• Title/Summary/Keyword: Partial discharge property

Search Result 29, Processing Time 0.023 seconds

Partial Discharge Property of Hydrogenerator Stator Windings (수력발전기 고정자 권선에서 부분방전 특성)

  • Kim, Hee-Dong
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2000.05a
    • /
    • pp.86-90
    • /
    • 2000
  • Partial discharge(PD) tests were performed when the hydrogenerator(rated 11kV and 25MVA) was shut down(off-line). Six cable couplers were installed in the ring bus as well as within hydrogenerator terminal box. PD tests were conducted using partial discharge analyzer(PDA) and digital partial discharge detector(PDD). PDA showed that the normalized quantity number(NQN) and the partial discharge magnitude increased with increase of ac voltage. Slot discharges were discovered in three phases(A, B and C) at the rated voltage. PDA and PDD test results are in accordance with the pattern and magnitude of partial discharge. This hydrogenerator stator windings were in good condition.

  • PDF

The Partial Discharge Resistances of Epoxy-Nano-and-Micro Composites

  • Lee, Chang-Hoon;Park, Jae-Jun
    • Transactions on Electrical and Electronic Materials
    • /
    • v.11 no.2
    • /
    • pp.89-91
    • /
    • 2010
  • Partial discharge (PD) resistances were investigated for three types of samples: original epoxy resins, epoxy micro composites with and without the silane processing, and mixture composites with micro and nano particles. The PD was applied to these materials using rod, gap, and plane electrodes. The partial discharge resistance found in the micro composites was better than that found in the original epoxy resin. Moreover, the mixture composites of $SiO_2$ nano and micro particles had much larger resistances than the original epoxy resin or microcomposites. It can be regarded that this excellent property was due to the fact that the nano particles have a dense structure between the micro particles.

Statistic Pattern Analysis of HFPD According to Applied Stress (인가 스트레스에 따른 HFPD의 통계적 패턴해석)

  • Kim, Duck-Keun;Lee, Eun-Suk;Jung, Young-Ill;Lim, Jang-Seub;Kim, Tae-Sung
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2000.05a
    • /
    • pp.18-22
    • /
    • 2000
  • The partial discharge testing is widely used in insulation property measurement because it gives low stress to high voltage equipment which is undertaken tests. Therefore it is very useful method compare to previous destructive methods and effective diagnosis method in power transformer that requires live-line diagnosis. But partial discharges have very complex characteristics of discharge pattern so it is required continuous research to development of precise analysis method. In recent, the study of partial discharge is carrying out discover of initial defect of power equipment through condition diagnosis and system development of degradation diagnosis using HFPD(High Frequency Partial Discharge) detection. In this study, simulated transformer is manufactured and HFPD occurred from transformer is measured with broad band antenna in real time, the degradation grade of transformer is analyzed through produced patterns in simulated transformer according to applied voltages.

  • PDF

A Study on the Sensitivities Characteristics in a PD and a HFPD (PD 측정과 HFPD의 감도특성에 관한 연구)

  • Lim, Jang-Seob;Kim, Duck-Keun
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2000.05a
    • /
    • pp.29-32
    • /
    • 2000
  • The partial discharge testing is widely used in insulation property measurement because it gives low stress to high voltage equipment which is undertaken tests. Therefore it is very useful method compare to previous destructive methods and effective diagnosis method in power transformer that requires on-line & on-site diagnosis. But partial discharges have very complex characteristics of discharge pattern so it is required continuous research to development of precise analysis method. In recent, the study of partial discharge is carrying out discover of initial defect of power equipment through condition diagnosis and system development of degradation diagnosis using HFPD(High Frequency Partial Discharge) detection. In this study, simulated transformer is manufactured and PD/HFPD occurred from transformer is measured with broad band antenna in real time, the degradation grade of transformer is analyzed through produced patterns in simulated transformer according to applied voltages.

  • PDF

Influence of Partial Discharge Properties due to Void in Cable Joint Parts (케이블 접속재 부분방전 특성에 미치는 보이드의 영향)

  • 신종열;홍진웅
    • Journal of the Korean Society of Safety
    • /
    • v.18 no.3
    • /
    • pp.69-74
    • /
    • 2003
  • To investigate the partial discharge and electric field distribution in cable joint parts, we measured the partial discharge and electric field in specimen. The specimens which cross-linked polyethylene(XLPE) and ethylene propylene diene ethylene(EPDM) are used to insulating material for underground cable md cable jointing parts. The polymers are used to insulating material in switchgear which is a kind of transformer equipment and in ultra-high voltage cable. Its using is increasing gradually, the electrical insulation properties are not only excellent but also mechanical property is excellent. And because it is possible to be made void of several type in insulator while it is produced, which the electrical field distribution is changed by void, it has a critical influence to insulator performance. The underground cable is connecting by the jointing material, insulating breakdown and the electric ageing which are caused by several mixing impurity and the damage of cable insulator layer, which reduced the life of cable while intermediate joint kit is connected. Therefore, the computer simulation is used to estimating insulator performance, XLPE is used to the insulating material of ultra-high voltage cable and EPDM is used to insulator layer in joint material kit, and which are produced as specimen. And it is analyzed the electric field concentrating distribution and partial discharge by modeling of computer simulation in void and cable joint kit.

