Browse > Article

Temperature Rise Prediction of GIS Bus Bar Considering Thermal Flow  

Kim, Joong-Kyoung ((주)효성 중공업PG 중공업연구소)
Oh, Yeon-Ho (한국전기연구원)
Lee, Ji-Yeon (동아대 공대 전기공학과)
Hahn, Sung-Chin (동아대 공대 전기공학과)
Publication Information
The Transactions of The Korean Institute of Electrical Engineers / v.58, no.4, 2009 , pp. 742-747 More about this Journal
Abstract
Many works on the temperature distribution of power apparatus have usually done by coupled magneto-thermal analysis. Such a method can not consider the internal gas or oil flow in the power apparatus such as gas insulated switchgear, GIS bus bar, and power transformer. Moreover it can not show the internal temperature distribution of the power apparatus exactly. This paper proposes a coupled magneto-thermal-flow analysis considering Navier-Stokes equations. The convection heat transfer coefficient is calculated analytically by applying Nusselt number for natural convection and is applied to the boundary condition of proposed method. Temperature distribution of the GIS bus bar model considering thermal flow is obtained by the proposed method and shows good agreement with the experimental data.
Keywords
GIS bus bar; Convection heat transfer coefficient; Flow field analysis; Temperature rise prediction;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
Times Cited By SCOPUS : 0
연도 인용수 순위
1 H. Sadakuni, K. Sasamori, H. Hama, K. Inami, 'Insulation and Current Carrying Design for GIS', JIEE, SP-96-12, pp. 33-42, 1996
2 W. Z Black, B. A. Bush, R. T. Coneybeer, ate and Ampacity of Busbar', IEEE Trans. on Power Delivery, Vol. 9, No.4, pp. 1822-1829, 1994. 10   DOI   ScienceOn
3 이경행, '초고압 전력기기의 기술 동향', 대한전기학회지, 제46권, 제8호, pp. 22-30, 1997.10
4 한국전기연구원, '765kV급 GIS용 차단부 설계 및 제조 기술 개발', 한국전력공사, 1999
5 김중경, '전자계-열계-유동계 결합해석에의한 GIS모선의 온도상승 예측', 동아대학교, 박사학위논문, 2008
6 여운동, 정의섭, 박경엽, '2003년 기술산업정보분석 : 초고압 GIS', 한국과학기술정보연구원, 2003
7 M. Necati Ozisik, 'Heat Transfer a Basic Approach', McGraw-Hill Publishing Company, 1990
8 김중경, 한성진, '해석적 기법을 이용한 초고압 GIS용 삼상모선의 온도분포 해석', 대한전기학회지, 제55B권, 제4호, pp. 196-202, 2006. 4   과학기술학회마을