열 감지기의 응답특성에 관한 시험연구 (Experiment study on the Responsiveness of Spot- Type Heat Detector)

  • 이복영
    • 방재기술
    • /
    • 통권19호
    • /
    • pp.9-16
    • /
    • 1995
  • The spot-type heat detector is a main component of the automatic fire alarm system intended to signal when heat energy is produced in protected area. The most of protected area in our country is installed spot-type heat detector. On this study, the responsiveness to the change of environmental temp. of spot-type heat detec-tor were obtained and analyzed under specified temp., velocity in accordance with the KOFEIS stan-dard. The experiment was carried under the condition with the change of environmental temp. Concluion of this study is as follows : 1. It was confirmed that the responsiveness of rate-of rise heat detector is sensitive to temp. below 10 degrees above zero. The malfunction appeared at 40 degrees above zero and intended performance is disqualified at 50 degrees above zero. 2. The intended performance of fixed-temp. detector which is maintained for the change of envi-ronmental temp. But the responsiveneness is confirmed instability for the change of environmental temp.

  • PDF

차동식스포트형열감지기 현장점검용 표준화기기 개발에 관한 연구 (A Study on the Development of Standardization Tester for the Field Inspection of the Rate of Rise Spot Type Heat Detector)

  • 김시국;육현대;양승현;지승욱;이춘하
    • 한국화재소방학회논문지
    • /
    • 제23권3호
    • /
    • pp.85-92
    • /
    • 2009
  • 본 논문은 차동식스포트형열감지기 현장점검용 표준화기기 개발에 관한 연구이다. 현재 소방점검 시 차동식스포트형열감지기의 성능확인을 위해 사용되는 점검기기(4 Type)들을 실험대상으로 선정하여 문제점을 찾고, 도출된 문제점을 바탕으로 차동식스포트형열감지기 형식승인 시 감도시험기준과 동일한 온도조건인 실온보다 $30^{\circ}C$ 높은 온도로 자동설정 할 수 있고 설정된 온도를 계속 유지할 수 있는 기능과 풍속 조건인 풍속 85cm/s를 유지할 수 있는 차동식스포트형열감지기 현장점검용 표준화기기의 회로를 설계하고 시제품을 제작하였다. 개발된 시제품의 성능확인 결과 차동식스포트형열감지기의 형식승인시험 시 감도시험조건과 동일한 성능이 나타나는 것을 확인하였다.

차동식 스포트형 열감지기의 인공 가속열화특성에 관한 연구 (A Study of the Rate of Rise Spot Type Heat Detector on the Artificially Accelerated Aging Characteristics)

  • 김찬영
    • 한국화재소방학회논문지
    • /
    • 제25권2호
    • /
    • pp.107-113
    • /
    • 2011
  • 차동식 스포트형 공기 팽창식 열감지기를 인위적으로 높은 온도에서 가속열화시켜 경년변화되는 특성에 대하여 연구하였다. 이 연구는 현장에 설치된 감지기가 화재 또는 점검기기에 의한 고온의 열에 노출되었을 경우에 감지기의 동작에 미치는 영향을 분석하기 위하여 실험하였다. 실험결과 현장에서 5년 동안 사용되었던 2005년 B사 감지기는 $100^{\circ}C$의 온도에서 1시간 동안 노출되었을 경우에 감지기가 동작하지 않는 경우가 발생하였다. 이것은 감지기 감열실내의 팽창된 공기가 리크공 이외의 곳에서 리크 되었기 때문인 것으로 판단된다. 그러나 감지기의 동작표시를 나타내는 LED는 온도가 $160^{\circ}C$까지 올라갔음에도 불구하고 모두 정상적으로 동작하였다. 따라서 동작표시 LED의 회로소자는 고장은 발생하지 않았음을 알 수 있었다.

