• 제목/요약/키워드: Power Cables

검색결과 675건 처리시간 0.038초

배전급 해저케이블의 절연열화진단 (Insulation Aging Diagnostics of Submarine Medium Voltage Power Cables)

  • 모종명;이동영;송광용
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2001년도 추계학술대회 논문집 전력기술부문
    • /
    • pp.149-152
    • /
    • 2001
  • In this work, we have conducted insulation aging assessment and maintenance for submarine medium voltage power cable systems to discriminate and maintain bad cables economically. We have found that aging status of submarine cable systems are very poor and in progress. We have found that insulation status were improved with the replacement of cable terminations. We have confirmed with the electrical and structural analysis of terminations, that the poor aging status of cables are mainly caused not by the cable insulations but by the aging of cable terminations. From the above results, we have also confirmed that the domestic diagnostic system is successful and convenient for the discrimination and maintenance of the damaged cables economically.

  • PDF

원전 저압케이블 열화도 평가를 위한 초음파 음속계측에 관한 연구 (A Study on the Measurement of Ultrasound Velocity to Evaluate Degradation of Low Voltage Cables for Nuclear Power Plants)

  • 김경조;강석철;구철수;김진호;박재석;주금종;박치승
    • 비파괴검사학회지
    • /
    • 제24권4호
    • /
    • pp.325-330
    • /
    • 2004
  • 원자력발전소에는 여러 종류의 케이블이 전력공급, 감시 및 제어신호의 전달을 위해 열악한 환경하에서 이용되고 있다. 발전소의 안전한 운전을 위해서 이 케이블이 어느 정도 열화 되었는지 확인할 필요가 있다. 특히, 원자력발전소의 수명 연장과 더불어 저압 케이블을 장기간 사용함에 따라서 저압케이블의 열화를 평가하기 위한 방법이 필요하게 되었다 저압케이블의 열화를 측정하는 파라미터로는 주변 온도, 절연재질의 경도, 파단시 연신률(EAB, Elongation At Breaking Point) 등이 있다. 그러나, 온도나 경도를 계측하는 검사는 정량적인 판단기준의 설정이 곤란하고 진단의 정밀도가 낮으며, 부분적으로 샘플링하는 방법은 샘플링되는 케이블에 연결된 부하를 정전시켜야 하고 장소와 시간적인 제약이 있으며, 전기적 측정법은 노화 초기부터 중기까지의 열화정도를 확인하기 어렵다. 본 연구에서는 재료의 열화에 따라서 초음파의 음속이 변화한다는 이론적인 배경(1,2)을 바탕으로 저압 케이블 재료의 열화에 따른 초음파의 음속을 측정하였다. 이를 위해, 원자력발전소에서 사용되는 저압케이블을 가속 열화시켰으며, 저압케이블의 피복재에서 초음파의 음속을 측정할 수 있는 장비를 개발하여, 초음파의 음속측정 후 인장시험을 통해 파단시 연신률을 측정하였다. 파단시 연신률이 증가함에 따라서 음속이 선형적으로 감소하였으며, 초음파의 음속은 열화의 정량적 평가 파라미터로서의 사용 가능성을 확인할 수 있었다.

전력선 용량증대를 위한 해저케이블 설계 (Design of Submarine Cable for Capacity Extension of Power Line)

  • 손홍철;문채주;김동섭
    • 한국전자통신학회논문지
    • /
    • 제17권1호
    • /
    • pp.77-84
    • /
    • 2022
  • 해저 전력케이블은 수면 아래로 전력을 운송하는 송전케이블이다. 최근 해저케이블은 해상의 재생에너지인 풍력, 파력 및 조류시스템 등의 전력을 육지로 전송하며, 이 케이블이 위치하는 장소에 따라 해저에 매설하거나 해저면에 놓여진다. 전력케이블은 극한 환경에서 이용되어 왔기 때문에 가혹한 조건들과 온도 및 강한 조류를 견디도록 제작되나, 해저조건은 해상케이블에 대해 수 많은 종류의 심각한 손상을 만들기에 충분한 조건을 갖는다. 이러한 원인은 전력전송을 중단시키는 케이블 손상을 가져온다. 본 논문에서는 케이블에 대한 설계기준과 시공절차와 난제 그리고 케이블 전환 접속시스템에 대하여 연구한다. 설계된 해저케이블의 규격은 154kV 기존 케이블 1회선과 신규 케이블 2회선 등 3회선으로 구성되고, 선로당 100MVA 전력용량을 갖는다. 해저케이블 매설깊이를 결정하고 기존 및 신규 케이블을 함께 배치하는 방법을 연구하였다. 지중선로에 대한 해저케이블의 전력용량 허용값을 계산하였고 그 결과 케이블 선로당 100MW 이상의 전력용량을 갖는다는 것을 확인하였다.

