On Setting Method of the operating Parameters of SFCL in Transmission Systems Considering Power Protection Relay

계통보호릴레이와의 협조를 고려한 SFCL의 동작파라메타 설정방법에 대한고찰

  • Published : 1998.07.20

Abstract

Design & Operation of power system for meeting increase of electric power demand is becoming more difficult and complex. One of reasons is increase of fault current. As one of the most effective methods for suppressing the fault current, installation of SFCL is expected. This paper describes a method of fault analyses of power system with SFCLs, and also discusses determination of specification of SFCLs, effects of limiting the fault current due to SFCLs by use of the model system of two - bus electric power system with parallel circuit model transmission line. Also, describes the definition of six specific parameters of SFCL for power system application & a proposal of design method of specific parameter of a resistance type SFCL in overhead transmission lines considering operation of protective relays.

Keywords