Abstract
In this paper, the radiative electric field intensity due to the communication signal and conductive noise is calculated in overhead medium voltage power lines for power line communication. The input impedance is calculated by means of 2 port equivalent model of medium voltage power line network and basic transmission line theory. And then, currents is calculated by calculated input impedance and finally, the emissive electric field is calculated. The input impedance appears like a standing wave form with a fixed cycle because high reflection at the input terminal due to the characteristic impedance of medium voltage power line is very large. A calculated current and radiative electric field also appears like this form. From the measurement results, the measured results are very similar to the calculated results.
본 논문에서는 전력선 통신을 위해 사용되는 고압 배전선로에서 통신신호 및 잡음신호에 의해 방사되는 방사전계강도를 계산하였다. 전력선 통신 네트워크의 2포트 등가모델 및 기본적인 전송선로 이론을 이용해 입력임피던스를 계산하였다. 그리고 계산된 입력임피던스를 이용해 전력선상 전류를 계산하고 최종적으로 방사전계강도를 계산하였다. 전력선의 특성임피던스가 매우커서 입력 단에서의 반사가 심하기 때문에 입력임피던스는 일정한 주기를 가지는 정재파 형태를 가진다. 계산된 전류 및 방사전계 또한 이러한 형태임을 알 수 있었다. 실제 측정한 결과계산 치와 측정치가 매우 유사함을 알 수 있었다.