A Study on the Optimal Control Strategy of Air-Conditioning System with Slab Thermal Storage - Results Influenced by the Choice of a Criterion Function -  

Jung, Jae-Hoon (Advanced Building Science and Technology Research Center, Yonsei University)
Shin, Young-Gy (Department of Mechanical Engineering, Sejong University)
Publication Information
Korean Journal of Air-Conditioning and Refrigeration Engineering / v.18, no.11, 2006 , pp. 896-905 More about this Journal
Abstract
An optimal control of an air-conditioning system with slab thermal storage is investigated by making use of the Maximum Principle. An optimal heat input to a plenum chamber and an air-conditioned room is determined by minimizing a criterion function which is given as integral sum of two terms. The first term is the square of the deviation in the room air temperature from the set-point value, and the second is the absolute value of the heat input. The result indicates that it tries to keep a room air temperature in set-point value by heating as much as possible at the time of a setup of a room air temperature or just before that, in order to avoid a heat loss arising at the time of the non-air conditioning. The result is compared with that of the case when the square of the heat input is used as a criterion.
Keywords
Slab thermal storage; Optimal control; Maximum principle; Criterion function;
Citations & Related Records
Times Cited By KSCI : 2  (Citation Analysis)
연도 인용수 순위
1 Roh, H. W. and Udagawa, M. H., 2001, Simulation study on the performance of a fabric heat storage system, Transactions of AIJ, No. 544, pp.31-38
2 Pontryagin, L. S., Boltyanskii, V. G., Gamkrelidze, R. V. and Mishchenko, E. F., 1986, L. S. Pontryagin selected works, Volume 4, The mathematical theory of optimal processes, Gordon and Breach Science Publishers
3 Kwakernaak, H. and Sivan, R., 1972, Linear optimal control systems, Wiley Interscience
4 Jung, J. H. and Shin, Y. G., 2005, An Experimental study on thermal storage performance of an air conditioning system with slab thermal storage, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 17, No.5, pp.427-435   과학기술학회마을
5 Jung, J. H., 2004, Fundamental study into optimized control for air-conditioning system with floor thermal storage, Ph.D. thesis, University of Kyoto, Kyoto, Japan
6 lung, J. H., Rokoi, S.I. and Urabe, W., 1999, Fundamental study into optimized control for air-conditioning system with floor thermal storage based on optimal control theory, Transactions of AIJ, No. 520, pp.33-39
7 Shinkai, K. I., Kasuya, A. and Kato, M. H., 2000, Performance evaluation of floor thermal storage system, ASHRAE Transactions, Vol. 106, No.1, pp.311-316
8 Jung, J. H. and Shin, Y. G., 2006, A study on the optimal control strategy of air-conditioning system with slab thermal storage, The difference by the presence of radiant heat as a criterion factor, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 18, No.4, pp.287-296   과학기술학회마을
9 Lim, J. H., Lee, S. R., Cha, Y. R., Chung, K. S. and Yee, J. J, 2003, A study on the indoor environment characteristics of air conditioning system with thermal storage capacity in slab - In the case of winter heating only, Proceedings of the SAREK 2003 Summer Annual Conference, pp. 1017-1022