Experiment study on the Responsiveness of Spot- Type Heat Detector (열 감지기의 응답특성에 관한 시험연구)

  • Lee, Bok-Yeong
    • Fire Protection Technology
    • /
    • s.19
    • /
    • pp.9-16
    • /
    • 1995
  • The spot-type heat detector is a main component of the automatic fire alarm system intended to signal when heat energy is produced in protected area. The most of protected area in our country is installed spot-type heat detector. On this study, the responsiveness to the change of environmental temp. of spot-type heat detec-tor were obtained and analyzed under specified temp., velocity in accordance with the KOFEIS stan-dard. The experiment was carried under the condition with the change of environmental temp. Concluion of this study is as follows : 1. It was confirmed that the responsiveness of rate-of rise heat detector is sensitive to temp. below 10 degrees above zero. The malfunction appeared at 40 degrees above zero and intended performance is disqualified at 50 degrees above zero. 2. The intended performance of fixed-temp. detector which is maintained for the change of envi-ronmental temp. But the responsiveneness is confirmed instability for the change of environmental temp.

  • PDF

A Study on the Development of Standardization Tester for the Field Inspection of the Rate of Rise Spot Type Heat Detector (차동식스포트형열감지기 현장점검용 표준화기기 개발에 관한 연구)

  • Kim, Shi-Kuk;Yuk, Hyun-Dai;Yang, Seung-Hyun;Jee, Seung-Wook;Lee, Chun-Ha
    • Fire Science and Engineering
    • /
    • v.23 no.3
    • /
    • pp.85-92
    • /
    • 2009
  • This paper studied on the development of standardization tester for the field inspection of the rate of rise spot type heat detector. It was to find the problems of the 4 type's testers such as A type (electric bulb type), B type (halogen lamp type), C type (heating coil type), D type (fumigator type) which were used to check of the rate of rise spot type heat detector in inspection for the fire protection. To identify those problems, this paper described about the development of standardization tester for the field inspection of the rate of rise spot type heat detector and that have the function of auto setting temperature more $30^{\circ}C$ higher than room temperature and keep the constant temperature. And keep the constant wind velocity of 85cm/sec. Performance verification results of the developed prototype that had same conditions such as the sensitivity test conditions at the type approval of the rate of rise spot type heat detector.

A Study of the Rate of Rise Spot Type Heat Detector on the Artificially Accelerated Aging Characteristics (차동식 스포트형 열감지기의 인공 가속열화특성에 관한 연구)

  • Kim, Chan-Young
    • Fire Science and Engineering
    • /
    • v.25 no.2
    • /
    • pp.107-113
    • /
    • 2011
  • This paper presents the results of artificially accelerated aging characteristics of the rate of rise spot type heat detectors. This experiment carried out to investigate the detector's operating characteristics when a fire was broken out or the regular tests were performed. The result showed that the delay of operating time or no-operation of heat detector which was made by company B and used in the field for 5 years may be occurred even at the $100^{\circ}C$. This result is due to the leakage of inflated air from heat chamber. However the operating display LED was not out of order, even if the temperature was increased up to $160^{\circ}C$.

Failure Analysis of the Rate of Rise Spot Type Heat Detector on Artificially Accelerated Aging (인공 가속열화에 따른 차동식 스포트형 열감지기의 고장 원인분석)

  • Kim, Chan-Young
    • Fire Science and Engineering
    • /
    • v.25 no.4
    • /
    • pp.48-55
    • /
    • 2011
  • This paper presents the failure analysis of the rate of rise spot type heat detectors on artificially accelerated aging. The failures of heat detector turned out by two reasons. The first one is the separation of binder from plastic moulding, resulting in the leakage of air from heat chamber. The second reason is the crack of plastic. The large cracks were maybe created by these reasons, thermal expansion difference, mechanical stress, or growth of microcrack. In the sound detector, the separation and the crack were not occurred or not developed to the critical size. The glass fibers which increase the mechanical strength were added in the binder of detector 2010G. The densities of binder or plastic of each detector were similar. However, the TGA result shows that the thermal characteristics of 2005A and 2005B were not similar.

Study on the Operation Characteristics of Heat Detectors through Fire and Wind Tunnel Experiment (풍동실험과 화재실험을 통한 열감지기의 동작특성에 관한 연구)

  • Ryu, Hocheol;Kim, Doohyun
    • Journal of the Society of Disaster Information
    • /
    • v.11 no.2
    • /
    • pp.203-209
    • /
    • 2015
  • The heat detector detects heat in the fire and is an important core element of the automatic fire alarm system used generally for every fire prevention objects. The heat detector is distinguished in spot type and spread type and in spot type, there are differential and thermistor types. These heat detectors give a great influence on the loss of people and property according to the sensitivity of response such as operation time and operation temperature in actual fire and in overseas people apply it for the development of products that can be operated in the early stage of fire including certification, quality management, and comparison standard by introducing response time index through the theory of heat balance that considers the heat loss and ventilation tests. In Korea, the response time index is introduced and used in the head of sprinkler products, but it is not applied to the heat detector at present. It is necessary to introduce the response time index that shows the sensitivity of response of the heat detector the installation standard for the heat detector that the response time index is applied should be different according to the fire weight, danger degree of fire, and shape of buildings. Through this study, it tries to help reduce lives and property of people through the swift warning by installing detectors suitable for the building structure.

