• Title/Summary/Keyword: Protection IED

Search Result 65, Processing Time 0.027 seconds

A Study of the Operating Characteristic for Voltage Restrained Overcurrent Relay using the ATPDraw5.7p4 Modeling Data (ATPDraw5.7p4 모델링 데이터를 이용한 전압억제 과전류계전기 동작특성에 관한 연구)

  • Park, Chul-Won;Ban, Yu-Hyeon
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.61 no.1
    • /
    • pp.23-28
    • /
    • 2012
  • The market of domestic Power Plant Generator Protection and Control System (GPCS) is narrow and required the high reliability, and technology. So, it is still operated as turn-key. In recent years, digital relays has evolved into IED can perform the control and monitoring functions without central monitoring based on IEC61850 international standards communications, and attention for advancement of smart grid and ECMS has been increased in South Korea. The increasing attention on multi-function IED, DGPS(digital generator protection system), for internal fault protection of large generator results in starting a national project in South Korea, the IED prototype development for next-generation power units. The voltage restrained overcurrent relay have been used as back-up overcurrent protection for generators. In this paper, voltage restrained overcurrent relay is one of the back-up protective factors in generator protection IED was presented. For evaluation performance of the voltage restrained overcurrent relay, the data of ATPDraw5.7p4 modeling was used.

Hardware Design of IED using DSP for Power Transformer Protection (DSP를 이용한 전력용 변압기용 IED의 하드웨어 설계)

  • Park C. W.;Jung Y. M.;Ha K. J.;Koo C. S.;Shin M. C.
    • Proceedings of the KIEE Conference
    • /
    • summer
    • /
    • pp.363-365
    • /
    • 2004
  • This paper proposes a hardware implementation of intelligent electronic device for power transformer protection. And proposes an advanced main protection algorithm by voltage-current trend and flux-differential current slope characteristics. The secondary protection functions include UR, OCGR, OVR, and W etc. The main board of IED is based on the DSP chip TMS32C32 processor The IED was tested with relaying signals obtained for EMTP simulation package.

  • PDF

Testing of Advanced Relaying and Design of Prototype IED for Power Transformer Protection (전력용 변압기 보호용 시제품 IED 설계와 개선된 기법의 시험)

  • Park, Chul-Won;Shin, Myong-Chul
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.55 no.1
    • /
    • pp.6-12
    • /
    • 2006
  • A popular method used by primary protection for power transformer is current ratio differential relaying (RDR) with 2nd harmonic restraints. In modern power transformer due to the use of low-loss amorphous material, the 2nd harmonic component during inrush is significantly reduced. The higher the capacitance of the high voltage status and underground distribution, the more the differential current includes the 2nd harmonic component during internal fault. Thus the conventional method may not operate properly. This paper proposes an advanced relaying algorithm and the prototype IED hardware design and it's real-time experimental results. To evaluate performance of the proposed algorithm, the study is well constructed power system model including power transformer utilizing the EMTP software and the testing is made through simulation of various cases. The proposed relaying that is well constructed using DSP chip and microprocessor etc. has been developed and the prototype IED has been verified through on-line testing. The results show that an advanced relaying based prototype IED never mis-operated and correctly identified all the faults and that inrushes that are applied.

A Study on Setting of IED for Small Hydro Generation System (소수력 발전시스템을 위한 IED의 정정치에 관한 연구)

  • Ahn, Tae-Pung;Park, Chul-Won
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.66 no.1
    • /
    • pp.15-20
    • /
    • 2017
  • In order to advance and improve the performance of domestic aged power plants, IEDs have been developed for power generation systems. For smooth installation and operation of the protection relays, a detail settings study of IED is required. This paper deals with an analysis based on PSCAD and setting investigation of IED for loss of field, reverse power protection in Small Hydro Generation System.

Intelligent Electronic Device for Power Transformer Protection (전력용 변압기 보호를 위한 IED)

  • Park, Chul-Won;Shin, Myong-Chul
    • Proceedings of the KIEE Conference
    • /
    • 2005.07a
    • /
    • pp.365-367
    • /
    • 2005
  • This paper proposes a hardware of IED for power transformer protection that is well constructed using DSP chip and MPU chip. The performance of the adaptive relaying algorithm, by real-time testing in a prototype of it, has been verified. And test results indicate the proposed relaying of the IED was proven to be faster and more reliable.

