• Title/Summary/Keyword: Magneto-flow-thermal

Search Result 7, Processing Time 0.025 seconds

Temperature Rise Prediction of 145kV 40kA Three-phase GIS Bus Bar (145kV 40kA 3상 GIS 모선의 온도상승 예측)

  • Kim, Joong-Kyoung;Lee, Ji-Yeon;Jung, Sang-Yong;Hahn, Sung-Chin
    • Proceedings of the KIEE Conference
    • /
    • 2008.07a
    • /
    • pp.842-843
    • /
    • 2008
  • Many works on the temperature prediction of power apparatus have usually done by coupled magneto-thermal analysis. However, this method can not consider the internal gas or oil flow in the power apparatus. This paper proposes a new coupled magneto-thermal-flow analysis considering Navier-Stokes equations. The convection heat transfer coefficient is calculated analytically and is applied to the boundary condition to the proposed method. Temperature distribution of 145kV 40kA three-phase GIS bus bar model is obtained by coupled magneto-thermal-flow analysis and shows good agreement with the experimental data.

  • PDF

Temperature Rise Prediction of GIS Bus Bar Considering Thermal Flow (열유동을 고려한 GIS 모선의 온도상승 예측)

  • Kim, Joong-Kyoung;Oh, Yeon-Ho;Lee, Ji-Yeon;Hahn, Sung-Chin
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.58 no.4
    • /
    • pp.742-747
    • /
    • 2009
  • Many works on the temperature distribution of power apparatus have usually done by coupled magneto-thermal analysis. Such a method can not consider the internal gas or oil flow in the power apparatus such as gas insulated switchgear, GIS bus bar, and power transformer. Moreover it can not show the internal temperature distribution of the power apparatus exactly. This paper proposes a coupled magneto-thermal-flow analysis considering Navier-Stokes equations. The convection heat transfer coefficient is calculated analytically by applying Nusselt number for natural convection and is applied to the boundary condition of proposed method. Temperature distribution of the GIS bus bar model considering thermal flow is obtained by the proposed method and shows good agreement with the experimental data.

A 3-D Steady-State Analysis of Thermal Behavior in EHV GIS Busbar

  • Lei, Jin;Zhong, Jian-ying;Wu, Shi-jin;Wang, Zhen;Guo, Yu-jing;Qin, Xin-yan
    • Journal of Electrical Engineering and Technology
    • /
    • v.11 no.3
    • /
    • pp.781-789
    • /
    • 2016
  • Busbar has been used as electric conductor within extra high voltage (EHV) gas insulated switchgear (GIS), which makes EHV GIS higher security, smaller size and lower cost. However, the main fault of GIS is overheating of busbar connection parts, circuit breaker and isolating switch contact parts, which has been already restricting development of GIS to a large extent. In this study, a coupled magneto-flow-thermal analysis is used to investigate the thermal properties of GIS busbar in steady-state. A three-dimensional (3-D) finite element model (FEM) is built to calculate multiphysics fields including electromagnetic field, flow field and thermal field in steady-state. The influences of current on the magnetic flux density, flow velocity and heat distribution has been investigated. Temperature differences of inner wall and outer wall are investigated for busbar tank and conducting rod. Considering the end effect in the busbar, temperature rise difference is compared between end sections and the middle section. In order to obtain better heat dissipation effect, diameters of conductor and tank are optimized based on temperature rise simulation results. Temperature rise tests have been done to validate the 3-D simulation model, which is observed a good correlation with the simulation results. This study provides technical support for optimized structure of the EHV GIS busbar.

Topology Optimization of Magneto-thermal Systems Considering Eddy Current as Joule Heat (와전류를 열원으로 고려한 자계-열계 위상최적설계)

  • Shim, Ho-Kyung;Wang, Se-Myung;Hameyer, Kay
    • Proceedings of the KIEE Conference
    • /
    • 2006.07b
    • /
    • pp.651-652
    • /
    • 2006
  • This research presents a topology optimization for manipulating the main heat flow in coupled magneto-thermal systems. The heat generated by eddy currents is considered in the design domain assuming an adiabatic boundary. For a practical optimization, the convection condition is considered in the topological process of the thermal field. Topology design sensitivity is derived by employing the discrete system equations combined with the adjoint variable method. As numerical examples, a simple iron and a C-core design heated-up by eddy currents demonstrate the strength of the proposed approach to solve the coupled problem.

  • PDF

Multi-objective Topology Optimization of Magneto-Thermal Problem considering Heat Flow Rate (열 유입률을 고려한 자계-열계 다목적 위상최적설계)

  • Shim, Ho-Kyung;Wang, Se-Myung;Moon, Hee-Gon;Hameyer, Kay
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.138-139
    • /
    • 2007
  • This research provides machine designers with some intuition to consider both, magnetic and heat transfer effects. A topological multi-objective function includes magnetic energy and heat inflow rate to the system, which equals to the total heat dissipation by conduction and convection. For the thermal field regarding the heat inflow, introduced as a reaction force, topology design sensitivity is derived by employing discrete equations. The adjoint variable method is used to avoid numerous sensitivity evaluations. As a numerical example, a C-core design excited by winding current demonstrates the strength of the multi-physical approach.

  • PDF

Thermal-magneto-mechanical stability analysis of single-walled carbon nanotube conveying pulsating viscous fluid

  • R. Selvamani;M. Mahaveer Sree Jayan;Marin Marin
    • Coupled systems mechanics
    • /
    • v.12 no.1
    • /
    • pp.21-40
    • /
    • 2023
  • In thisstudy, the vibration problem ofthermo elastic carbon nanotubes conveying pulsating viscous nano fluid subjected to a longitudinal magnetic field is investigated via Euler-Bernoulli beam model. The controlling partial differential equation of motion is arrived by adopting Eringen's non local theory. The instability domain and pulsation frequency of the CNT is obtained through the Galerkin's method. The numerical evaluation of thisstudy is devised by Haar wavelet method (HWM). Then, the proposed model is validated by analyzing the critical buckling load computed in presentstudy with the literature. Finally, the numerical calculation ofsystem parameters are shown as dispersion graphs and tables over non local parameter, magnetic flux, temperature difference, Knudsen number and viscous parameter.

Optimum design analysis of ICP(Inductively Coupled Plasma) torch for high enthalpy thermal plasma flow (고엔탈피 열유동 발생용 고주파 유도결합 플라즈마 토치의 최적 설계변수 해석)

  • Seo, Jun-Ho
    • Journal of the Korean Society for Aeronautical & Space Sciences
    • /
    • v.40 no.4
    • /
    • pp.316-329
    • /
    • 2012
  • In this paper, optimum design process of ICP (Inductively Coupled Plasma) torch, which has been used widely in aerospace application, such as supersonic plasma wind tunnel, is presented. For this purpose, the behaviors of equivalent circuit parameters (equivalent resistance and inductance, coupling efficiency) were investigated according to the variations of torch design parameters (frequency, $f$, confinement tube radius, $R$ and coil turn numbers, $N$) in the basis of analytical and numerical MHD (Magneto Hydro-Dynamics) models combined with electrical circuit theory. From the results, it is found that equivalent resistance is increased with the increase of $f$ values but vice versa for equivalent inductance. For elevated values of $R$ and $N$, however, both parameters tend to increase. Based on these observations, ICP torch with a power level of 10 kW can be optimized at the design ranges of $f$=4~6 MHz, $R$=17~25 mm and $N$=3~4 to maximize the electrical coupling efficiency, which is the ratio of equivalent resistance to equivalent inductance.