슬래브축열의 최적축열시간 산정 : 구배법 알고리즘에 의한 해석 (An Analysis of the Optimal Thermal Storage Time of Air-Conditioning System with Slab Thermal Storage : An Analysis by the Gradient Method Algorithm)

  • 정재훈
    • 설비공학논문집
    • /
    • 제20권10호
    • /
    • pp.702-709
    • /
    • 2008
  • In this paper, the optimal thermal storage time of an air-conditioning system with slab thermal storage in office building was analyzed on the basis of the gradient method algorithm. The sum of room temperature deviation and heat extraction rate was set to the criterion function. It was calculated that four hours is the optimal thermal storage time under the standard evaluation criterion. Furthermore, some case studies were executed by controlling ratio of weight functions of room temperature deviation and heat extraction rate in criterion function. It is possible to design many kinds of optimal operation of an air-conditioning system with slab thermal storage by controlling ratio of the weight functions in criterion function.

구배법 알고리즘에 의한 슬래브축열의 최적제어 해석 (An Analysis of the Optimal Control of Air-Conditioning System with Slab Thermal Storage by the Gradient Method Algorithm)

  • 정재훈
    • 설비공학논문집
    • /
    • 제20권8호
    • /
    • pp.534-540
    • /
    • 2008
  • In this paper, the optimal bang-bang control problem of an air-conditioning system with slab thermal storage was formulated by gradient method. Furthermore, the numeric solution obtained by gradient method algorithm was compared with the analytic solution obtained on the basis of maximum principle. The control variable is changed uncontinuously at the start time of thermal storage operation in an analytic solution. On the other hand, it is showed as a continuous solution in a numeric solution. The numeric solution reproduces the analytic solution when a tolerance for convergence is applied severely. It is conceivable that gradient method is effective in the analysis of the optimal bang-bang control of the large-scale system like an air-conditioning system with slab thermal storage.

슬래브축열의 최적제어방책에 관한 연구 -평가요소로 복사열의 고려 유무에 의한 차이- (A Study on the Optimal Control Strategy of Air-Conditioning System with Slab Thermal Storage - The Difference by the Presence of Radiant Heat as a Criterion Factor -)

  • 정재훈;신영기
    • 설비공학논문집
    • /
    • 제18권4호
    • /
    • pp.287-296
    • /
    • 2006
  • In this paper, optimal control strategy of the air-conditioning system with slab thermal storage was investigated based on the optimal control theory. An optimal heat output to the plenum chamber and the air-conditioned room was determined based on two kinds of criterion functions. The first one requires small deviation in room air temperature from a set-point value and low energy consumption. It is shown that the optimized control is to store heat through the whole storage time and to increase storage rate gradually with time. As the second case, a criterion that both a deviation of operative temperature from a set-point temperature and the energy consumption should be minimized was adopted. The room air temperature was a little high and the cooling load during storage time was reduced, compared with the results when a criterion function considering only the room air temperature is used.

슬래브축열의 최적제어방책에 관한 연구 -평가함수의 선택이 결과에 미치는 영향- (A Study on the Optimal Control Strategy of Air-Conditioning System with Slab Thermal Storage - Results Influenced by the Choice of a Criterion Function -)

  • 정재훈;신영기
    • 설비공학논문집
    • /
    • 제18권11호
    • /
    • pp.896-905
    • /
    • 2006
  • An optimal control of an air-conditioning system with slab thermal storage is investigated by making use of the Maximum Principle. An optimal heat input to a plenum chamber and an air-conditioned room is determined by minimizing a criterion function which is given as integral sum of two terms. The first term is the square of the deviation in the room air temperature from the set-point value, and the second is the absolute value of the heat input. The result indicates that it tries to keep a room air temperature in set-point value by heating as much as possible at the time of a setup of a room air temperature or just before that, in order to avoid a heat loss arising at the time of the non-air conditioning. The result is compared with that of the case when the square of the heat input is used as a criterion.

신재생에너지 단독주택 모델 냉방운전의 선형계획법 기반 운전 최적화 연구 (Optimal Cooling Operation of a Single Family House Model Equipped with Renewable Energy Facility by Linear Programming)

  • 신영기;김의종;이경호
    • 설비공학논문집
    • /
    • 제29권12호
    • /
    • pp.638-644
    • /
    • 2017
  • Optimal cooling operation algorithm was developed based on a simulation case of a single family house model equipped with renewable energy facility. EnergyPlus simulation results were used as virtual test data. The model contained three energy storage elements: thermal heat capacity of the living room, chilled water storage tank, and battery. Their charging and discharging schedules were optimized so that daily electricity bill became minimal. As an optimization tool, linear programming was considered because it was possible to obtain results in real time. For its adoption, EnergyPlus-based house model had to be linearly approximated. Results of this study revealed that dynamic cooling load of the living room could be approximated by a linear RC model. Scheduling based on the linear programming was then compared to that by a nonlinear optimization algorithm which was made using GenOpt developed by a national lab in USA. They showed quite similar performances. Therefore, linear programming can be a practical solution to optimal operation scheduling if linear dynamic models are tuned to simulate their real equivalents with reasonable accuracy.