Differential temperature fire detector analysis of comparative study based on sensor installation (차동식 열감지기 설치기준 비교분석에 관한 연구)

  • Hwang, Dong-Hwan;Yang, Kwang Mo;Kang, Kyung-Sik
    • Journal of the Korea Safety Management & Science
    • /
    • v.16 no.4
    • /
    • pp.379-389
    • /
    • 2014
  • Fire detectors are designed to minimize loss of life from a fire alarm system as an alarm to help evacuate more quickly until the completion of the evacuation alarm should be continued. the purpose of such alarms in order to achieve the characteristic fire heat release rate reaches a certain level, or when a certain time has elapsed, when the heat detector is to be alarms to answer. Requires a quick response, it is desirable to install the sensor as much as possible, but taking into account the cost of installation problems by engineering approach to minimize the quantity and rapidity of detection capability should be increased. In order to increase the rapidity of fire detectors in a room according to the height of the sensing period is to be maintained the optimum distance of the fire detector detects characteristics should be considered. Differential spot-type heat detectors installed domestic basis, depending on the type of sensor that can detect one sensor area is limited and less than 4m ceiling height regulations and simply double the number in excess of 4m and intended to be installed.

Analysis on Activation Characteristic of Heat Detectors in a Compartment Fire (실내화재에서의 열감지기 동작특성 분석)

  • Ryu, Hocheol
    • Journal of the Society of Disaster Information
    • /
    • v.10 no.4
    • /
    • pp.598-608
    • /
    • 2014
  • The first operation of alarm system starts at a detector. And the largest effect is produced on the operation of detector by the fire source position and installation position. Nevertheless, the Korean standard for the installation of detector only specifies matters of fire detector installation according to area and height, without consideration of installation position and fire source position. Therefore, this study carried out a fire test in consideration of detector installation position and fire source position (5 places) in order to minimize casualties owing to the fast operation of fire detector when a fire occurred. Considering that it took the longest time for a detector close to a wall to work in the results of this test, it was possible to find that a minimum clearance to the wall was required.

Measurement of the Device Properties of Fixed Temperature Heat Detectors for the Fire Modeling (화재모델링을 위한 정온식 열감지기의 장치물성 측정)

  • Park, Hee-Won;Cho, Jae-Ho;Mun, Sun-Yeo;Park, Chung-Hwa;Hwang, Cheol-Hong;Kim, Sung-Chan;Nam, Dong-Gun
    • Fire Science and Engineering
    • /
    • v.28 no.1
    • /
    • pp.37-43
    • /
    • 2014
  • The high predictive performance of fire detector models is essentially needed to assure the reliability of fire and evacuation modeling in the process of Performance-Based fire safety Design (PBD). The main objective of the present study is to measure input information in order to predictive the accurate activation time of fixed temperature heat detectors adopted in Fire Dynamics Simulator (FDS) as a representative fire model. To end this, Fire Detector Evaluator (FDE) which could be measured the device properties of detector was used, and the spot-type fixed temperature heat detectors of two thermistor types and one bimetal type were considered as research objectors. Activation temperature and Response Time Index (RTI) of detectors required for the fire modeling were measured, and then the RTI was measured for ceiling jet flow and vertical jet flow in consideration of the install location of detectors. The results of fire modeling using measured device properties were compared and validated with the experimental results of full-scale compartment fires. It was confirmed that, in result, the numerically predicted activation time of detector showed reasonable agreement with the measured activation time.

A Study on the Development of Tester for the Field Inspection of the Rate of Rise Spot Type Heat Detector (차동식열감지기 현장점검용기기 개발에 관한 연구)

  • Kim, Shi-Kuk;Lee, Chun-Ha;Jee, Seung-Wook;Yuk, Hyun-Dai;Yang, Seung-Hyun
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2009.04a
    • /
    • pp.200-209
    • /
    • 2009
  • 본 논문은 차동식스포트형열감지기 현장점검용기기 개발에 관한 연구이다. 현재 소방점검 시 차동식스포트형열감지기의 성능확인을 위해 사용되는 점검기기(4 Type)들을 실험대상으로 선정하여 문제점을 찾고, 도출된 문제점을 바탕으로 감지기 형식승인 시 감도시험기준 조건과 동일한 온도조건인 주위온도 대비 30$^{\circ}C$ 높은 온도로 자동설정 할 수 있는 기능과 그 온도를 계속 유지할 수 있는 기능을 갖춘 새로운 차동식스포트형열감지기 현장점검용 기기의 시제품을 제작하고 그 성능을 확인하였다.

  • PDF