MCPF) to investigate the effect of SSSCs on the interface flow. A methodology for determining the interface flow margin is simply briefed. As a case study, a 771-bus actual system is used to verify that SSSCs enhance the voltage stability limit of interface flow.

전력조류계산을 위한 SSSC모델의 개발과 연속조류계산 알고리듬에의 적용 (Development of SSSC Power Flow Model and its Implementation into Continuation Power Flow Algorithm)

  • 김슬기;송화창;이병준
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 C
    • /
    • pp.1158-1160
    • /
    • 1999
  • This paper proposes a SSSC(Static Synchronous Series Compensator) power flow model to be incorporated into power flow calculation for the steady state analysis of the power system. SSSC provides controllable compensating voltage, which is in quadrature with the line current, over an capacitive and an inductive range, independently of the magnitude of the line current. This SSSC model is obtained from the injection model for series connected VSC(Voltage Source Converter) by adding a constraint that the injected voltage should be in quadrature with the line current. In this paper the static model is implemented into the continuation power-flow (CPF) program. It is shown that SSSC has its intrinsic superiority over TCSC in controllable power flow range.

  • PDF

Modeling and Analysis of the KEPCO UPFC System by EMTDC/PSCAD

  • Yoon, Jong-Su;Kim, Soo-Yeol;Chang, Byung-Hoon;Lim, Seong-Joo;Choo, Jin-Boo
    • KIEE International Transactions on Power Engineering
    • /
    • 제3A권3호
    • /
    • pp.148-154
    • /
    • 2003
  • This paper describes the development of KEPCO's 80MVA UPFC electromagnetic transient model and the analysis of its performance in the actual Korean power system. KEPCO's 80MVA UPFC is currently undergoing installation and will be ready for commercial operation from the year 2003. In order to apply a new FACTS device such as the UPFC to the actual power system, the utility needs, in advance, both load flow stability studies and transient studies. Therefore, KEPRI, the research institute of KEPCO, developed a detailed transient analysis model that is based on the actual UPFC S/W algorithm and H/W specifications. This simulation model is implemented by an EMTDC/PSCAD package. The results of the simulation show the effectiveness of UPFC operation in the KEPCO power system.

Maximization of Transmission System Loadability with Optimal FACTS Installation Strategy

  • Chang, Ya-Chin;Chang, Rung-Fang
    • Journal of Electrical Engineering and Technology
    • /
    • 제8권5호
    • /
    • pp.991-1001
    • /
    • 2013
  • Instead of building new substations or transmission lines, proper installation of flexible AC transmission systems (FACTS) devices can make the transmission networks accommodate more power transfers with less expansion cost. In this paper, the problem to maximize power system loadability by optimally installing two types of FACTS devices, namely static var compensator (SVC) and thyristor controlled series compensator (TCSC), is formulated as a mixed discrete-continuous nonlinear optimization problem (MDCP). To reduce the complexity of the problem, the locations suitable for SVC and TCSC installations are first investigated with tangent vector technique and real power flow performance index (PI) sensitivity factor and, with the specified locations for SVC and TCSC installations, a set of schemes is formed. For each scheme with the specific locations for SVC and TCSC installations, the MDCP is reduced to a continuous nonlinear optimization problem and the computing efficiency can be largely improved. Finally, to cope with the technical and economic concerns simultaneously, the scheme with the biggest utilization index value is recommended. The IEEE-14 bus system and a practical power system are used to validate the proposed method.

다중브리지로 구성된 SSSC의 동특성 분석 (Dynamic Characteristic Analysis of Multi-bridge SSSC)

  • 한병문;박덕희;백승택;김희중;소용철;김현우
    • 전력전자학회논문지
    • /
    • 제5권3호
    • /
    • pp.229-237
    • /
    • 2000
  • 본 논문에서는 멀티브리지 인버터로 구성된 SSSC를 제안하였다. SSSC의 동적특성을 분석하기 위해서 1기 무한모선 전력계통에 SSSC를 연결한 것을 가정하고 EMTP 시뮬레이션을 수행하였고, 축소모형 실험으로 그 특성을 확인하였다. 다중브리지 SSSC는 한 상당 6개의 단상 풀브리지 인버터로 구성되었고, 13-레벨 출력전압을 얻을 수 있다. 다중브리지 SSSC는 전압 주입을 위한 연계 변압기가 필요하기 않고, 전력계통에서 요구되는 동작전압에 따라 브리지 수를 가감하여 용이하게 구성할 수 있다.