고압케이블의 절연열화 특성 (Characteristics of Insulation Aging in High Voltage Cables)

  • 김경열
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2010년도 하계학술대회 논문집
    • /
    • pp.88-88
    • /
    • 2010
  • High Voltage cross-linked polyethylene (XLPE) cables are widely used in a thermal power plant. These cables had been in service for 26 years. The insulation condition of six 6 kV XLPE cables was estimated by insulation diagnostic analyzer (IDA) with voltage amplifier. IDA was measured dissipation factor and capacitance of the whole cable as a function of frequency and voltage. This system measures in the frequency range from 0.1 to 10 Hz at each voltage level. Six XLPE cables are judged good condition, but three cables are analyzed at an aged condition.

  • PDF

화력발전소 고전력 케이블의 누설 전류 측정 데이터의 표준 편차값을 사용한 절연감시 데이터 분석 (Analysis of Monitored Insulation Data Using Standard Deviation of Leakage Current Data in High-Power Cables at a Thermoelectric Power Station)

  • 김보경;엄기홍
    • 한국인터넷방송통신학회논문지
    • /
    • 제17권2호
    • /
    • pp.245-250
    • /
    • 2017
  • 케이블은 설치하여 동작함과 동시에 열화과정이 진행된다. 고압전력케이블 시스템에 있어, 케이블의 절연층 및 방식층의 절연상태뿐만 아니라 케이블을 연결하는 단말부 및 접속부의 절연상태도 함께 감시하여야 케이블 시스템의 절연상태를 종합 관리할 수 있다. 케이블 시스템(케이블 자체 및 접속재)의 상태가 계속 나빠지는 경우, XLPE의 절연 파괴현상으로 인한 화재가 발생한다. 우리는 케이블시스템의 절연 상태를 감시하기 위한 장비를 개발하여 충남 태안의 한국 서부발전주식회사(Korea Western Power Co. Ltd.)에 설치하였다. 이 논문에서, 이 장비를 사용하여 케이블에 흐르는 누설전류를 추출하여 누설전류의 표준편차를 계산하여 분석한 결과를 제시한다. 정해진 누설 전류의 표준 편차값이 기준값 미만이면 안전하지만. 그 이상이면 케이블시스템의 단말부 및 접속부의 절연상태가 나쁜 것으로 판단하고, 새로운 케이블시스템의 단말부 및 접속부로 대체함으로써 전력공급 중단으로 인한 전력설비의 중단사고를 미연에 방지할 수 있다.

Development and performance test of a liquid nitrogen circulation pump for HTS power cable

  • Seok, Jihoon;Kim, Dongmin;Lee, Changhyeong;Kim, Manryeol;Choi, Jeongdong;Kim, Seokho
    • 한국초전도ㆍ저온공학회논문지
    • /
    • 제20권3호
    • /
    • pp.28-33
    • /
    • 2018
  • With the continuous performance improvement and commercialization of HTS wires, there have been many efforts to commercialize HTS power cables recently. Unlike conventional power cables, a cryogenic cooling system is required for a HTS power cable and a cryogenic pump is one of the essential components to circulate subcooled liquid nitrogen and cool the HTS power cable. Especially, the development of a reliable and high-efficiency cryogenic pump is an important issue for the commercialization of HTS power cables of several kilometers or more. In this study, we designed and fabricated a cryogenic pump for subcooled liquid nitrogen with a mass flow rate of 1.2 kg/s, a differential pressure of 5 bar, and evaluated the hydraulic performance of the pump. Impeller design was conducted to meet the target design performance with 1 D analysis model and CFD analysis. The pump performance parameters such as pressure heads, mass flow rates, and efficiencies in accordance with rotating speeds were assessed using a laboratory's performance evaluation system.

