Browse > Article

A Study on the Optimal Control Strategy of Air-Conditioning System with Slab Thermal Storage - The Difference by the Presence of Radiant Heat as a Criterion Factor -  

Jung Jae-Hoon (Sejong-Lockheed Martin Aerospace Research Center, Sejong University)
Shin Young-Gy (Department of Mechanical Engineering, Sejong University)
Publication Information
Korean Journal of Air-Conditioning and Refrigeration Engineering / v.18, no.4, 2006 , pp. 287-296 More about this Journal
Abstract
In this paper, optimal control strategy of the air-conditioning system with slab thermal storage was investigated based on the optimal control theory. An optimal heat output to the plenum chamber and the air-conditioned room was determined based on two kinds of criterion functions. The first one requires small deviation in room air temperature from a set-point value and low energy consumption. It is shown that the optimized control is to store heat through the whole storage time and to increase storage rate gradually with time. As the second case, a criterion that both a deviation of operative temperature from a set-point temperature and the energy consumption should be minimized was adopted. The room air temperature was a little high and the cooling load during storage time was reduced, compared with the results when a criterion function considering only the room air temperature is used.
Keywords
Slab thermal storage; Optimal control theory; Radiant heat; Operative temperature;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 Lim, J. H., Lee, S. H., Cha, Y. H., Chung, K. S. and Yee, J. J., 2003, A study on the indoor environment characteristics of air conditioning system with thermal storage capacity in slab - In the case of winter heating only, Proceedings of the SAREK 2003 Summer Annual Conference, pp.1017-1022
2 Jung, J. H., 2004, Fundamental study into optimized control for air-conditioning system with floor thermal storage, Ph.D. thesis, University of Kyoto, Kyoto, Japan
3 Shinkai, K. I., Kasuya, A. and Kato, M. H., 2000, Performance Evaluation of Floor Thermal Storage System, ASHRAE Transactions, Vol. 106, No.1, pp.311-316
4 Kwakernaak, H. and Sivan, R., 1972, Linear Optimal Control Systems, Wiley Interscience
5 Urabe, W., Hokoi, S. I., Shinmura, K. I., Shinkai, K. I. and Kasuya, A., 1997, Thermal behavior in air conditioning system utilizing building thermal storage - Proposing analysis model and comparing with experiment, Summaries of Technical Papers of Annual Meeting Architectural Institute of Japan, Environmental Engineering II, pp.215-216
6 Roh, H. W. and Udagawa, M. H., 2001, Simulation study on the performance of a fabric heat storage system, Transactions of AU, No. 544, pp.31-38
7 Jung, J H., Hokoi, S. I. and Urabe, W., 1999, Fundamental study into optimized control for air-conditioning system with floor thermal storage based on optimal control theory, Transactions of AU, No. 520, pp.33-39
8 Jung, J. H. and Shin, Y. G., 2005, An experimental study on thermal storage performance of an air conditioning system with slab thermal storage, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 17, No.5, pp.427-435   과학기술학회마을