  • PDF

Calculation of an Indicator for Early Death Using Atomic Bomb Survivors' Data

  • Sasaki, Michiya;Fujimichi, Yuki;Yoshida, Kazuo;Iwasaki, Toshiyasu
    • Journal of Radiation Protection and Research
    • /
    • v.47 no.1
    • /
    • pp.22-29
    • /
    • 2022
  • Background: A comprehensive, traceable, and easy-to-understand radiation risk indicator is desired for radiological protection. The early-onset hypothesis could be used for this purpose. Materials and Methods: An indicator for early death (IED) was developed and calculated using the epidemiological dataset from the 14th Report of the Life Span Study (LSS) of Hiroshima and Nagasaki. By clarifying the calculation process, IED for all-cause mortality was estimated. In addition, the characteristics of IED for solid cancer mortality and cardiovascular mortality as well as those of men and women, and their dependence on age at exposure were investigated for detailed analysis. Results and Discussion: The IED for all-cause mortality was estimated to be approximately 4 years for an acute radiation exposure of 1 Gy regardless of the fitting dose range. The cumulative death rate for all solid cancers also indicated the early-death tendency (approximately 7-10 years at 1 Gy). Although, there is a slight difference in the characteristics of the risk obtained from the LSS study and this study, it is considered that the IED in a unit of years can also be used to show the overall picture of risk due to radiation exposure. Conclusion: We developed and calculated the indicator for early death, IED, for the cumulative mortality rate of all causes of death, all solid cancers, and circulatory diseases. The quantitative values of IED were estimated to be 4 years for all causes of death, 7-10 years for all solid cancers. IED has an advantage for intuitively understanding the meaning of radiation risk since it can be obtained by a simple and traceable method.

Performance Analysis of the GOOSE Transmission of an IED Considering Network Redundancy (네트워크 이중화를 고려한 IED GOOSE 전송에 관한 성능 분석)

  • Lee, Nam-Ho;Jang, Byung-Tae
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.23 no.10
    • /
    • pp.75-80
    • /
    • 2009
  • In order to prevent loss of communication packets and drop of transmission speed owing to the network fault occurrence, it should be considered network redundancy. That is why a messages of IED GOOSE is the critical signal in charge of protection and control of the substation. So most of users implement the substation automation system with Hybrid network topology ant IED supporting double ethernet ports. Because IEC 61850 GOOSE conformance test is limited in the functional test, this paper suggests how to test the performance of IED GOOSE transmission considering Network redundancy, and describes the analysis of an example test on real IEDs and how to impact the IED GOOSE performance to the substation automation system.

Real-time Testing and Hardware Design of Intelligent Electronic Device for Power Transformer Protection (전력용 변압기 보호를 위한 통합보호제어장치의 하드웨어 설계와 실시간 성능 시험)

  • Park, Chul-Won
    • Proceedings of the KIEE Conference
    • /
    • 2005.10a
    • /
    • pp.122-127
    • /
    • 2005
  • This paper proposes a prototype IED hardware design and it's real-time experimental results. To evaluate performance of the IED, the study is well constructed power system model including power transformer utilizing the EMTP software and the testing is made through simulation of various cases. The relaying that is well constructed using DSP chip and RISC CPU etc. has been developed and the prototype IED has been verified through on-line testing by LabVIEW simulator. The results show that an advanced relaying based prototype IED never mis-operated.

  • PDF

A New Agent Based Fault Tolerant IED System and Its Reliability Analysis (새로운 에이젼트 기반의 결함극복 IED시스템 및 신뢰성 분석)

  • Fan, Weizhong;Lee, Dong-Wook;Lee, Seun-Jae;Lim, Sung-Il;Han, Seung-Soo
    • Proceedings of the KIEE Conference
    • /
    • 2005.07b
    • /
    • pp.1371-1373
    • /
    • 2005
  • Nowadays, Intelligent Electronic Devices(IED) are widely used in power system. In order to improve the selectivity, sensitivity, and reliability of the power system composed by IEDs, A new fault tolerant IED system based on agent technique is presented in this paper. in the presented system, different with existing IED systems, the redundancies are drawn out from IED devices, and compose a standby backup system. And those redundancies are not specified to a particular type of IEDs. By using the agent technique, redundancies can download agents to modify their functions to fit different types of IEDs. As a conclusion, the reliability of the presented system is estimated in this paper.

  • PDF

Over-Excitation Protection Relaying using the 345kV Power System Modeling Data (345kV 계통 모델링 데이터를 활용한 과여자 보호계전기법)

  • Park, Chul-Won;Ban, Yu-Hyeon
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.60 no.4
    • /
    • pp.175-180
    • /
    • 2011
  • A large AC generator is an important component of the power system. It is a need for research of AC generator protection relay for the next-generation ECMS and an efficient operation of protection control system. However, most of protection and control systems used in power plants have been still imported as turn-key and operated in domestic. This may cause the lack of the correct understanding on the protection systems and methods, and thus have difficulties in optimal operation. In this paper, over-excitation protection relaying is one of the protective factors in generator protection IED was presented. The cause and protection principles were dealt and, DFT-based gain compensation algorithm was adopted for the frequency measurement. The Republic of Korea 345kV modeling data by EMTP-RV was used for performance evaluation.