PD Characteristics in C-GIS Using AE Sensor (AE Sensor를 적용한 C-GIS내의 PD 특성)

  • Lee, Yong-Hee;Shin, Yang-Sop;Jang, Su-Hyeong;Seo, Jung-Min;Lee, Yong-Hee;Lim, Ki-Joe
    • Proceedings of the KIEE Conference
    • /
    • 2002.07c
    • /
    • pp.1652-1654
    • /
    • 2002
  • The defects making partial discharge(PD) in a C-GIS(Cubicle Insulated Switchgear) initiate acoustic wave which can be detected using acoustic emission sensor placed outside or inside the C-GIS enclosure. In this paper, partial discharge property for 2 locations for AE sensor and 3 locations for defects in C-GIS are presented and PD waveforms were analyzed by PRPDA(Partial Resolved Partial Discharge Analysis). As a result, using post amplifier having gain of 10,000 and band pass filter having $20kHz{\sim}300kHz$, resolution of waveforms AE sensor signal by detected was good. Noise level was about 80 mV.

  • PDF

The Detection of Partial Discharge Signal by the Measurement of an Electromagnetic Wave and Pattern Recognition Technique (전자파의 측정과 패턴인식 기법에 의한 부분방전 신호 검출)

  • Kim, Yeong-No;Kim, Jae-Cheol;Seo, In-Cheol;Jeon, Yeong-Jae;Kim, Gwang-Hwa
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.51 no.6
    • /
    • pp.276-283
    • /
    • 2002
  • This Paper Presents the method for detecting a partial discharge(PD) using an electromagnetic wave measured by an antenna. The various electromagnetic waves are measured in the laboratory and wavelet transform, which is provides a direct quantitative measure of spectral content in the time-frequency domain, are applied for identifying the property of electromagnetic waves. Also, the statistical method and self-organizing feature map(SOFM) are applied for the pattern recognition of electromagnetic waves. The proposed method is shown to be useful for detecting electromagnetic waves emitted for PD in test data.

Partial Discharge Ultrasonic Analysis for Generator Stator Windings

  • Yang, Yong-Ming;Chen, Xue-Jun
    • Journal of Electrical Engineering and Technology
    • /
    • v.9 no.2
    • /
    • pp.670-676
    • /
    • 2014
  • The objective of this research is to utilize the ultrasonic method to analyze the property of partial discharge (PD) which is generated by the winding of the insulation stator in the generator. Therefore, a PD measurement system is built based on ultrasonic and virtual instruments. Three types of PD models (internal PD model, surface PD model and slot PD model) have been constructed. With the analysis of these experimental results, this research has identified the ultrasonic signals of the discharges which were produced by three types of PD models. This analysis shows the different features among these PD types. Both the time domain and frequency domain of the ultrasonic signals are obviously different. In addition, an experiment based on a large rotating machine has been done to analyze ultrasonic noises. The result indicates that the ultrasonic noises can be wiped off by the filters and algorithms. The application of this system is convenient for the detection of early signs of insulation failure, which is an effective method for diagnosis of insulation faults.

Partial Discharge Process and Characteristics of Oil-Paper Insulation under Pulsating DC Voltage

  • Bao, Lianwei;Li, Jian;Zhang, Jing;Jiang, Tianyan;Li, Xudong
    • Journal of Electrical Engineering and Technology
    • /
    • v.11 no.2
    • /
    • pp.436-444
    • /
    • 2016
  • Oil-paper insulation of valve-side windings in converter transformers withstand electrical stresses combining with AC, DC and strong harmonic components. This paper presents the physical mechanisms and experimental researches on partial discharge (PD) of oil-paper insulation at pulsating DC voltage. Theoretical analysis showed that the phase-resolved distributions of PDs generated from different insulated models varied as the increase of the applied voltages following a certain rule. Four artificial insulation defect models were designed to generate PD signals at pulsating DC voltages. Theoretical statements and experimental results show that the PD pulses first appear at the maximum value of the applied pulsating DC voltage, and the resolved PD phase distribution became wider as the applied voltage increased. The PD phase-resolved distributions generated from the different discharge models are also different in the phase-resolved distributions and development progress. It implies that the theoretical analysis is suitable for interpretation of PD at pulsating DC voltage.

Analysis of Partial Discharge Pattern according to Needle Electrode Slope in XLPE for Ultra High Voltage insulators (침 전극 기울기에 따른 초고압 절연체 XLPE의 부분방전 패턴해석)

  • Ahn, Byung-Chul;Kim, Tag-Yong;Lee, Kang-Won;Lee, Duck-Jin;Shin, Jong-Yeol;Lee, Chung-Ho;Hong, Jin-Woong
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2006.11a
    • /
    • pp.162-163
    • /
    • 2006
  • XLPE is used to insulator for Ultra High Voltage power cable. It is easy to processing also has a good insulating property. The study for diagnosis of lifetime and improvement is proceeding continuously. In this paper, it is investigated partial discharge distribution according to slope of needle electrode 0, 20, $40^{\circ}$. Applied voltage is 0.5 [kV/s] by step form for inception voltage. As the result of study, we conformed that increase of slope led to reduce of discharge number and total discharge quantity.

  • PDF