고정 방식 차이에 따른 배전 가공전선의 고주기피로 수명 특성 비교 평가 (Clamp Type-dependent HCF Life Estimation of the Overhead Cable for Distribution Grids)

  • 이두영;정진성;김영대;방지예
    • KEPCO Journal on Electric Power and Energy
    • /
    • 제7권2호
    • /
    • pp.241-248
    • /
    • 2021
  • High cycle fatigue life for the cables with two different types of clamps is estimated comparatively through acceleration testing. The high cycle fatigue fracture of overhead lines is caused mainly by the aeolian vibration which is induced by vortex shedding. It is necessary to manage the integrity of cables continuedly considering that the aeolian vibration is unavoidable since it occurs in steady and relatively low wind velocity. Two types of clamps which are largely used for overhead lines of the distribution grids are selected and failure data are obtained by step stress testing with a electrodynamic shaker with them. The inverse power law is assumed to describe the stress-life relationship and the fatigue limit at any specified life is supposed to follow Weibull distribution. The life of the cable is defined as the number of cycles to the time that one of strands is completely broken. Finally, the fatigue limits of the cables with two clamp types are estimated at the reference life of 500 Mcycles and compared each other based on a bending vibration amplitude.

22.9[kV] 지중배전용 전력케이블의 전기적 특성과 파괴수명 고찰 (The Consideration of Electrical Characteristics and Breakdown Lifetime in 22.9[kV] Underground Distribution Power Cables)

  • 김충배;홍경진;임장섭;정우성;김상준;김태성
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제48권9호
    • /
    • pp.628-633
    • /
    • 1999
  • Degradation diagnosis of XLPE insulated URD cables was accomplished through out new method, which was to be analyzed by non-electrical experiments and synthesized by degradation points. To supplement this method, It was also carried out using several electrical analyses. Tan$\delta$ had commonly a different tendency by means oftemperature and frequency and also appeared higher at the outer part rather than innerpart of insulator. PD-q increased generally in proportion to the applied voltage andshowed regular patterns in relation to the thickness of insulator. Breakdown voltageswere measured and breakdown lifetimes were predicted appling for Weibull distribution function. As a result, breakdown lifetime in failure cables was shorter up to$\fraction one-third$ times than that in general cables. It was very available to estimate cable degradation using above method, but it needs further study on XLPE insulated URD cables in order to improve reliability.

  • PDF

가속열화 된 CSPE 상태감시법 유효성 평가 (A Study on Practicality of Condition Monitoring Method of Accelerated Thermal Aging CSPE)

  • 이정훈;구철수;김인용;신용덕
    • 전기학회논문지
    • /
    • 제60권11호
    • /
    • pp.2088-2092
    • /
    • 2011
  • The accelerated thermal aging of CSPE(chloro sulfonate polyethylene) of test cables were carried out for the period equal to 10, 20 and 30 years in air at $100^{\circ}C$, respectively. The CSPE cables(TAIHAN electric wire Co. Ltd) which installed in nuclear power plant for three years were used as starting materials. Condition monitering methods of the accelerated thermal aging of CSPE cables were estimated through indenter modulus and OIT(oxidation induction time) of IEC 62582, and those were newly estimated through volume electrical resistivity, ultrasound reflection time, density, FE-SEM(field emission scanning electron microscopy), XPS(x-ray photoelectron spectroscopy), EDS(energy dispersive spectroscopy), and WD-XRF(wavelength dispersive x-ray fluorescence). A new condition monitoring methods of the accelerated thermal aging of CSPE cables were generally coincident with trend of indenter modulus expect EDS, XPS and XRF. A volume electrical resistivity among new condition monitoring methods of the accelerated thermal aging of CSPE cables is excellent. It is considered that life-time of CSPE cable can be predicted through volume electrical resistivity, if CSPE jacket was aged for period such as more than 20 years.

이종매질에서의 이종전력케이블에 대한 은도 및 허용전류 계산 (The Ampacity of Dissimilar Power Cables Installed in Thermally Dissimilar Soil Materials)

  • 정성환;최상봉;남기영;류희석;이재덕
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2005년도 제36회 하계학술대회 논문집 A
    • /
    • pp.399-401
    • /
    • 2005
  • When power cables cross regions with unfavorable thermal conditions, conductor temperatures higher than the design value can occur. This paper proposes the calculation algorithms of the permissible current-carrying capability of dissimilar power cables installed in thermally dissimilar soil materials.

  • PDF