Basic Study on Flashover Characteristics of Power Lines by Forest Fire(II) (산불화재에 의한 전력선 섬락사고 기초연구(II))

  • Kim, C.N.;Lee, S.W.;Lee, K.S.;Kim, I.S.;Lee, D.I.;Park, C.S.
    • Proceedings of the KIEE Conference
    • /
    • 2001.11b
    • /
    • pp.391-394
    • /
    • 2001
  • Occurring forest fire or burning bushes beneath overhead transmission lines have caused system disturbances in many countries. In this study, various tests in the simulated condition of power lines were conducted so as to investigate the reduction in insulation strength caused by combustion flame. The results of an experimental investigation into the flashover characteristics of air dielectric strength in the presence of oil flame are reported. It is demonstrated that flame can reduce by more than half, 80% in maximum, the breakdown voltage of a model line.

  • PDF

Distribution Condition of Electrical and Magnetic Fields under Distribution Line (배전선로하의 전자계 분포 실태)

  • Jang, T.I.;Lee, J.P.;Lee, S.D.;Lee, D.I.;Yoo, Y.P.;Jeong, I.J.
    • Proceedings of the KIEE Conference
    • /
    • 2003.07a
    • /
    • pp.470-472
    • /
    • 2003
  • This paper presents the measurement results and the statistical analysis of electrical and magnetic fields in the vicinity of overhead distribution lines. The maximum values of electrical and magnetic fields are 0.042kV/m and 8.3mG. The median values are 0.005kV/m and 1.3mG. The electrical and magnetic fields of distribution lines are compared to those of transmission lines and home appliances.

  • PDF

A Study on Selection of an Overhead Electrical Transmission Line Corridor with Social Conflict (사회적 갈등을 갖는 송전선로 경과지 선정에 관한 연구)

  • Son, Hong-Chul;Moon, Chae-Joo;Kim, Hak-Jae
    • The Journal of the Korea institute of electronic communication sciences
    • /
    • v.16 no.4
    • /
    • pp.577-584
    • /
    • 2021
  • Electrical energy is an essential component in present societies, which is an important basis for our technological society. In the design of new power infrastructure, it is important to consider the psychological aspects of how our culture considers and aspects its development as an integral component of the community environment. The construction of new high voltage overhead transmission lines has become a controversial issue for public policy of government due to social opposition. The members of community are concerned about how these power lines may have an impact on their lives, basically caused by their effects on health and safety. The landscape and visual impact is one of the most impact that can be easily perceived for local community. The computer 3D simulation of new landscape is illustrated by a real life use corresponding to the selection of the power line route with least observability for local community. This paper used ArcGIS(geographic information system tool) for planning, survey, basic route and detailed route, route for implementation of transmission line corridor. Also, the paper showed the map of natural environment, living environment, safety and altitude using database of power line corridor, and transmission siting model was developed by this study. The suggested landscape of computer simulation with lowest visibility on a power line zone can contribute to reducing oppositions of local community and accelerating the construction of new power lines.

The Swing Restraint effects for Suspension I string type Jumper Devices (현수I련을 부가한 점퍼장치의 횡진억제효과 분석)

  • Sohn, H.K.;Lee, E.W.
    • Proceedings of the KIEE Conference
    • /
    • 1997.11a
    • /
    • pp.35-37
    • /
    • 1997
  • The jumper devices of overhead transmission lines are getting increased in size with the adaptation of higher voltage and bundled conductor. Incensement of jumper devices size caused to large swing angle and flashover with tower post or arm. The suspension I type string type jumper devices are used for swing restraint of suspension type. This paper is compared and analysized to its swing characteristics. The results showed that suspension I string type has a good effects.

  • PDF

An Application of Maximum Swing Angle in Dynamic Swing Characteristics for Jumper Devices (점퍼장치의 동적인 횡진특성에 대한 최대횡진각의 적용 연구)

  • Sohn, H.K.;Lee, E.W.
    • Proceedings of the KIEE Conference
    • /
    • 1999.07a
    • /
    • pp.83-85
    • /
    • 1999
  • The jumper devices of overhead power transmission lines are getting increased in size with the adoptation of higher voltage and bundled conductors. Increasement of jumper devices' size results in the cost increasement. Therefore, the adoptation of prefabricated jumper device is cost effective method in T/L. This papers are mentioned about selection of proper value of standard deviation for jumper devices by dynamic swing characteristics. And we are analyzed to effects for tower scheme and weight addition.

  • PDF

Calculation of Radiative Electric Field Intensity of Overhead Medium-Voltage Power lines for Power Line Communication (전력선통신을 위한 고압 배전선로의 방사전계강도 계산)

  • Chun Dong-wan;Park Young-jin;Kim Kwan-ho;Shin Chull-chai
    • The Journal of Korean Institute of Communications and Information Sciences
    • /
    • v.30 no.12A
    • /
    • pp.1136-1146
    • /
    • 2005
  • In this paper, the radiative electric field intensity due to the communication signal and conductive noise is calculated in overhead medium voltage power lines for power line communication. The input impedance is calculated by means of 2 port equivalent model of medium voltage power line network and basic transmission line theory. And then, currents is calculated by calculated input impedance and finally, the emissive electric field is calculated. The input impedance appears like a standing wave form with a fixed cycle because high reflection at the input terminal due to the characteristic impedance of medium voltage power line is very large. A calculated current and radiative electric field also appears like this form. From the measurement results, the measured results are very similar to the calculated results.