인공 가속열화에 따른 차동식 스포트형 열감지기의 고장 원인분석 (Failure Analysis of the Rate of Rise Spot Type Heat Detector on Artificially Accelerated Aging)

  • 김찬영
    • 한국화재소방학회논문지
    • /
    • 제25권4호
    • /
    • pp.48-55
    • /
    • 2011
  • 차동식 스포트형 공기 팽창식 열감지기를 인공 가속열화 시켰을 때 발생하는 고장 원인에 대하여 분석하였다. 감지기에 고장이 발생하는 원인은 감열실 금속을 고정하는 접합재(binder)가 플라스틱 몰딩(moulding)에서 분리되어 발생하는 고장과, 감열실 금속과 다이어프램 금속을 고정하는 플라스틱 몰딩에 균열이 발생되는 고장으로 확인되었다. 고장이 발생하지 않은 감지기는 감열실 금속 및 다이어프램 금속이 플라스틱 몰딩에 접합재로 완전히 부착되어 있었다. 또한 2010G 감지기는 접합재의 기계적 강도를 향상시키기 위하여 접합재에 유리강화섬유가 추가되었음이 확인되었다. 감지기 종류별에 따른 플라스틱과 접합재의 밀도에는 큰 차이가 없었다. 그러나 감지기의 플라스틱에 대한 열중량분석(TGA) 결과, 제작년도는 같지만 제조회사가 다른 2005A와 2005B의 플라스틱 열적특성이 동일하지 않은 것으로 확인되었다.

풍동실험과 화재실험을 통한 열감지기의 동작특성에 관한 연구 (Study on the Operation Characteristics of Heat Detectors through Fire and Wind Tunnel Experiment)

  • Ryu, Hocheol;Kim, Doohyun
    • 한국재난정보학회 논문집
    • /
    • 제11권2호
    • /
    • pp.203-209
    • /
    • 2015
  • 열감지기는 화재시 발생되는 열을 감지하는 것으로 모든 소방대상물에 일반적으로 사용되는 자동화재탐지설비의 중요한 핵심 요소이다. 열감지기는 스포트(spot)형과 분포형으로 구분되며, 스포트형에는 차동식과 정온식이 있다. 이러한 열감지기는 실제 화재시 작동시간 및 작동온도 등 반응의 민감도에 따라 인명과 재산 손실에 큰 영향을 준다. 국내에서는 스프링클러 헤드제품에 응답시간지수를 도입하여 사용하고 있으나, 열감지기에 대해서는 현재 적용이 되어지지 않고 있으며, 반응의 민감도를 표시하는 응답시간지수의 도입이 필수적으로 본 연구에서는 국내 생산된 정온식 스포트형 열감지기와 다이아프램형 및 반도체 형식의 차동식 스포트형 열감지기에 대하여 풍동실험 및 화재실험을 통하여 응답시간지수, 작동시간, 작동온도 등에 대하여 연구하였다. 응답시간지수를 적용한 열감지기를 설치하여 신속한 경보로 인한 국민의 생명과 재산손실을 줄이는데 도움을 주고자 한다.

차동식 열감지기 설치기준 비교분석에 관한 연구 (Differential temperature fire detector analysis of comparative study based on sensor installation)

  • 황동환;양광모;강경식
    • 대한안전경영과학회지
    • /
    • 제16권4호
    • /
    • pp.379-389
    • /
    • 2014
  • Fire detectors are designed to minimize loss of life from a fire alarm system as an alarm to help evacuate more quickly until the completion of the evacuation alarm should be continued. the purpose of such alarms in order to achieve the characteristic fire heat release rate reaches a certain level, or when a certain time has elapsed, when the heat detector is to be alarms to answer. Requires a quick response, it is desirable to install the sensor as much as possible, but taking into account the cost of installation problems by engineering approach to minimize the quantity and rapidity of detection capability should be increased. In order to increase the rapidity of fire detectors in a room according to the height of the sensing period is to be maintained the optimum distance of the fire detector detects characteristics should be considered. Differential spot-type heat detectors installed domestic basis, depending on the type of sensor that can detect one sensor area is limited and less than 4m ceiling height regulations and simply double the number in excess of 4m and intended to be installed.

실내화재에서의 열감지기 동작특성 분석 (Analysis on Activation Characteristic of Heat Detectors in a Compartment Fire)

