Insulation Aging Diagnostics of Submarine Medium Voltage Power Cables

배전급 해저케이블의 절연열화진단

  • Published : 2001.11.16

Abstract

In this work, we have conducted insulation aging assessment and maintenance for submarine medium voltage power cable systems to discriminate and maintain bad cables economically. We have found that aging status of submarine cable systems are very poor and in progress. We have found that insulation status were improved with the replacement of cable terminations. We have confirmed with the electrical and structural analysis of terminations, that the poor aging status of cables are mainly caused not by the cable insulations but by the aging of cable terminations. From the above results, we have also confirmed that the domestic diagnostic system is successful and convenient for the discrimination and maintenance of the damaged cables economically.

Keywords