저 에너지형 축냉식 저온유통 시스템 개발 (Development of Cold Chain System Using Thermal Storage with Low-Energy Type)

  • 권기현;정진웅;김종훈;최창현
    • Journal of Biosystems Engineering
    • /
    • 제31권3호
    • /
    • pp.161-167
    • /
    • 2006
  • The purpose of this study is to find the optimal conditions of PCM slurry manufacturing equipment for saving the marketing cost and keeping the original quality of products. In addition, the characteristics of the movable container for shipping or distributing products is analysed. The major results are as follows. 1. PCM thermal storage system is designed with the conditions of temperature($-5{\sim}10^{\circ}C$), cold chain time(30 minutes), and one time usage(50 liter). This system includes tank, freezer, circulating pump, cycle type heat exchanger, swelling tank, equipment of supplying PCM supplying unit includes cold tank, cycle type heat exchanger, suction unit and control equipments, etc. 2. After ability test of PCM thermal storage system, it shows that the required freezing time of PCM thermal storage system is less than one of the previous system. The reason is that churn (top and bottom) and compulsion circulation are occurred simultaneously and unit cooler type method is better than chiller type method. 3. By the experiment of transportation latent heat container, it is decided that the best container is $K_1$ with latent heat temperature($0{\sim}5^{\circ}C$) and density(0.15%). However, for $K_l\;and\;K_2$, it is necessary more studies on latent heat thermal conditions and conditions of making method.

건물용 열병합발전 설비를 중심으로 한 종합 에너지 시스템의 최적 일간 운전모형 수립에 관한 연구 (A Study on Daily Operation Model for Total Energy System Including Building Cogeneration, Ice Storage, Thermal and Electrical Storage Facilities)

  • 박종성;장승찬;심건보;김정훈;고요
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1996년도 하계학술대회 논문집 B
    • /
    • pp.724-726
    • /
    • 1996
  • In this paper, we propose an optimal daily operation model for the total energy system which includes cogeneration, thermal storage and electrical charger and ice storage facilities. Storing and utilizing the surplus thermal and electrical energy, the daily operation cost could be reduced and more efficient use of thermal energy could be achieved. The ice storage cooling system has a merit of reduce the electricity cost by time of day rate(peak/off-peak). And also, refrigerator can be down sized compare to the other cooling system From this model, operation costs of the sample cogeneration system with/without auxiliary facilities are obtained and compared to each other. In case study, the sensitivity of operating cost is simulated according to the variation of cogeneration production cost, electricity rate, etc.

  • PDF

키토산 섬유를 담체로 이용한 라이소자임 효소의 고정화 (Immobilization of Lysozyme from Hen Egg by Crosslinking Method onto Chitosan Non-woven)

  • 이소희
    • 한국염색가공학회지
    • /
    • 제30권4호
    • /
    • pp.264-274
    • /
    • 2018
  • Immobilization of lysozyme on chitosan non-woven using glutaraldehyde(GA) was investigated. For this, 100 % chitosan non-woven was prepared as novel support for the enzyme immobilization. In addition, free lysozyme activity was examined depending on various pH and temperature by measuring time. Moreover, the optimum immobilization conditions depending on various pH, temperature, immobilization time and lysozyme concentration was evaluated. In addition, thermal stability and storage stability of immobilized lysozyme were measured. The characteristics of immobilized lysozyme was examined by FT-IR, surface morphology, and MTT assay. The results are follows: the optimal immobilization of lysozyme were pH 7.0, $25^{\circ}C$, lysozyme concentration 1.5 mg/ml, immobilization time 240 min. The immobilized lysozyme showed higher thermal stability than the free trypsin. The immobilized lysozyme activity was retained 80 % of its initial activity at $4^{\circ}C$ over 30 days of storage. The lysozyme was immobilized effectively on chitosan non-woven by observation of surface morphology.

Exergetic design and analysis of a nuclear SMR reactor tetrageneration (combined water, heat, power, and chemicals) with designed PCM energy storage and a CO2 gas turbine inner cycle

  • Norouzi, Nima;Fani, Maryam;Talebi, Saeed
    • Nuclear Engineering and Technology
    • /
    • 제53권2호
    • /
    • pp.677-687
    • /
    • 2021
  • The tendency to renewables is one of the consequences of changing attitudes towards energy issues. As a result, solar energy, which is the leader among renewable energies based on availability and potential, plays a crucial role in full filing global needs. Significant problems with the solar thermal power plants (STPP) are the operation time, which is limited by daylight and is approximately half of the power plants with fossil fuels, and the capital cost. Exergy analysis survey of STPP hybrid with PCM storage carried out using Engineering Equation Solver (EES) program with genetic algorithm (GA) for three different scenarios, based on eight decision variables, which led us to decrease final product cost (electricity) in optimized scenario up to 30% compare to base case scenario from 28.99 $/kWh to 20.27 $/kWh for the case study. Also, in the optimal third scenario of this plant, the inner carbon dioxide gas cycle produces 1200 kW power with a thermal efficiency of 59% and also 1000 m3/h water with an exergy efficiency of 23.4% and 79.70 kg/h with an overall exergy efficiency of 34% is produced in the tetrageneration plant.

해석적 비용함수와 최대원리리에 의한 양수운전을 포함하는 최적전원계획 (Optimal Generation Planning Including Pumped-Storage Plant Based on Analytic Cost Function and Maximum Principle)

  • 박영문;이봉용
    • 대한전기학회논문지
    • /
    • 제34권8호
    • /
    • pp.308-316
    • /
    • 1985
  • This paper proposes an analytic tool for long-term generation expansion planning based on the maximum principle. Many research works have been performed in the field of generation expansion planning. But few works can be found with the maxinmum principle. A recently published one worked by professor Young Moon Park et al. shows remarkable improvements in modeling and computation. But this modeling allows only thermal units. This paper has extended Professor Park's model so that the optimal pumped-storage operation is taken into account. So the ability for practical application is enhanced. In addition, the analytic supply-shortage cost function is included. The maximum principle is solved by gradient search due to its simplicity. Every iteration is treated as if mathematical programming such that all controls from the initial to the terminal time are manipulated within the same plane. Proposed methodology is tested in a real scale power system and the simulation results are compared with other available package. Capability of proposed method is fully demonstrated. It is expected that the proposed method can be served as a powerful analytic tool for long-term generation expansion planning.

  • PDF