  • Ryu, Hocheol
    • 한국재난정보학회 논문집
    • /
    • 제10권4호
    • /
    • pp.598-608
    • /
    • 2014
  • 소방대상물에서의 경보설비는 실내에 있는 사람들에게 화재를 최초로 알려주는 설비로써, 보다 많은 사람들을 대피시킬 수 있도록 하는 매우 중요한 역할을 한다. 이에 자동화재탐지설비와 같은 경보설비의 최초동작을 빠르게 하기 위한 연구가 필요하다. 이러한 자동화재탐지설비에서 감지기의 동작은 설치위치와 화원의 위치에 따른 영향을 가장 많이 받는다. 그럼에도 불구하고 국내의 감지기 설치 기준은 설치 위치와 화원의 위치는 중시하지 않고 면적과 높이에 따른 화재감지기 설치에 대한 사항만을 규정하고 있다. 따라서 본 연구에서는 실내에 열감지기와 보를 설치하고, 일반적인 화재를 가정하여 5 개소의 화원을 발생시켜 설치된 감지기의 동작시간을 측정하였고, 감지기의 설치위치와 화원의 위치를 고려한 화재실험을 통하여 열감지기의 동작특성을 분석한 것으로 다음과 같은 결론을 얻었다. 열감지기는 벽면에 근접하게 설치된 감지기에서 작동지연현상이 보였으며, 벽면에서 적어도 22cm 이상 이격해서 설치하여야 한다. 화원이 보 외측에 존재할 때 감지기는 보에서 55cm 이격한 거리에서 동작이 가장 빨랐다. 또한 화원에 근접한 감지기와 가장 늦게 동작한 감지기의 동작시간의 차이는 피난거리로 환산하였을 때 최대 115 m 의 피난거리가 확보되는 것으로 나타났다. 이를 통하여 적합한 위치와 적응성을 고려한 감지기의 선택은 피난개시 시간을 최소화시켜 줄 수 있는 것을 확인하였다.

화재모델링을 위한 정온식 열감지기의 장치물성 측정 (Measurement of the Device Properties of Fixed Temperature Heat Detectors for the Fire Modeling)

  • 박희원;조재호;문선여;박충화;황철홍;김성찬;남동군
    • 한국화재소방학회논문지
    • /
    • 제28권1호
    • /
    • pp.37-43
    • /
    • 2014
  • 성능위주 소방설계(PBD)의 과정에서 화재 및 피난모델링의 신뢰성을 확보하기 위해서는 화재감지기 모델의 높은 예측성능이 필수적으로 요구된다. 본 연구의 목적은 대표적인 화재모델인 FDS에 적용되고 있는 정온식 열감지기의 정확한 작동 개시시간을 예측하기 위한 입력정보를 측정하는 것이다. 이를 위해 화재감지기의 장치특성을 측정할 수 있는 Fire Detector Evaluator (FED)가 사용되었으며, 국내에서 적용되는 2개의 써미스터 방식(Thermistor types)과 1개의 바이메탈 방식(Bimetal type)의 스포트형 정온식 열감지기가 연구대상으로 고려되었다. 화재모델링을 위해 요구되는 감지기의 작동 개시온도 및 반응시간지수(Response Time Index)가 측정되었으며, 이때 RTI는 감지기의 설치위치를 고려하여 천장제트기류(Ceiling jet flow)와 수직제트기류(Vertical jet flow)에 대하여 측정되었다. 측정된 장치물성을 이용한 화재모델링 결과는 실규모 구획화재실험 결과와 비교 검증되었다. 그 결과 수치적으로 예측된 감지기의 작동 개시시간은 실험결과를 적절히 잘 예측함을 확인하였다.

차동식열감지기 현장점검용기기 개발에 관한 연구 (A Study on the Development of Tester for the Field Inspection of the Rate of Rise Spot Type Heat Detector)

  • 김시국;이춘하;지승욱;육현대;양승현
    • 한국화재소방학회:학술대회논문집
    • /
    • 한국화재소방학회 2009년도 춘계학술논문발표회 논문집
    • /
    • pp.200-209
    • /
    • 2009
  • 본 논문은 차동식스포트형열감지기 현장점검용기기 개발에 관한 연구이다. 현재 소방점검 시 차동식스포트형열감지기의 성능확인을 위해 사용되는 점검기기(4 Type)들을 실험대상으로 선정하여 문제점을 찾고, 도출된 문제점을 바탕으로 감지기 형식승인 시 감도시험기준 조건과 동일한 온도조건인 주위온도 대비 30$^{\circ}C$ 높은 온도로 자동설정 할 수 있는 기능과 그 온도를 계속 유지할 수 있는 기능을 갖춘 새로운 차동식스포트형열감지기 현장점검용 기기의 시제품을 제작하고 그 성능을 확인하였다.

  • PDF