  • PDF

Fitness Sharing Particle Swarm Optimization Approach to FACTS Installation for Transmission System Loadability Enhancement

  • Chang, Ya-Chin
    • Journal of Electrical Engineering and Technology
    • /
    • 제8권1호
    • /
    • pp.31-39
    • /
    • 2013
  • Proper installation of Flexible AC Transmission Systems (FACTS) devices in existing transmission networks can enable power systems to accommodate more power transfer with less network expansion cost. The problem to maximize transmission system loadability by determining optimal locations and settings for installations of two types of FACTS devices, namely static var compensator (SVC) and thyristor controlled series compensator (TCSC), is formulated as a mixed discrete-continuous nonlinear optimization problem (MDCP). For solving the MDCP, in the paper, the proposed method with fitness sharing technique involved in the updating process of the particle swarm optimization (PSO) algorithm, can diversify the particles over the search regions as much as possible, making it possible to achieve the optimal solution with a big probability. The modified IEEE-14 bus network and a practical power system are used to validate the proposed method.

직렬 보상 선로에서의 SSR 억제를 위한 강인한 STATCOM 보조 제어기의 설계 (Design of a Robust STATCOM Supplementary Controller to Suppress the SSR in the Series-compensated System)

  • 서장철;문승일;박종근
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제49권3호
    • /
    • pp.136-141
    • /
    • 2000
  • This paper presents the design of an H$\infty$ based robust Static Synchronous Compensator (STATCOM) supplementary controller to suppress the subsynchronous resonance (SSR) in the series-compensated system. The IEEE second benchmark, System-l model is employed for this study. In order to design the effective controller, the modal controllability and observability indices to the oscillation modes are considered. Comprehensive time domain simulations using a nonlinear system model that the proposed STATCOM supplementary controller can suppress the SSR efficiently in spite of the variations of power system operating conditions.

  • PDF

EMTP 시뮬레이션과 축소모형 실험에 의한 SSSC의 성능 해석 (New Performance Analysis of SSSC with EMPT Simulation and Scaled-model Experiment)

  • 강중구;한병문
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제48권5호
    • /
    • pp.524-530
    • /
    • 1999
  • This paper describes performance analysis techniques for SSSC using computer simulations with EMPT and experiments with a hardware scaled-model. A switching-level simulation model with EMTP was developed for the SSSC connected in series with the transmission line. The increase of transmission capability and dynamic performance was analyzed with the simulation model. The simulation results were reverified by experimental works with a hardware scaled-model. The developed analysis techniques can be used for designing and evaluating actual system of SSSC.

  • PDF

Available Transfer Capability Enhancement with FACTS Devices in the Deregulated Electricity Market

  • Manikandan, B.V.;Raja, S. Charles;Venkatesh, P.
    • Journal of Electrical Engineering and Technology
    • /
    • 제6권1호
    • /
    • pp.14-24
    • /
    • 2011
  • In order to facilitate the electricity market operation and trade in the restructured environment, ample transmission capability should be provided to satisfy the demand of increasing power transactions. The conflict of this requirement and the restrictions on the transmission expansion in the restructured electricity market has motivated the development of methodologies to enhance the available transfer capability (ATC) of existing transmission grids. The insertion of flexible AC transmission System (FACTS) devices in electrical systems seems to be a promising strategy to enhance single area ATC and multi-area ATC. In this paper, the viability and technical merits of boosting single area ATC and multi-area ATC using Thyristor controlled series compensator (TCSC), static VAR compensator (SVC) and unified power flow controller (UPFC) in single device and multi-type three similar and different device combinations are analyzed. Particle swarm optimization (PSO) algorithm is employed to obtain the optimal settings of FACTS devices. The installation cost is also calculated. The study has been carried out on IEEE 30 bus and IEEE 118 bus systems for the selected bilateral, multilateral and area wise transactions.

SSSC를 이용한 전력조류제어에 관한 연구 (A Study of the Power Flow Control Using SSSC)

  • 나완기;정재길;이인용;정인학;이홍주
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2000년도 하계학술대회 논문집 A
    • /
    • pp.239-241
    • /
    • 2000
  • This paper describes a modeling of a FACTS(Flexible AC Transmission System) device, namely, SSSC(Static Synchronous Series Compensator) model. The SSSC, a solid-state voltage source inverter coupled with a transformer, is connected in series with a transmission line. SSSC provides controllable compensating voltage, which is in quadrature with the line current, over an capacitive and an inductive range, independently of the magnitude of the line current. This SSSC model is obtained from the injection model for series connected VSC(Voltage Source Converter) by adding a constraint that the injected voltage should be in quadrature with the line current. The paper discusses the basic operating and performance characteristics of the SSSC, and power flow control in power system.

  • PDF