Ion Effects of HVDC ±500 kV Double Bipole Overhead Transmission Line with Metallic Return Conductor Using Full-scale Test Line (실증시험선로를 이용한 도체귀로형 HVDC ±500 kV Double Bipole 가공송전선로의 이온류 특성 평가)

  • Shin, Kooyong;Kwon, Gumin;Ju, Munno;Woo, Jeong Min
    • KEPCO Journal on Electric Power and Energy
    • /
    • v.5 no.4
    • /
    • pp.249-256
    • /
    • 2019
  • A full-scale test line was established to verify the electrical environmental interferences caused by the HVDC ±500 kV Double Bipole overhead transmission line with metallic return conductor, which is scheduled for construction in Korea and the fullscale test was conducted for one year. And through the human perception test of the DC electric-field under the HVDC Double Bipole line, the threshold value at which the human detects DC electric field was investigated to verify the validity of the design guide for the HVDC ±500 kV Double Bipole overhead transmission line. The polarity configuration of the HVDC ±500 kV Double Bipole test line was arranged diagonally with the same polarity in terms of the electrical environment disturbance and operation. The test line utilized the 6-bundle arrangement to prevent the corona discharge taking into account the domestic social acceptability. The test results show that the HVDC ±500 kV Double Bipole transmission line generated very little corona discharge from the conductors. Therefore, both DC electric field and ion current density met the domestic design guide for DC overhead transmission lines. Also, the human perception test of DC electric fields under the test line showed that 70% of participants did not recognize the DC electric field even when exposed to 23 kV/m.

Surface Ageing Property of Polymer Insulator for Transmission line with Forest Fire Test (송전용 폴리머 애자의 산불 모의시험에 따른 표면열화 특성)

  • Cho, Han-Goo;Kim, Kyang-Young
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2010.06a
    • /
    • pp.110-110
    • /
    • 2010
  • Suspension insulator have made use of porcelain insulator mainly, but polymer insulator is using recently. Polymer suspension insulator have advantage that it is light than porcelain insulator. The ageing performance is excellent and it is possible for mass production. There is high possibility of mountain fire because a lot of potential inflammables such as fallen leaves are stacked on the ground Therefore surface aging of polymer insulator most of the overhead transmission lines in Korea are operated on the mountain need analysis of transmission line into forest fire. surface aging property is analyzed by SEM, EDX, XPS, FTIR, DSC in this paper.

  • PDF

On Setting Method of the operating Parameters of SFCL in Transmission Systems Considering Power Protection Relay (계통보호릴레이와의 협조를 고려한 SFCL의 동작파라메타 설정방법에 대한고찰)

  • Hong, Won-Pyo
    • Proceedings of the KIEE Conference
    • /
    • 1998.07c
    • /
    • pp.1231-1234
    • /
    • 1998
  • Design & Operation of power system for meeting increase of electric power demand is becoming more difficult and complex. One of reasons is increase of fault current. As one of the most effective methods for suppressing the fault current, installation of SFCL is expected. This paper describes a method of fault analyses of power system with SFCLs, and also discusses determination of specification of SFCLs, effects of limiting the fault current due to SFCLs by use of the model system of two - bus electric power system with parallel circuit model transmission line. Also, describes the definition of six specific parameters of SFCL for power system application & a proposal of design method of specific parameter of a resistance type SFCL in overhead transmission lines considering operation of protective relays.

  • PDF

A Study on Utilization Ratio and Operation of Transmission Lines (송전선로의 이용률 평가 및 합리적 운영에 관한 연구)

  • Kim, Dong-Min;Bae, In-Su;Cho, Jong-Man;Kim, Jin-O
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.55 no.10
    • /
    • pp.426-432
    • /
    • 2006
  • This paper describes the concepts of Static Line Rating (SLR) and Dynamic Line Rating (DLR) and the computational methods to demonstrate them. Calculation of the line capacity needs the heat balance equation which is also used for computing the reduced tension in terms of line aging. SLR is calculated with the data from the worst condition of weather throughout the year. Even now, the utilization ratio is obtained from this SLR data in Korea. DLR is the improved method compared to SLR. A process for DLR reveals not only improved line ratings but also more accurate allowed line ratings based on line aging and real time conditions of weather. In order to reflect overhead transmission line aging in DLR, this paper proposes the method that considers the amount of decreased tension since the lines have been installed. Therefore, the continuous allowed temperature for remaining life time is newly acquired. In order to forecast DLR, this paper uses weather forecast models, and applies the concept of Thermal Overload Risk Probability (TORP). Then, the new concept of Dynamic Utilization Ratio (DUR) is defined, replacing Static Utilization Ratio (SUR). For the case study, the two main transmission lines which are responsible for the north bound power flow in the Seoul metropolitan area are chosen for computing line rating and utilization ratio. And then line rating and utilization ratio are analyzed for each transmission line, so that comparison of the present and estimated utilization ratios becomes available. Finally, this paper proves the validity of predictive DUR as the objective index, with simulations of emergency state caused by system outages, overload and so on.